City of Westminster backflow testing

A testable assembly is tested before Westminster turns on the service, and again within 90 days of the city’s annual letter. Appendix A prints a city test charge only when that report is not returned.

Sources checked November 13, 2026.

The utilities page says the City of Westminster has provided drinking water since 1925 and that the Chauga River is the source. That page does not print a test interval, a test form, or the word backflow. The rules below are the Cross-Connection Control Policy revised September 12, 2024, printed in the November 12, 2024 council packet. Seneca Light & Water and the City of Walhalla are other Oconee systems. Their clocks do not transfer to a Westminster account.

The minutes of that meeting record a unanimous vote to approve the updated City of Westminster Water Policies. The agenda names four files in that item: the standard operating procedures, the flushing program, the fire-hydrant policy, and the Cross Connection Control Policy. The minutes do not reprint the policy. The agenda spells the utilities director “Scott Paris.” The minutes, the utilities page, and the SCDES record spell Parris.

If this page and the letter on the account disagree, follow the letter. What is a backflow preventer is the device. What is backflow testing is the state test. Oconee County testers are General Testers from the July 9, 2026 SCDES list.

Which file is the policy

The policy heading is “Revised September 12, 2024.” Section 14.1(2) refers to “the effective date of this Cross-Connection Control Policy” and does not print a second date. Current copies, the definitions say, are available at the City Utility Shop, 864-647-3233.

The same packet includes standard operating procedures for water distribution system 3710003, revised 08/09/2024. That file says “See New Revised Policy Located in Tab 1” and then the September 12 policy follows. The utilities page does not link either file.

A utility-policies file updated February 11, 2025 covers bills, deposits, and leak adjustments. A text reading of that file did not contain the word backflow. The service agreement on the city site says pressure-reducing valves and backflow devices are the customer’s responsibility for maintenance, repair, and testing. It does not print a day count, a filing address, or a test fee. The irrigation line on that form is a yes-or-no box. It does not name an assembly.

The system the record describes

The SCDES drinking-water record for Westminster City of, SC3710003, lists the principal county as Oconee, the primary source as SW, status A, and an activity date of 06-01-1977. The service-area table lists Chauga River as an intake with status A, and Ramsey Creek as an intake with status I. The purchases table lists Seneca City of, SC3710002, and two rows for Walhalla City of, SC3710004. A purchase row is the seller on that table. It is not a Seneca or Walhalla backflow rule.

The 2024 drinking-water quality report prints System #3710003 and says the source is the Chauga River, a surface-water source, with two emergency connections, one with the City of Seneca and the second with the City of Walhalla. The report does not use the word backflow. Questions on that report go to 864-647-3219.

The standard operating procedures say raw water is pumped to the city’s treatment facility by two five-hundred-horsepower pumps on the Chauga River, and that a twenty-four-inch main carries it on Highway 76 to the 4.0 MGD water treatment plan at 735 Cornelia Avenue. The file prints “plan.” The same section says the city serves 3.40 square miles, with lines also extended to Highway 76, Highway 123, and Highway 11, and it prints 3414 residential service connections and 52 non-residential connections.

Section 2.1(3) of the cross-connection policy says the treatment facilities are owned and controlled by other entities, that water is master metered into the city system, and that the city is a “consecutive system.” That sentence is the policy. The utilities page, the 2024 report, the operating procedures in the same packet, and the SCDES primary-source code SW are the other descriptions. This page does not choose one of them.

The operating procedures’ connection counts and the SCDES detail page’s counts are also different documents. The detail page retrieved November 13, 2026 prints population type R as 9588 and population type W as 1560. The service-area code list on that page expands R as RESIDENTIAL AREA and does not expand W. The connection table prints type CM as 72 and type RS as 3995. The page does not print the date of those counts.

Where a report goes

Section 1.4 says testing and repair reports on an approved SCDES form go to the city every 12 months. Section 2.2(6) says a copy of testing and repair reports is submitted to the city and the original is retained on site. Section 2.3 says a successful report on a new assembly is received before water service is established. None of those sentences prints an email address.

The number 864-647-3233 is the utility-shop line in the definitions, the water and sewer supervisor line in section 10.1, and the phone and the fax line on the operating-procedures cover, which also prints fax 864-647-3216. The utilities page’s customer line is 864-647-3200. The same page says after-hours water, electric, or sewer trouble goes to (864) 247-6017. Those lines are on the utilities page. They are not a filing instruction in the policy.

The SCDES record prints owner telephones 864-247-2389, 864-647-3219, and 864-647-3232 at 735 Cornelia Ave, Westminster, SC 29693. The owner-row emails on that retrieval are timborow@gmail.com, tborow@westminstersc.org, KBRONSON@WESTMINSTERSC.ORG, and SPARRIS@WESTMINSTERSC.ORG. Kevin Bronson is the administrative contact, at kbronson@westminstersc.org, with telephones 864-647-3219 and 864-647-3232. The record prints Tim Borow with the job title WTP SUPT and Scott A Parris with the job title UTILITIES DIRECTOR. The utilities page names Scott Parris as Utilities Director, at sparris@westminstersc.org, and Tim Borow as Water Treatment Plant Supervisor. Those addresses and telephones are the pages that print them. They are not a sentence in the policy telling a tester where to send the form. Use the letter on the account. How to read your notice is the reading for forms other utilities publish.

The test the policy sets

Section 2.3 splits new and existing assemblies.

  • A new testable assembly is tested upon installation and before the customer uses it. The installer contacts a certified tester. The city receives the successful report before water service is established.
  • Customers with an existing device in the city’s inventory are notified annually by letter. The customer contacts a certified tester and has the test completed within 90 days of notification. The policy prints “90 DAYS” in that sentence. If the assembly fails and cannot be repaired immediately, it is replaced immediately, tested successfully, and the report is submitted promptly.
  • A report that is not back within the 90-day period is noncompliance. The city then proceeds with administrative action up to and including immediate discontinuance of water service within a 30-day period.

Section 2.2(6) says the test is at least once a year, every 12 months, at the water user’s expense. SCDES or the city may require certified inspections more often when the hazard is great enough. The section does not print that shorter interval. Section 2.3(3) says the city will randomly retest a few recently returned reports, at the city’s expense, and will notify the customer in advance if service will be interrupted. The sentence does not print how many reports.

Section 3.4 says that after any repair, overhaul, re-piping, or relocation, the customer has the assembly retested. Backflow preventer repair is how other published manuals split a repair from a replacement. It is not this section.

Who may test

Section 2.2(7) says testers of devices in the city’s system shall be certified by SCDES and in good standing with SCDES. The city may check a test. If it determines that test records were falsified, the tester is banned from work in the city’s system and the information goes to SCDES’s Cross Connection Control Department.

The introduction lists four certified-tester types: General Tester, Limited Tester, Inspector Tester, and Manufacturer’s Agent. It says the definition of each is specified in R.61-58(A). The same introduction prints a three-year card, a written examination with a passing score of 70 percent, and a gauge accurate within 2 percent of full scale or plus or minus 0.3 pounds per square inch differential. Those sentences are the city’s introduction. The state card is on General vs Limited. The gauge sentence in the regulation is on Backflow test kit calibration. County pages on this site list General Testers only.

A house, a lawn, and a well

The residential dual check, in the definitions, has no shutoff valves and no test cocks. It is for selectively approved low-hazard connections such as residential irrigation and domestic metering. Because it is not testable, the definition says these devices are changed out on a 10-year rotation at the customer’s water meter.

Section 2.2(4)(g) is the lawn sentence. Residential irrigation with no chemical injection or addition is a low hazard and is protected by a dual check. A customer who adds a testable device keeps the maintenance and testing of that device. Chemical addition on a residence is a high hazard and is protected by a reduced-pressure device. Non-testable dual checks on taps with residential lawn irrigation are on a 10-year replacement cycle by the city. Irrigation backflow testing is the state split and the schedules other utilities print. Greenville Water’s thirty-year parts replacement is not this 10-year cycle.

Section 2.2(4)(h) says commercial, non-residential lawn irrigation is a medium hazard and is protected by at least a double check valve assembly.

The operating procedures say a 3/4-inch by 5/8-inch meter is installed in a setter with a built-in backflow device. That sentence does not print the 10-year rotation. The 10-year sentences are the policy.

Section 5 says a physical separation must be made between any private water supply, including a groundwater well, and the city system. The overview uses a private well pump tied into house plumbing that the city also supplies as an example of backpressure. Auxiliary water and private wells is how Spartanburg Water and Anderson word a well. Those sentences are not section 5.

High, medium, and low

The definitions list two degrees of hazard, high and low. Section 4 also says two degrees, health and non-health. Section 2.2(4) then uses a third label, medium hazard, for water that would be objectionable but not hazardous to health, and for commercial lawn irrigation. The medium-hazard device in that subsection is an approved double check valve assembly. This page leaves the three labels as the policy prints them.

A high hazard in section 2.2(4), including an auxiliary supply that represents a danger, material dangerous to health, and uncontrolled cross connections, is an air gap or an approved reduced-pressure principal assembly. The examples printed for material dangerous to health are sewage treatment plants, chemical manufacturing and processing plants, medical facilities, mortuaries, and metal plating operations. The section does not name a restaurant, a dental office, or a car wash. High-hazard commercial is how other manuals sort a shop. It is not this list.

Section 7 is a guide of minimum protection. The health hazard governs the final choice. Rows in that table include clinics and laboratories at a reduced-pressure principal assembly, a connection to a sewer pipe at an air gap, fire sprinkler systems at a double check, a firefighting system with toxic liquid foam at a reduced-pressure principal assembly, irrigation with chemical additives at a reduced-pressure principal assembly, and the row the file spells “Irrigations systems (non-residential))” at a double check. Public swimming pools are a double check. Premises where inspection is restricted are a reduced-pressure principal assembly. The table has more rows than this paragraph. Read section 7 for the row that matches the account.

The air-gap definition is at least twice the diameter of the supply outlet above the flood rim, and never less than one inch. Section 6 repeats that minimum and adds “(25mm).” Air gap separation is the one-inch and two-inch lines in the other published manuals. Anderson’s two-inch minimum is not this definition.

Where a pressure vacuum breaker is provided, section 6 says it is installed a minimum of twelve inches above the highest downstream piping and is not subject to backpressure. Pressure vacuum breaker is the same height in the state rule.

Fire lines

Section 10 sorts fire protection into five classes and then prints a second rule for new and renovated systems.

  • Class 1 is a direct connection from public mains only: no pumps, tanks, or reservoirs, no physical connection from another water supply, no antifreeze or other additives, and sprinkler drains discharging to atmosphere, dry wells, or other safe outlets. The connection has a backpressure sustaining valve.
  • Class 2 is Class 1 except that booster pumps may be installed. It has the same valve.
  • Class 3 adds elevated storage tanks, fire pumps taking suction from above-ground covered reservoirs or tanks, or pressure tanks. Storage is filled from the potable supply and kept potable. It has the same valve.
  • Class 4 is supplied from public mains like Classes 1 and 2 and has an auxiliary supply dedicated to fire-department use, such as an auxiliary supply within approximately 1,700 feet of the pumper connection.
  • Class 5 is supplied from public mains and interconnected with an auxiliary supply. The examples include pumps taking suction from reservoirs exposed to contamination, rivers and ponds, driven wells, mills or other industrial water systems, and antifreeze or other additives.

The protection table prints a double check valve for Classes 1, 2, and 3, and an air gap or a reduced-pressure principal assembly for Classes 4 and 5.

Section 10.2 then says all new or renovated fire sprinkler systems have a UL-approved meter and an approved double check valve assembly. Section 10.1(4) says no antifreeze or similar chemical is allowed unless the city approves it. Section 10.1(3) says a booster pump is designed so pressure in the immediate area of the fire tap does not drop more than 30 psi, and that a back-pressure sustaining valve is required on every fire line tap. That 30 psi line is a limit on the drop. How it differs from the residual floors in other files is on Booster pumps and backpressure. The hydraulic-modeling sentence says the developer pays a fee for that service and does not print the amount.

The double detector check, in the definitions, is a main-line double check with a small bypass and a meter, typically on fire-line taps. The same definition says these devices cannot be used in new installations. Fire-line backflow is the state fire-line rule and the detector assemblies other manuals still name. It is not section 10.2.

Installation of the fire-line double check is the owner’s. The assembly is readily accessible for testing, maintenance, and inspection. The application is made by a licensed fire-suppression contractor or a licensed plumber. The owner maintains the system from the valve at the city’s distribution system to the inside of the building, including the assembly, the meter, and control valves. The city maintains from the main to the inlet side of the fire-line vault. Plans go to the city before connection. The complete specification is the copy requested at 864-647-3233. This packet does not attach that specification.

A parallel assembly, and the five-to-twenty-minute line

Section 8 says assemblies with test cocks are tested once a year, every 12 months, at a minimum. It says testing may require a water shutdown usually lasting five to twenty minutes. Where water cannot be interrupted and a separate meter is not available, the section requires a parallel installation: one assembly stays on while the other is tested. The city will not accept an unprotected bypass around a backflow preventer. Multi-story buildings with flushometer toilets are the example. The section says experience has shown that flushometers may have to be reset if the supply is shut off. That sentence is the policy’s.

The five-to-twenty-minute line is that shutdown. It is not a duration in R.61-58.7(F). The same wording is already on Powdersville Water. Bypass and parallel assemblies is the state list and the other manuals. Section 8 does not print a dollar amount for the second assembly.

Heated water and freezing

Section 11 says a customer system closed by a backflow assembly or a similar checking device has to be altered for thermal expansion. Where water is heated and stored behind a backflow preventer, a pressure-reducing valve, or any other checking device, an approved auxiliary relief valve goes between the checking device and the water-heating equipment. The limit is not more than 80 pounds per square inch no-flow pressure at any fixture. The discharge line is not less than 1/4 inch inside diameter, drains by gravity, and is protected from freezing. The owner and the plumbing official install it. Plumbing past the meter, including a residential water heater, is the customer’s. Thermal expansion is the 150 psi line in three other manuals and the same 80 psi sentence in Powdersville Water’s section 11. Section 11 does not print a price.

Section 12 says the device owner protects an outdoor assembly from freezing, without interfering with inspection, operation, or maintenance. Weather damage is repaired immediately by the account owner. The section does not print a dollar amount.

Where the assembly sits

Section 2.2(3) says an approved assembly is installed on the service line at or near the property line. Section 15 says no installation inside the building or establishment is allowed without authorization from the city, and that devices shall be located at the property line. It points to “section 2.2.3.” The property-line sentence in the copy is section 2.2 item (3).

Section 13 says plans for the assembly are submitted before installation. The approved-assembly sentence in section 13.2 cites “AWWA-0506-78” and “SC DHEC’s list.” Section 2.2(5) cites AWWA C510-89 and AWWA C511-89. Both citations are the policy. The current South Carolina list is the January 1, 2026 notice.

Appendix B names five drawings: WCCCP-10, Reduced Pressure Backflow Preventor Detail; WCCCP-20, Metered Fire Line; WCCCP-30, Air Gap Separation; WCCCP-40, Pressure Vacuum Breaker; and WCCCP-50, Double Check Valve Assembly. The drawing title spells “Preventor.” A text extract of those five sheets on November 13, 2026 returned the titles and no dimension notes.

The dollar amounts, and what they are

Section 3.5 says testing fees are charged by the city only when the customer has failed to submit a current successful test report after a final notice, and only when the city’s workload allows it. Otherwise the customer gets a 30-day notice and service is discontinued if the device is not tested and operating properly.

Appendix A is headed “Annual Testing (when customer fails to complete).”

  • A DCVA, RP, or PVB less than 8 inches is $275.
  • A DCVA, RP, or PVB of 8 inches or larger is $500.
  • Confined-space entry is $250 plus cost.
  • The fee to lock and unlock a meter is $50.
  • The fee to lock and unlock a meter after 5 p.m. is $100.

The appendix says all fees are subject to change without notice. Section 14.4 points to those lock and unlock charges when a customer fails to comply with testing, maintenance, and repair. Those amounts are the city’s charge in that table. They are not a price for a tester the customer hires. The cost guide keeps a third-party range for a hired test. That range is not Appendix A.

The February 11, 2025 utility-policies file prints a $50 reconnect fee and an additional $100.00 when a customer is reconnected over a weekend or after business hours. Those lines are in the billing section of that file. They are not Appendix A, and that file does not use the word backflow. The service agreement’s $25 is the new-account service fee printed next to the deposit blank. It is not a test fee. The utilities page’s water-leak adjustment is a bill adjustment. It is not a test fee.

If the test is missed

Section 14.1 has three categories. An existing customer with no device, where the city has determined a health hazard, takes immediate corrective action. A potential system hazard is corrected within 30 days of notification, or service is terminated. A new customer installs an approved device before connection when the city has determined a hazard, and the device is installed, successfully tested, and reported before service is established. A device that does not meet city standards is replaced immediately. A malfunctioning low-hazard device is repaired or replaced within 30 days. A malfunctioning high-hazard device is repaired or replaced immediately, or service is discontinued.

Section 14.2 says service is discontinued if a required assembly is not installed, tested, and maintained. The copy prints “pers schedule.” Service is also discontinued if a device has been removed or bypassed, or if an unprotected cross connection exists and protection at the service is inadequate. Service stays off until the condition is corrected. A written notice says service will be terminated if the policy is not met. The section says the city will not be liable for losses, damages, or claims arising from that termination. It does not print a number of days inside the written-notice sentence. The copy prints sections 14.1, 14.2, and 14.4. It does not print a section 14.3.

Failed backflow test is the repair clock in the Greenville, Spartanburg, and Anderson manuals. Those clocks are not section 14.

The sheet at the end of the policy

The packet includes a Backflow Prevention Device Observation Form after section 16. The blanks are the date, street address, business name, phone, location as pit or box or inside building, type as RP, DCVA, or other, size, make, model, serial number, plumber or installer, and comments. The form does not print a due date, a fee, a pass line, or a fail line. It does not print an email. The test report the policy names is the approved SCDES form in section 1.4. How to read your notice is for a different sheet.

Oconee County testers What the state test requires

Sources checked November 13, 2026: the City of Westminster utilities page; the November 12, 2024 council agenda packet, including the standard operating procedures revised 08/09/2024, the Cross-Connection Control Policy revised September 12, 2024, sections 1 through 16, Appendix A, Appendix B, and the observation form, read from a text extract of the PDF; the November 12, 2024 council minutes; the utility-policies file headed Updated February 11, 2025; the service agreement at the April 2026 path on westminstersc.org; the 2024 annual drinking-water quality report, System #3710003; and the SCDES drinking-water record SC3710003. The utilities page, the February 11, 2025 file, and the 2024 report did not use the word backflow. Appendix A’s dollar amounts are the city’s charge when the customer does not complete the test. They are not a hired-tester price.