Air gap separation: one-inch and two-inch minimums
An air gap is the open vertical space between a water outlet and the flood rim of the tank or fixture under it. Greenville Water and Spartanburg Water set that space at twice the outlet diameter and no smaller than one inch. Anderson’s definition sets it at twice the diameter and no smaller than two inches. The letter from the utility names the protection on the account.
Sources checked October 28, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is how to tell an air gap from a double check, a reduced pressure assembly, and a residential dual check. Double check versus reduced pressure is the hazard split those assemblies follow. This page is the air gap itself: the minimum each manual prints, and the separate gap on a relief-valve drain.
Two gaps, measured on different parts
A supply air gap is the open space under a pipe or faucet, above the flood rim of the receptacle. A relief-valve air gap is the open space between the discharge opening on a reduced pressure assembly and the drain piping that catches that discharge. Greenville Water, Spartanburg Water, and Anderson each print both ideas. The inch floors are not one shared number, and the part being measured changes which sentence applies.
R.61-58.7(F) uses the words “air gap separation” for a high hazard. Section (4) of that rule, read on October 28, 2026, does not print an inch minimum for the separation.
What the state rule assigns
Section (4)(a) calls a high hazard a connection to a service or other water system that has or may have any material dangerous to health, handled under pressure or subject to negative pressure. Protection is an air gap separation or an approved reduced pressure principle backflow prevention assembly.
Section (4)(b) says reduced pressure principal backflow prevention assemblies are not installed where flooding is possible. That includes a pit or vault without a gravity drain to the ground surface that can pass more water than the relief valve discharges. That sentence is about the drain. It does not print the one-inch or two-inch floors below.
Section (2) is the low-hazard minimum: an approved double check valve assembly or a pressure vacuum breaker, except the residential lawn policy in section (3). The low-hazard sentence does not name an air gap.
Section (5) sends a high-hazard fire sprinkler system back to section (4). The rule’s examples include antifreeze systems, foam systems, and systems charged from or tied into a pond, lake, stream, or any source other than the approved public supply. Other fire-line sprinkler systems are protected by an approved double check valve assembly. How the three manuals apply that split, including where a fire sentence names an air gap and where it names only an assembly, is below and on Fire-line backflow.
Section (7) is the certified test. It names a double check valve assembly, a pressure vacuum breaker, and a reduced pressure principle assembly. It does not name an air gap in that list. The annual test of those assemblies is What is backflow testing.
The supply minimum each manual prints
| Source | What the definition measures | Minimum |
|---|---|---|
| Greenville Water, definition (1) | The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet and the flood rim of the receptacle. | At least twice the diameter of the water supply outlet, and never less than one inch. |
| Spartanburg Water, definition (1) | The same vertical distance. The sentence says “receptor, and/or the flood rim.” | At least twice the diameter of the water supply outlet, and never less than one inch. |
| Anderson, appendix definition | The same vertical distance, measured to the flood level rim. The sentence includes water or waste, and “or other assembly.” | At least twice the diameter of the water supply outlet, and never less than two inches. |
Greenville Water’s manual (PDF created November 10, 2025) lists the air gap as the first type under “backflow prevention assembly,” with the reduced pressure principle assembly, the double check valve assembly, the double detector check, and the residential dual check. Spartanburg Water’s manual revised June 4, 2026 (PDF created June 5, 2026) lists it the same way and adds a pressure vacuum breaker in that definition list. Anderson’s September 2008 policy puts the two-inch definition in the appendix and uses “flood level rim,” the words “water or waste,” and “or other assembly.” Greenville Water and Spartanburg Water use “flood rim” and do not add “waste” in the air-gap definition.
Twice the diameter and the inch floor are both in each of those three sentences. When twice the outlet diameter is smaller than the inch floor in that sentence, the floor is the distance the sentence requires. When twice the diameter is larger, that multiple is the distance. Use the manual the notice cites. This page does not pick one floor for every utility.
Which hazard the documents assign
| Source | Where an air gap is named |
|---|---|
| R.61-58.7(F)(4)(a) | High hazard: air gap separation or an approved reduced pressure principle assembly. |
| Greenville Water, section 5-1 | High hazard: a reduced pressure principle assembly or an air gap. Low hazard: a double check valve assembly or a dual check. |
| Greenville Water, section 6-2.1 | High-hazard fire protection: a reduced pressure principle assembly, as close as possible to the service connection and the property line. This fire sentence does not name an air gap. |
| Spartanburg Water, section 7(a) | Premises where material hazardous to health is handled so as to create an actual or potential hazard: an approved air-gap separation or an approved reduced-pressure principle assembly. The examples in that paragraph are sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries, and plating plants. |
| Spartanburg Water, section 9.1 | High hazard: a reduced pressure principle assembly, a pressure vacuum breaker for back-siphonage only, or an air gap. Low hazard: a double check valve assembly or a double detector valve assembly. |
| Spartanburg Water, section 9.5 | High-hazard fire protection, including antifreeze, foam injection, or a lake, pond, stream, or other source: a reduced pressure assembly or an air gap, as close as possible to the service connection and the property line. |
| Anderson, device rule | High hazard: an air gap, a reduced pressure principal assembly, or a pressure vacuum breaker that is not used where backpressure is expected. Low hazard: any of those, or a double check valve assembly. An air gap is encouraged for both when a physical separation is practical. |
Spartanburg Water section 7(b) is the other premises case: water or a substance that would be objectionable but not hazardous to health. That paragraph names an approved double-check valve assembly. It does not name an air gap. Where section 7 and section 9.1 do not read the same way, use the notice Spartanburg Water sent for the account. The pressure-vacuum-breaker limit is on Pressure vacuum breaker.
Greenville Water section 6-2.1 and section (4) of the state rule do not name the same protection for a high-hazard fire line. Section 6-2.1 names a reduced pressure principle assembly. Section (4) names an air gap or that assembly. On a Greenville Water fire account, follow the notice. Questions in that manual go to the Cross Connection Control Department at (864) 241-6100. Notice timing is on Greenville Water.
Anderson’s fire-line paragraph is separate from the encouragement above. Unmetered dedicated fire lines require a reduced pressure principle detector assembly or a double detector check valve assembly at or near the earliest reasonable point beyond the service connection. The policy says the type depends on the hazard in Table 1. That paragraph does not name an air gap. Fire-line backflow is the fire case. The coordinator evaluates each facility and uses Table 1 as a guide. Shops already discussed on this site stay on the high-hazard commercial page.
Where Anderson places the supply gap
Anderson’s device-installation section says an air gap is encouraged for both high and low hazards. The appropriate location is at the meter or at an approved location. No branch, tap, tee, bypass, or any other connection that may allow a substance to enter or exit the water line is installed between the meter and the air gap.
The same section says that when an air gap is not practical, the assembly methods that follow are the ones used. Those methods, including the 12-inch and 36-inch height band for an above-ground double check or reduced pressure assembly, are on Backflow preventer installation.
Greenville Water’s section 5-1 and Spartanburg Water’s section 9.1 name an air gap for a high hazard. Those two sections do not add Anderson’s “at the meter” sentence for the supply gap. Spartanburg Water’s fire sentence, in the table above, is the location line that manual prints for an air gap on a high-hazard fire system.
The relief-valve drain is a second measurement
On a reduced pressure assembly the relief valve can discharge. The drain piping stops short of that opening. The open space at that opening is also called an air gap. It is measured on the relief opening, not on the water supply outlet in the definitions above.
| Source | Relief-valve air gap |
|---|---|
| Greenville Water, section 5-5.2 and 5-5.3 | Two times the relief-valve diameter, or 1 inch, whichever is greater. The piping is sized to exceed the discharge rate of the relief valve. The relief valve shall never become submerged. |
| Spartanburg Water, section 9.4 | Two times the relief-valve diameter, or 1 inch, whichever is greater. The piping is sized to exceed the discharge rate of the relief valve. The relief valve will never become submerged. |
| Anderson, reduced-pressure installation | The relief valve is not plumbed directly to any piping. The air gap between the relief opening and any discharge-catch piping meets the typical air gap: at least twice the diameter, and never less than two inches, of the opening size of the relief port. |
Anderson also sizes a gravity floor drain, for a reduced pressure assembly inside a building or in a pit, at least twice the diameter of the relief valve. That sentence is the drain size. The row above is the open space at the relief opening. The policy says a sump pump is not a substitute for that floor drain. RPZ testing is the rest of the reduced-pressure installation rule, including Greenville Water’s and Spartanburg Water’s limits on an underground reduced pressure assembly.
Seneca Light & Water, and Easley
Seneca Light & Water’s backflow manual, revised October 2021, calls an air gap a vertical, physical separation between the end of a potable water supply and the flood-level rim of a receiving vessel. The vertical distance between the supply pipe and the receiving vessel is at least twice the diameter of the supply pipe. That section does not print a “never less than one inch” or “never less than two inches” floor. The same section says an air gap can be bypassed. Its example is a laboratory sink: tubing added to the faucet carried the outlet down into water in the sink and removed the gap. The rest of that manual is on Seneca Light & Water.
Easley Combined Utilities’ standard specifications, cover dated March 2025, are a construction specification. Subsection 3.6 says to provide an air gap wherever possible. That subsection does not print a minimum distance. The same subsection’s pit-drain and fire-line sentences are on Easley Combined Utilities.
On October 28, 2026 the Greer CPW cross-connection plan linked from Greer CPW was an image PDF. This page does not add a Greer distance from it. The relief-valve sentence already on that page was checked against the plan on October 14, 2026.
Who looks at it
Anderson’s testing section says air gaps do not need to be tested, and that they should be visually inspected by the Electric City Utilities Cross Connection Control Coordinator annually. That sentence is Anderson’s. It is not a line in R.61-58.7(F)(7).
Greenville Water’s section 7 says all backflow prevention assemblies are tested by certified testers in accordance with SCDHEC and Greenville Water regulations, and that new testable assemblies are tested upon installation and before the customer uses them. The section does not print Anderson’s visual-inspection sentence. Spartanburg Water’s section 10.2 says existing approved backflow assemblies are tested annually, with the low-hazard residential lawn exclusion printed in that section. It does not print a separate visual-inspection sentence for an air gap. Where a letter tells you which check the utility wants, follow the letter. Filing rules for those two utilities are on the Greenville Water and Spartanburg Water pages. Anderson’s test-form timing is on Anderson, Pickens, and Oconee.
A customer does not substitute this page for the inspection the utility names. County lists of General Testers copied from the July 9, 2026 SCDES report start at Greenville County, Spartanburg County, and Anderson County. Confirm the current card before you hire. A row on this site is not an appointment. The regulation does not set a price for an air gap or for a test. The cost guide keeps a third-party range, labeled as that range, separate from any utility fee. Official links are on Resources.
What a preventer is Double check versus reduced pressure
Sources checked October 28, 2026: R.61-58 on des.sc.gov, section 58.7(F); Greenville Water’s November 10, 2025 manual; Spartanburg Water’s manual revised June 4, 2026; Anderson Electric City’s September 2008 policy; Seneca Light & Water’s backflow manual revised October 2021; Easley Combined Utilities’ standard specifications, cover dated March 2025, subsection 3.6. The Greer CPW plan linked from the Greer page was an image PDF the same day, and no Greer distance was added from it.