Booster pumps and backpressure in Upstate SC

A pump can raise pressure on the customer side of the meter above the supply. That is one cause the manuals name for backpressure. A pressure vacuum breaker is not the assembly those files allow on that kind of line. A fire booster pump is a different sentence, and the pressure number is not the same in every file.

Sources checked November 18, 2026.

If this page and the letter on the account disagree, follow the letter. What is a backflow preventer is how the Greenville Water, Spartanburg Water, and Anderson manuals define backpressure. Pressure vacuum breaker is the 12-inch rule and the backsiphonage limit. Fire-line backflow is the state split for a dedicated fire line. A pump sentence on another system uses that utility’s notice.

The regulation uses “booster pump” outside the cross-connection section

R.61-58 definition (16) says a booster pump is any pump installed within a water distribution system to increase the pressure in that system, including distribution storage downstream from the pump. The same definition says the term does not apply to the low-service and high-service pumps at water treatment plants. The file prints “so called.” That definition does not name a backflow assembly.

Section (F) of R.61-58.7 is the cross-connection section. A text reading of section (F) on November 18, 2026 did not contain the word booster or the word pump. The backpressure sentence in that section is (9): where a pressure vacuum breaker is used, it is installed at a minimum of twelve inches above the highest downstream piping and shall not be subject to backpressure. The annual test in section (7) is the test for an assembly that protects the public system. It does not print a number of minutes, and it does not print a pump rule.

R.61-58.4(B)(2)(a) is a design rule for the public system’s own booster pump stations. Booster pumps are located or controlled so they will not produce less than 25 pounds per square inch anywhere in the affected distribution system when the pump is in normal operation. An automatic cutoff or a throttling valve prevents the pressure anywhere in that area from dropping below 20 pounds per square inch. The same paragraph says fire booster pumps must have a device to monitor suction pressure and throttle the output so suction stays above 20 pounds per square inch anywhere in the affected distribution system, and so the device does not shut the pump off. That paragraph does not name a double check or a reduced pressure assembly. It does not print a test fee.

R.61-58.4(D)(15)(b) is a different sentence. Individual home booster pumps shall not be allowed to meet the 25 pounds per square inch minimum pressure at the service connection. That sentence does not say a house is forbidden to have a pump for some other reason. It does not name an assembly, and it does not print a fee.

The 2025 recertification study guide says backpressure occurs when internal plumbing pressure exceeds the supply pressure, and that storage tanks, vessels, pumps, and elevated piping supplied by the water system, along with tank-type water heaters, may cause backpressure. The same page says backsiphonage occurs when the distribution system drops below atmospheric pressure, which it prints as 14.7 psi at sea level. That 14.7 psi line is the study guide’s description of backsiphonage. It is not the 20 psi line in R.61-58.4(B)(2)(a), and it is not a residual a utility requires a fire pump to hold. The study guide also says a pressure vacuum breaker is not approved or designed for backpressure. The 10 psi loss and the 1.0 psid check-valve line on that page are test readings for a double check. They are not a residual floor.

The January 1, 2026 approved-assembly list says a pressure vacuum breaker and a spill-resistant pressure vacuum breaker are not designed for backpressure. The filename on the state site spells “equipment” the way the URL shows.

What the manuals call backpressure

These definitions name a pump as one cause. They do not share one sentence, and they do not print a pounds-per-square-inch number.

  • Greenville Water’s manual (PDF created November 10, 2025) defines back pressure as a pressure higher than the supply pressure, caused by a pump, an elevated tank, an elevated piping system, a boiler, or any other means that may cause pressures greater than the public water supply. A text reading of that manual on November 18, 2026 did not contain the word booster.
  • Spartanburg Water’s manual revised June 4, 2026 (PDF created June 5, 2026) defines backpressure as any elevation of pressure in the downstream piping, caused by a pump, an elevated tank or piping, steam, air pressure, or any other cause, above the supply pressure at the point which would cause or influence a reversal of the normal direction of flow. Definition (5) says a pressure vacuum breaker is approved only for back-siphonage. A text reading of that manual did not contain the word booster.
  • Anderson’s September 2008 policy defines back pressure as a pressure higher than the water purveyor’s supply pressure, caused by a pump, an elevated or pressurized tank, a boiler, or any other means that may cause a backflow. The device section says a pressure vacuum breaker is not used where backpressure is expected. A text reading of that policy did not contain the word booster.
  • Powdersville Water’s September 2024 policy uses the same kind of back-pressure definition as Greenville Water, naming a pump. A later section lists causes of backpressure. The first example is booster pump systems designed without backflow prevention devices. Another example is a private well pump interconnected with house plumbing that is also supplied by Powdersville Water. A reduced supply-main pressure on the suction side of a water-main booster pump is listed there as an example of back-siphonage, not as an example of backpressure.
  • The City of Westminster’s Cross-Connection Control Policy, revised September 12, 2024, in the November 12, 2024 council packet, prints the same four backpressure examples and the same water-main booster-pump example under back-siphonage. The file says “THE CITY” in those examples.

Greer CPW’s plan amended April 2025 was read from the scan. Appendix C defines backpressure as a pressure higher than the supply pressure caused by a pump, an elevated tank, a boiler, or any other means that may cause backflow. A reading of that scan did not show the word booster.

A pressure vacuum breaker and a booster pump

Section (9) keeps a pressure vacuum breaker off a line that is subject to backpressure. Seneca’s manual revised October 2021 says a pressure vacuum breaker is designed to protect against back siphon only, that booster pumps shall not be used with a pressure vacuum breaker, and that the assembly may be used for a high or low hazard that is not subject to backpressure. The same bullet’s example of backpressure is lake pumps for irrigation. The installation section says no lines, gauges, jockey pumps, booster pumps, or Siamese connections are installed before the assembly. Seneca Light & Water is the rest of that installation section. Oconee County testers are the General Testers in that county on the July 9, 2026 list.

Anderson’s device section allows a pressure vacuum breaker for a high hazard and says it is not used where backpressure is expected. A low hazard may use that assembly or a double check valve assembly. The coordinator still chooses. Anderson, Pickens, and Oconee is the test-form clock in that policy.

The pressure numbers are not one number

Pressure lines read on November 18, 2026. A cell is that file’s sentence. It does not transfer to the next row.
Source What the sentence is about The figure that file prints
R.61-58.4(B)(2)(a) A booster pump station on the public system, in normal operation. Fire booster pumps are the next sentence in the same paragraph. Not less than 25 psi in the affected distribution system. A cutoff or throttling valve keeps the pressure from dropping below 20 psi. A fire booster pump throttles so suction stays above 20 psi and does not shut the pump off.
R.61-58.4(D)(15)(b) An individual home booster pump, and the minimum pressure at the service connection. The home pump shall not be allowed to meet the 25 psi minimum at the service connection.
SJWD Article 9, section 9.70 A fire booster pump on a private fire-protection system. The section says the rule maintains the distribution system and complies with DHEC regulations. At least 25 psi in the affected area. In no case below 20 psi in that area. The file prints “pound” in the 20 psi sentence.
Powdersville Water, September 2024, section 10 Class 1 and Class 2 fire connections, and any booster pump installation in section 10.1(3). Class 1 must never cause system pressure to drop below 50 psi. Class 2 must not drop below 50 psi during filling. A booster pump must not drop the distribution system below 50 psi residual. The pump withdraws from a tank or reservoir sized for that residual.
Westminster, September 12, 2024, section 10.1(3) Any booster pump installation on a fire line. Pressure in the distribution system does not drop more than 30 psi in the immediate area of the fire tap. A back-pressure sustaining valve is required on every fire line tap.
City of Pickens water tap application, December 2011 Water availability for a new tap. A reading of the scan did not contain the word pump or the word booster. The city will provide pressure of 25 psi or greater. It is the customer’s responsibility to reduce or increase the pressure on the customer’s side of the service meter if that is desired or required.
2025 recertification study guide Backsiphonage, described as a drop below atmospheric pressure. 14.7 psi at sea level. That line is not a residual a fire pump has to hold.

Westminster’s 30 psi line is a limit on how far the pressure may fall at the fire tap. Powdersville Water’s 50 psi line is a residual the policy says the system must keep. SJWD’s 25 and 20, and the same pair in R.61-58.4(B)(2)(a), are residuals in the affected area. The Pickens 25 psi line is what the city says it will provide at a new tap. None of those sentences is a price for a tester the customer hires.

Fire pumps, by the file that names them

SJWD’s Article 9 (PDF created August 15, 2007) is headed private fire-protection systems. Section 9.40 says the plans submitted before installation show site piping, valving, vault construction, booster pumps, and the required backflow-prevention equipment. Section 9.60 says any fire service supplied by the district has an approved backflow prevention device, the district determines the type, and a system with corrosion inhibitors or antifreeze uses an approved reduced-pressure device. Section 9.70 says the district must approve all fire booster pumps. The applicant will not permit a pump that takes water directly from the district’s system without prior written permission. The applicant furnishes fire-pump specifications, pump curves, and the other information the section names before the pumps are installed. The 25 psi and 20 psi sentences are in that section. Section 9.70 does not name the assembly on the pump. Section 9.80 is a storage tank and an associated pump, and it repeats the written-permission sentence for a pump that takes water directly from the district. SJWD is the rest of Article 9, including the monthly fire-protection charge, which is not a test fee. Spartanburg County testers are the General Testers in that county.

Powdersville Water section 10 puts Class 1 on a direct connection with no pumps, tanks, or reservoirs, no other water supply, no antifreeze or additives, and drains to atmosphere, a dry well, or another safe outlet. Class 2 may use a fill pipe to a tank that supplies booster pumps. Both classes use a double check valve. The 50 psi lines are in that section. Section 10.1(3) adds that the pump recirculates any test water back to the tank or reservoir, and that detailed specifications go to Powdersville Water’s engineer before installation. The section says violations are subject to severe fines for every pressure-drop event that leaves a residual below 50 psi. It does not print a dollar amount for that fine. The hydraulic-modeling sentence says the developer pays a fee and does not print the amount. Customer service in section 10.1 is 864-269-5440. Powdersville Water is the 90-day letter and the rest of the policy.

Westminster’s section 10 uses five classes. Class 1 is a direct connection with no pumps, tanks, or reservoirs, and it requires a backpressure sustaining valve. Class 2 is Class 1 except that booster pumps may be installed in the connection from the city’s distribution system, with a back-pressure sustaining valve. Class 3 adds elevated storage tanks, fire pumps taking suction from above-ground covered reservoirs or tanks, and pressure tanks. Classes 1, 2, and 3 use a double check valve. Classes 4 and 5 use an air gap or a reduced-pressure principal assembly. Section 10.1(3) is the 30 psi drop and the back-pressure sustaining valve on every fire line tap. The water and sewer supervisor telephone in section 10.1 is 864-647-3233. The modeling fee has no dollar amount. City of Westminster is the 90-day letter. Oconee County testers are the General Testers in that county.

Spartanburg Water section 9.5 says each private fire-protection system is evaluated by a site or plan survey. The low-hazard paragraph says simple wet or dry fire sprinkler systems may also include covered storage tanks or pumps supplied by Spartanburg Water. On page 11 of the June 4, 2026 manual, that sentence runs into the next one with no period: “supplied by the Spartanburg Water A Double Detector Check Assembly is required.” The heading on that paragraph prints “Low Hazard/Health Hazard Category.” The high-hazard paragraph in the same section names antifreeze, foam, and a supply other than Spartanburg Water, and it requires a reduced pressure assembly or an air gap. That high-hazard paragraph does not name a pump. The section does not print a pounds-per-square-inch floor for the pumps it names. Spartanburg Water is the notice language. Double check versus reduced pressure is the hazard split.

Greer CPW section 6.2, read from the scan, says low-hazard fire systems include simple wet or dry sprinkler systems and may also include covered storage tanks or pumps supplied by Greer CPW. That section requires a double detector check assembly, ASSE 1015 or 1048, as close as possible to the service connection and the property line. Section 6.1, the high-hazard fire category, names antifreeze, foam, and a supply other than Greer CPW, and it does not name a pump. The questionnaire in Appendix A has a checkbox labeled “Pump Prime Lines.” The incident-report form uses “chemical pump” as an example of a cross-connection source. Neither of those lines is section 6.2. Appendix D item 7 names sewage treatment plants, sewage pumping stations, and stormwater pumping stations. That item does not use the word booster. Greer CPW is the rest of the plan. Greenville County testers are the General Testers in that county on the July 9, 2026 list.

Anderson’s Table 1 is a guide. “Pumped water systems” is on the low-hazard side, with the parenthetical “for pumping water to upper floors in a multi-level structure, fire fighting, etc.” Fire protection systems with injection are a high-hazard line. Fire protection systems without injection, and fire protection that uses onsite storage, are low-hazard lines. The table does not use the word booster. The coordinator evaluates each facility. A low-hazard mark on the table is the guide. It is not a sentence that every pumped system receives a double check. Anderson County testers are the General Testers in that county.

Files that do not use the word booster

A text reading on November 18, 2026 did not contain the word booster in these files. Silence in the file is not a finding that the account has no pump and no assembly. Use the notice.

  • Greenville Water’s November 10, 2025 manual. The back-pressure definition names a pump. Section 5-1 says a high hazard uses a reduced pressure principle assembly or an air gap, and a low hazard uses a double check valve assembly or a dual check. The section does not name a pump. Greenville Water is the notice and the portal.
  • Spartanburg Water’s June 4, 2026 manual, except for the word pump in the backpressure definition and in section 9.5, as quoted above. Section 7(a) names sewage pumping stations among premises protected by an air gap or a reduced pressure principle assembly. A sewage pumping station in that list is not section 9.5’s fire-system pumps.
  • Anderson’s September 2008 policy, except for the pumped-water-systems line and the back-pressure definition, as quoted above.
  • Easley Combined Utilities’ specifications with a March 2025 cover. A text reading did not contain booster, backpressure, or back pressure. Easley Combined Utilities is the water page, the test form, and those specifications.
  • Laurens CPW’s water-main specifications, cover dated September 8, 2021. A text reading did not contain booster, backpressure, or back pressure. Laurens is the commission’s backflow page and these specifications.
  • Blue Ridge Rural Water’s company policies PDF. A text reading did not contain the word booster. The capacity section uses “pumping” for the company’s own source, storage, and distribution. That sentence is not a customer fire-pump rule and does not name an assembly. Blue Ridge Rural Water is section 14.
  • Gaffney Board of Public Works’ water construction specifications. Section 02660 part 3.3 item I says no cross connections are allowed between water lines and any pipes, valves, tanks, or pumps that are not part of the potable water system. The section does not use the word booster and does not name an assembly. Gaffney is the test form and those specifications.
  • The City of Pickens water tap application, read from the scan. The 25 psi sentence is on City of Pickens. It does not name a pump. Pickens County testers are the General Testers in that county.

What to do with the letter

Hire a General Tester, the classification that may test for the public. County pages copy that classification from the SCDES report printed July 9, 2026. Confirm the current card before you hire. A row on this site is not an appointment.

The letter names the assembly, the date, and where the report goes. How to read your notice is the reading for the forms Greenville Water, Spartanburg Water, and Anderson publish. A failed result is on Failed backflow test. A repair, and the retest after it, is on Backflow preventer repair.

The regulation does not set a price for the device or the test. None of the pump lines above print a test fee for a tester the customer hires. Powdersville Water’s severe-fine sentence does not print a dollar amount. Westminster’s modeling sentence does not print a dollar amount. The cost guide is a third-party range for a test a customer hires. It is not a pump price and it is not a utility fee. Official links are on Resources.

Fire-line backflow Pressure vacuum breaker

Sources checked November 18, 2026: R.61-58 on des.sc.gov (PDF created June 24, 2025, modified May 22, 2026), including definition (16), R.61-58.4(B)(2)(a), R.61-58.4(D)(15)(b), and R.61-58.7(F), including sections (7) and (9); the 2025 recertification study guide, including the backpressure paragraph, the 14.7 psi line, and the pressure-vacuum-breaker paragraph; the January 1, 2026 approved-assembly list, pressure vacuum breaker and spill-resistant section; Greenville Water’s manual created November 10, 2025, including the back-pressure definition and section 5-1; Spartanburg Water’s manual revised June 4, 2026, created June 5, 2026, including the backpressure definition, definition (5), section 7(a), and section 9.5 on page 11; Anderson Electric City’s September 2008 policy, including the back-pressure definition, Table 1, and the device section after the table; Greer CPW’s cross-connection control plan amended April 2025, read from the scan, including section 6.1, section 6.2, Appendix A’s questionnaire and incident-report form, Appendix C, and Appendix D item 7; Seneca Light & Water’s manual revised October 2021, including the pressure-vacuum-breaker bullets and the fire-service installation section; Powdersville Water’s September 2024 cross-connection policy, including the back-pressure definition, the backsiphonage and backpressure examples, section 10, and section 10.1(3); the City of Westminster November 12, 2024 council packet, including the Cross-Connection Control Policy revised September 12, 2024, the backsiphonage and backpressure examples, section 10, and section 10.1(3); SJWD’s private fire-protection file, Article 9, created August 15, 2007, including sections 9.40, 9.60, 9.70, and 9.80; Easley Combined Utilities’ specifications with a March 2025 cover; Laurens CPW’s water-main specifications dated September 8, 2021; Blue Ridge Rural Water’s company policies PDF; Gaffney Board of Public Works’ water construction specifications, section 02660 part 3.3 item I; and the City of Pickens water tap application dated December 2011, read from the scan.