Auxiliary water and private wells in Upstate SC
An auxiliary supply is water on the property other than the utility’s approved supply. Spartanburg Water’s well section says a building served by a private well is physically disconnected from the well before metered service is turned on. If the well stays connected, that section requires a reduced pressure device on the customer side of the meter. Anderson’s table lists an auxiliary water system and a well as low hazard and says the table is a guide. The letter from the utility names the protection on the account.
Sources checked October 29, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is how to tell a reduced pressure assembly from a double check, an air gap, and a residential dual check. Residential backflow testing is the ordinary house service. A lawn system that also ties into another water source is on Irrigation backflow testing. This page is the second supply: a private well, a spring, a pond, another water system, or used water on the same property as a public meter.
What the three manuals call it
R.61-58.7(F), read on October 29, 2026, does not use the words “auxiliary water” or “private well.” The three manuals that define the phrase are below. A cell is the sentence in that document.
| Source | What the definition covers |
|---|---|
| Spartanburg Water, definitions | Any water supply on or available to the premises other than the Spartanburg Water approved supply. The examples are another purveyor’s public potable system, a natural source such as a well, spring, river, or stream, used waters, and industrial fluids. The same sentence says they may be polluted, contaminated, or objectionable, and that Spartanburg Water does not have sanitary control over that source. |
| Greenville Water, definition (auxiliary water supply) | Any water supply on or available to the customer’s premises other than the Greenville Water approved supply. The examples are other purveyors’ public potable systems, a natural source such as a well, spring, river, stream, or harbor, used waters, and industrial fluids. This definition does not add the sanitary-control sentence Spartanburg Water prints. |
| Anderson, appendix | Any water on or available to the customer’s premises other than the City of Anderson / Electric City Utilities drinking-water supply. The examples are other purveyors, a natural source (groundwater wells, springs, rivers, streams), used waters, and industrial fluids. The same entry says these waters may be contaminated, polluted, or objectionable, and that the purveyor does not have sanitary control over that source. |
Anderson’s appendix also defines three well terms. A private well supplies potable or non-potable water to a single person or premises, from ground or surface, with a bored well given as the example. A public well serves a public water system. The longer “well” entry is a bored, drilled, or driven shaft, or a dug hole whose depth is greater than the largest surface dimension, from which water is extracted or injected. That entry includes wells for irrigation, industrial or manufacturing processes, or drinking water, wells used to inject waste, wells used in mineral or geothermal recovery, and any other special-process well. Spartanburg Water’s manual revised June 4, 2026 and Greenville Water’s November 10, 2025 manual do not print those three definitions.
What the state rule does cover
Section (1)(b) says no person may install or keep a cross connection between a public water system and any other non-public water system, a sewer, or a line from a container of liquids or other substances, unless an approved backflow prevention device or assembly sits between the public system and the source of contamination.
Section (2) is the low-hazard case: a connection between an approved public water system and another water source that is not hazardous to health, that does not meet the standards of the approved public system, and that is not cross-connected inside its own system with a potentially dangerous substance. The minimum that sentence names is an approved double check valve assembly or a pressure vacuum breaker, except the residential-lawn rule in section (3). Double check versus reduced pressure is that split. The regulation does not say every private well meets those three conditions.
Section (3)(b) is one high-hazard case the rule does name. A residential lawn irrigation system that adds chemicals, or that is also connected to a water source which is not an approved public water system, has to meet section (4): an air gap or an approved reduced pressure principle assembly. Spartanburg Water’s definition of low-hazard residential lawn irrigation is a system on a single-family dwelling with no chemical injection and no auxiliary water source. The schedules are on the irrigation page.
Section (4)(a) is the broader high hazard: a connection to a service or other water system that has or may have any material dangerous to health, handled under pressure or subject to negative pressure. Protection is an air gap or an approved reduced pressure principle assembly. The inch floors on an air gap are on Air gap separation.
Section (5) puts a fire sprinkler system charged from or tied into a pond, lake, stream, or any water source other than the approved public supply in the high-hazard category. That case is on Fire-line backflow.
Spartanburg Water’s well section
Section 8.4 of the June 4, 2026 manual (PDF created June 5, 2026) is titled Wells. It says any building presently being served from a private well must physically disconnect from the well prior to Spartanburg Water System metered service being turned on for use.
The same section says the well can be maintained for outdoor use. If the customer desires the well to remain connected to the metered service, a reduced pressure backflow prevention device must be installed on the service line, on the customer side of the water meter, by the customer, as outlined in section 8.1.
Section 8.1 is the new-connection section. The customer gives information on how the water will be used. Spartanburg Water evaluates the service and notifies the customer of the assembly and the timeline. The customer installs it to the manual, to SCDES, and to the manufacturer. Spartanburg Water inspects. The meter is turned on when that inspection is satisfactory. Deficiencies are corrected, and a follow-up inspection is completed, before the service is turned on.
Two lines elsewhere in the same manual are easy to mix with section 8.4.
- Section 6 says a residential customer with a 3/4-inch to 1-inch service has a residential dual check installed by Spartanburg Water. Section 8.4’s reduced pressure device is installed by the customer. The dual-check house service is on the residential page. Who installs each kind of assembly is on Backflow preventer installation.
- Section 9.1 says a high hazard requires a reduced pressure principle assembly, a pressure vacuum breaker for back-siphonage only, or an air gap. Section 8.4 names a reduced pressure device for a well that stays connected. It does not name an air gap, a pressure vacuum breaker, or a double check in that paragraph. Where those sections do not read the same way, use the notice Spartanburg Water sent for the account.
Section 8.4 does not print a fee, a test interval, or a description of a hose, a tank, or a pump. It does not describe a well added after metered service is already on. A reduced pressure principle assembly that protects the public system is in section (7) of the state rule: a certified tester tests it after installation and before use, at least once a year, and again immediately after any repair. Spartanburg Water section 10.2 says existing approved backflow assemblies are tested annually, excluding low-hazard residential lawn irrigation. The notice tiers are on Spartanburg Water. RPZ testing is the assembly. The field order on the 2025 state sheets is on RPZ testing step by step.
Anderson’s table
The September 2008 Cross Connection Control Policy says Table 1 is a list of typical service connections and the hazard level characteristically associated with each use. The policy says the list is not complete, that it is a guide for Electric City personnel, and that every service is evaluated on its own. A footnote says the hazard tables are based on an American Water Works Association standard.
On the low-hazard portion of that table:
- Auxiliary water system.
- Wells (public and private), including spring-fed and surface-water systems.
- Inner-connections with surface-water intakes, with a lake irrigation system given as the example.
- Water, used, through reclamation, recycling, or other.
The coordinator evaluates each facility and uses Table 1 as a guide. A high hazard requires an air gap, a reduced pressure principal assembly, or a pressure vacuum breaker that is not used where backpressure is expected. A low hazard may use any of those, or a double check valve assembly. The policy encourages an air gap for both when a physical separation is practical. The September 2008 policy does not print Spartanburg Water’s sentence that a building on a private well is physically disconnected before metered service is turned on.
A row on the table is the guide. It is not a device selected for an address. If the writing from Electric City names a testable assembly, the form timing already summarized for Anderson customers is on Anderson, Pickens, and Oconee. Questions in the policy go to the Cross Connection Control Coordinator at (864) 231-5230. The policy still prints “SC DHEC.” Current tester cards are SCDES cards.
Greenville Water
Greenville Water’s November 10, 2025 manual defines an auxiliary water supply, in the table above. Section 2-4 says the customer shall not install or maintain any unprotected cross connection beyond the water service connection. The same section lists auxiliary water systems, with industrial fluids, recycled water, product manufacturing, processing, fire protection, irrigation, and temperature-increasing devices, as cross connections. The customer installs, tests, and maintains the assemblies Greenville Water requires, and pays for purchase, installation, testing, and maintenance. The same section says to contact the Cross Connection Control Department before buying or installing an assembly.
The manual does not print a private-well paragraph, and it does not print a sentence that a well is physically disconnected before the meter is turned on. Section 5-1 says a high hazard uses a reduced pressure principle assembly or an air gap, and a low hazard uses a double check valve assembly or a dual check. Section 5-1 does not assign a well to either category.
When an assembly is required, section 3-1 is the path for a new account: a cross-connection questionnaire, a written notice of the assembly, installation to the manual, and a site inspection before the meter is turned on. The applicant notifies the department at least two days before that inspection at (864) 241-6100. Section 3-2 is the path for an existing service the department evaluates: the same questionnaire, a written notice with an installation deadline, and the same two-day call before the inspection. The device is the one in that writing. Notice timing for a testable assembly already on the account is on Greenville Water.
Seneca, Easley, and Greer
Seneca Light & Water’s backflow manual, revised October 2021, read on October 29, 2026, does not name a private well or an auxiliary water supply in its assembly-selection list. The installation section says Seneca Light & Water reserves the right to require a testable backflow device on any water service connection the Cross-Connection Control Department deems a hazard. The rest of that manual is on Seneca Light & Water.
Easley Combined Utilities’ standard specifications, cover dated March 2025, subsection 3.6, say to ensure there are no connections between the distribution system and any pipes, pumps, hydrants, or tanks from which unsafe water or other contaminated materials may be discharged or drawn into the system. That subsection does not name a private well or an auxiliary water supply. It is a construction specification. The water page’s account of the February 2005 policy is on Easley Combined Utilities. That policy was not a separate file on the water page when the Easley page was written.
On October 29, 2026 the Greer CPW cross-connection plan linked from Greer CPW was an image PDF. This page does not add a Greer well sentence from it. The Greer page already records that section 2.4 names auxiliary water systems among cross connections. That reading was checked October 14, 2026.
Walhalla
Ordinance 2026-06, section 310-309, in the City of Walhalla’s May 26, 2026 council packet, says no part of the waterworks system shall be connected with any other water source, including well systems. The section does not print Spartanburg Water’s choice between a physical disconnect and a reduced pressure device. The rest of that ordinance is on City of Walhalla.
Starr-Iva
The water users agreement linked from Starr-Iva’s new-service page says the user will make no physical connection between any private water system and the district’s water system. A violation is grounds for disconnection. The sentence does not name a well, an air gap, or a reduced pressure assembly. The general utility easement on the forms page says the grantor shall not drill or operate any well or septic system inside the easement strip without the district’s written permission. That sentence is the easement. It is not the private-system sentence, and it does not name an assembly. The rest of the district’s form is on Starr-Iva.
If the letter names a test
Read the date, the service address, and the device. How to read your notice walks through the public forms. Hire a General Tester. County pages copy General Testers from the SCDES report printed July 9, 2026. Start with Greenville County, Spartanburg County, or Anderson County. Confirm the current card before you hire. A row on this site is not an appointment.
The regulation does not set a price for the device or the test. Section 8.4 and Anderson’s Table 1 do not print one. The cost guide keeps a third-party range, labeled as that range, separate from any utility fee. Official links are on Resources.
Spartanburg Water notices Residential testing
Sources checked October 29, 2026: R.61-58 on des.sc.gov, section 58.7(F); Spartanburg Water’s manual revised June 4, 2026, including the auxiliary-water definition, the low-hazard lawn definition, sections 6, 8.1, 8.4, 9.1, and 10.2; Anderson Electric City’s September 2008 policy, including the auxiliary-water definition, the well definitions, and Table 1; Greenville Water’s November 10, 2025 manual, including the auxiliary-water definition and sections 2-4, 3-1, 3-2, and 5-1; Seneca Light & Water’s backflow manual revised October 2021; Easley Combined Utilities’ standard specifications, cover dated March 2025, subsection 3.6. The Greer CPW plan was an image PDF the same day, and no Greer well sentence was added from it. The Walhalla sentence was checked November 7, 2026 against section 310-309 of Ordinance 2026-06 in the May 26, 2026 council packet. The Starr-Iva sentences were checked November 20, 2026 against the water users agreement and the general utility easement linked from the forms page.