Thermal expansion after a backflow preventer in Upstate SC
A backflow preventer or a dual check can stop heated water from moving back into the utility main. Five Upstate files describe that condition. They do not all name the same valve, and none of them prints a price for the work.
Sources checked November 13, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is the device on the service. Where that device is installed is on Backflow preventer installation. A house, and the difference between a testable assembly and a residential dual check, is on Residential backflow testing.
The state regulation does not print this subject
R.61-58, the State Primary Drinking Water Regulations file on des.sc.gov, does not contain the phrases “thermal expansion” or “expansion tank.” The annual test of a testable assembly is a different rule. It is on What is backflow testing. The pressure figures below are sentences in the utility manuals. They are not a line in that regulation, and they are not a fee.
Greenville Water
Section 8 of the Cross Connection Control Manual is headed “Thermal Expansion.” The table of contents lists it on page 17. The file properties record a creation date of November 10, 2025.
The section says that since 1971, Greenville Water has required backflow prevention assemblies on all service connections. It says practically all customers use heated water, that heated water expands and needs more space, and that this is thermal expansion. It says thermal expansion will often cause water temperatures to rise and pressure relief valves to discharge due to excessive water pressures, usually at above 150 psi. Before backflow preventers were on service lines, that expanded water pushed back into Greenville Water’s distribution system. The section calls that an open system, and says an open system is no longer possible where a backflow preventer is present at the meter.
Section 8 does not use the words “closed system.” It does not name a dual check. It does not name a water heater. The three methods it names are a bladder type expansion tank, a special ball cock and relief valve in the water closet, or a remote thermal expansion relief valve. It says Greenville Water suggests discussing those alternatives with a licensed plumber, and that installation of those three devices can be “do-it-yourself” projects. Questions about thermal expansion as it relates to cross-connection control go to 864-241-6100.
Section 2-4 is a separate customer sentence. The customer maintains special plumbing fixtures or devices that accommodate variations in water pressure, including thermal expansion tanks, relief valves, and pressure reducing valves. The same section says Greenville Water’s supply pressure varies and that the supply can be shut off for repairs, maintenance, and construction, planned or unplanned.
On November 9, 2026, Greenville Water’s backflow page did not use the words thermal or expansion. The section 8 phone number is the one in the manual.
Spartanburg Water
Section 13 of the manual revised June 4, 2026 is headed “Thermal Expansion.” The index lists it on page 18. The sheet that prints the section is marked Page 17 of 18. The file properties record a creation date of June 5, 2026. The commercial and industrial page still links this file.
The section says that since 1971, backflow prevention assemblies have been installed on many service connections, and that in 1985 Spartanburg Water began installing residential dual check valves on 3/4-inch services. Before a backflow preventer or a dual check was on the service line, expanded water went back into Spartanburg Water’s distribution system. The section calls that an open system. It says that is no longer possible where a backflow preventer or a dual check is present, and it calls that a closed system. Heated water expanding in a closed system is thermal expansion.
The section says thermal expansion will often cause the water heater’s temperature and pressure relief valves to discharge excessive water pressures, usually at above 150 psi. The three methods are the same three Greenville Water’s section 8 names. The section uses the initials SWS and says to discuss those alternatives with a licensed plumber. It also says these three methods can be “do it yourself” projects. Questions about thermal expansion as it relates to cross-connection control go to 864-585-8296.
Spartanburg Water’s section 13 names a dual check and a closed system. Greenville Water’s section 8 does not. The 150 psi line is in both sections. The two sentences around that number are not the same sentence: Greenville Water names water temperatures and pressure relief valves, and Spartanburg Water names the water heater’s temperature and pressure relief valves.
Greer CPW
Section 9 of the Cross-Connection Control Plan, cover “Amended April 2025,” is headed “Thermal Expansion.” It is printed on the sheet marked 14. On November 9, 2026 that PDF was an image file. Section 9 was read from that sheet.
The section says that since 1971, backflow prevention assemblies have been installed on many service connections, and that in 1985 the Greer Commission of Public Works began installing residential dual check valves on 3/4-inch services. It says those practices continue in order to prevent backflow from various size services from entering the public supply. It uses “open system” for the time before a backflow preventer or a dual check, and “closed system” for where one is present. It says the condition of heated water expanding in a closed system is thermal expansion, and that this will often cause water heater temperature and pressure relief valves to discharge excessive water pressures, usually at above 150 psi.
The three methods are the same three. The section says the GCPW suggests discussing them with a licensed plumber, and that thermal expansion control shall be in accordance with the South Carolina Plumbing Code. It does not print the do-it-yourself sentence that Greenville Water’s section 8 and Spartanburg Water’s section 13 print. Questions about thermal expansion related to cross-connection control go to (864) 848-5500.
Section 2.4, on the sheet marked 3, says the customer maintains special plumbing fixtures or devices that accommodate variations in water pressure, including thermal expansion tanks, relief valves, and pressure-reducing valves. It says the Greer CPW supply is subject to variations in pressure and to being shut off for repairs, maintenance, and construction, planned or unplanned. The rest of the plan is on Greer CPW.
Powdersville Water
Section 11 of the cross-connection policy revised September 2024 is headed “Thermal Protection – Owner Responsibility.” The contents list it on page 25, and the section continues onto the next sheet.
It says every customer water system that has been closed or contained by a backflow assembly or a similar checking device must be altered to protect against thermal expansion. Where water is heated and stored, and any branch or all of the system has been closed by a backflow preventer, a pressure reducing valve, or any other checking device, an approved auxiliary relief valve shall be installed at an accessible location between the checking device and the water heating equipment. That valve limits thermal expansion of the water being heated to not more than 80 pounds per square inch no-flow pressure at any fixture. A discharge line not less than 1/4 inch inside diameter is piped to an approved location where the discharge would not cause water damage, where water in the discharge pipe would drain by gravity, and where that pipe is protected from freezing.
The installation is the responsibility of the owner and of the plumbing officials having jurisdiction. Plumbing beyond Powdersville Water’s meter is the customer’s, including a residential water heater and other appliances.
Section 11 does not print the 150 psi line. It does not list the three methods in the other three manuals. It does not print a phone number or a dollar amount. The rest of the policy, including who tests, is on Powdersville Water.
City of Westminster
Section 11 of the Cross-Connection Control Policy revised September 12, 2024 is headed “Thermal Protection – Owner Responsibility.” The policy is in the November 12, 2024 council packet.
The section says a customer system closed or contained by a backflow assembly or a similar checking device must be altered to protect against thermal expansion. Where water is heated and stored, and any branch or all of the system has been closed by a backflow preventer, a pressure reducing valve, or any other checking device, an approved auxiliary relief valve is installed between the checking device and the water heating equipment. The valve limits thermal expansion to not more than 80 pounds per square inch no-flow pressure at any fixture. The discharge line is not less than 1/4 inch inside diameter, drains by gravity, and is protected from freezing.
The installation is the owner’s and the plumbing official’s. Plumbing beyond the city’s meter is the customer’s, including a residential water heater. Section 11 does not print the 150 psi line, the three methods, a phone number, or a dollar amount. The rest of the policy, including the 90-day letter, is on City of Westminster.
The relief valve on a reduced pressure assembly
A reduced pressure principle assembly has its own relief valve. That opening is not the water-heater valve in the thermal-expansion sections.
Greenville Water section 5-5.1 says periodic pressure fluctuations may cause the relief valve of the assembly to discharge enough to be a nuisance, and that the customer should then install an additional check valve prior to the assembly. Spartanburg Water section 9.4 says the same thing. The air-gap distance those sections set for the assembly’s relief-valve drain is on Air gap separation. The rest of the reduced-pressure installation limits are on RPZ testing.
Greenville Water section 5-4.5 and Spartanburg Water section 9.3 say the manufacturer’s installation requirements are followed, including hot-water and high-pressure applications. That sentence is about installing the assembly. It is not section 8, section 13, or section 9.
These sections do not print a price
Greenville Water’s section 8, Spartanburg Water’s section 13, Greer CPW’s section 9, Powdersville Water’s section 11, and Westminster’s section 11 do not print a dollar amount for an expansion tank, a relief valve, a plumber, or a do-it-yourself part. The cost guide keeps a third-party range for a backflow test a customer hires. That range is not a price for this work.
A county list on this site is the SCDES General Tester report. It is the list for a test of a testable assembly. It is not a list of plumbers, and a row is not an appointment. General vs Limited is the card. Start with Greenville County, Spartanburg County, or Anderson County only when the letter is about the test.
If the utility is not one of these five
Anderson’s September 2008 policy does not print a thermal-expansion section. The word thermal appears in that file inside “geothermal,” in the well definition on Auxiliary water and private wells.
Seneca Light & Water’s backflow manual, revised October 2021, does not print a thermal-expansion section. The heater sentence in the reduced-pressure installation instructions is freeze protection: heat stripping or heaters when electrical power is available. That sentence is not a water-heater rule. The rest of the manual is on Seneca Light & Water.
This page does not add a thermal-expansion rule for a utility whose file is not cited here. Use the letter on the account. Official links are on Resources.
Where the preventer goes Residential testing
Sources checked November 9, 2026: R.61-58 on des.sc.gov, searched for the phrases “thermal expansion” and “expansion tank”; Greenville Water’s backflow page and the November 10, 2025 manual, section 8, section 2-4, section 5-4.5, and section 5-5.1; Spartanburg Water’s commercial and industrial page and the manual revised June 4, 2026, section 13, section 9.3, and section 9.4; Greer CPW’s Cross-Connection Control Plan, cover “Amended April 2025,” section 2.4 on the sheet marked 3 and section 9 on the sheet marked 14, read from the image PDF; Powdersville Water’s cross-connection policy, cover “Revised September 2024,” section 11; Anderson Electric City’s September 2008 policy; and Seneca Light & Water’s backflow manual revised October 2021, including the reduced-pressure freeze-protection sentence. Westminster’s section 11 was checked November 13, 2026 in the Cross-Connection Control Policy revised September 12, 2024, printed in the November 12, 2024 council packet.