SJWD Water District backflow testing
The test form leaves “Test Report Due” blank and does not print a fee. The October 2008 specifications require an air gap or a reduced pressure preventer on a high hazard.
Sources checked November 5, 2026.
The public site is sjwd.com. The home page says the district was established in 1956, that it serves western Spartanburg County, and that it first served the mill towns of Startex, Jackson, Wellford, and Duncan. The same page says it provides water to over 87,000 residents. The engineering page and the business page both say the standards and forms linked there are for information and may not be the latest versions. Ask the district before you treat an older file as the rule for a project.
The home page, the engineering page, and the business page print the same contact block: 198 Watershed Way, Spartanburg, SC 29301, Monday through Thursday 7:15AM to 5:15PM, Friday closed, phone 864-439-4423, fax 864-949-3511, postal address P.O. Box 607, Lyman, SC 29365, email sjwdservice@sjwd.com. The SCDES drinking-water record for SJWD Middle Tyger WTP, SC4220006, lists the principal county as Spartanburg. Its owner address is 307 Spartanburg Hwy, Wellford, SC 29385, and it also prints P.O. Box 607, Lyman, SC 29365-0607. The record prints 864-439-4423 and 864-949-2831. Use the address and the telephone on the letter for the account.
The purchases table on that record lists Greer CPW, Blue Ridge Water Co Inc, Spartanburg Water System, Inman Campobello W/D, and a row the record spells SPRINGS INDUSTIES/LYMAN. The service-area table marks Greer CPW and Blue Ridge Water Co Inc active, and marks Inman-Campobello and Spartanburg Water System inactive. Spartanburg Water, Greer CPW, Blue Ridge Rural Water, and Inman-Campobello notice clocks do not transfer to an SJWD account. A purchase row is the seller. Follow the letter and the current district file.
The site at sjwd.org is San Juan Water District in Granite Bay, California. Its standard details are not this district’s. Nothing on this page comes from that site.
The test form
The business page links a Backflow Device Testing Form. The engineering page links the same file. The header reads “BACKFLOW PREVENTION ASSEMBLY TEST REPORT” and “SJWD Water District.” The PDF was created January 12, 2012. Its server last-modified date on November 5, 2026 was February 25, 2023.
The form has blanks for assembly ID, facility name, account number, meter number, service address, equipment location, location ID, containment, contact name and phone, map page, serial number, manufacturer, type, size, model, install date, and permit number. A line is labeled “Test Report Due:” and another is labeled “Schedule Code.” Both are blanks. The form does not print a calendar date or a number of days. How to read your notice walks through the forms other Upstate utilities publish. Use the letter on the account for the date.
Other blanks are labeled Confinement, Freeze Protection, Hazard Type, and Haz. Level. The test table has columns for check valve number 1, check valve number 2, a relief valve, a PVB/SVB column, and shutoff valves number 1 and number 2. There is a line for line pressure at the time of the test, and a line labeled “Approved BFP.” The initial test has Pass and Fail. A repairs block has Cleaned and Replaced rows. The final test repeats the readings. Double check versus reduced pressure is how the state rule splits those two assemblies. RPZ testing is the reduced-pressure assembly. Pressure vacuum breaker is the state rule for that device. The form does not define PVB or SVB.
The tester block asks for the initial test by, a certificate, a date, a gauge number, time in, time out, the company, and a phone. It has lines for a final test and for the repair. The certification sentence reads “THE ABOVE REPORT IS CERTIFIED TO BE TRUE.” Backflow test kits is what SCDES requires of the gauge. The time-in and time-out lines are blanks. The form does not print how long a test takes.
The form does not print a fee, an email address, or a filing instruction. It does not label the district fax as the place to send the test. Ask at the telephone on the contact block before you use a filing method from another utility. Failed backflow test is how Greenville Water, Spartanburg Water, and Anderson count the days after a result that does not pass. Those clocks are not this form’s. The repairs block does not print a number of days. Backflow preventer repair is who arranges a repair on those other systems.
The approved-devices file
The engineering page and the commercial checklist page link Approved Backflow Devices. The PDF creator is Adobe Acrobat 8.1 Combine Files, dated December 1, 2008. The server last-modified date on November 5, 2026 was February 25, 2023.
The first part is headed “NOTICE OF APPROVED BACKFLOW PREVENTIVE DEVICES FOR SOUTH CAROLINA” and dated February 22, 2005. The pages carry an SCDHEC header. Item 6 of that notice says backflow prevention devices are to be tested immediately after installation and at least once a year thereafter. That sentence is the 2005 notice. It is not a day count printed on SJWD’s test form. What is backflow testing is the current state rule for who tests and how often. The model tables in the 2005 notice are not the current approved list. The January 2026 list is on Resources.
The same PDF ends with a page headed “Cross Connection and Backflow FAQ.” Those pages do not print the name SJWD, a date, or the SCDHEC header. The FAQ says the approved methods “for our area” are a reduced-pressure principle assembly, which it marks as a testable device, for high hazard applications, and a double check assembly, also testable, or a residential dual check, which it marks as non-testable, for low hazard applications. It says SCDHEC’s State Primary Drinking Water Regulations require periodic testing of testable devices and replacement of non-testable devices, and that a SCDHEC certified backflow inspector tests the device. The FAQ answer does not print the word annually, a fee, or a filing address. General vs Limited is the state card. The FAQ uses the word inspector. It does not say which card SJWD will accept on the test form above.
The typical water service detail, linked from the business page and created June 14, 2023, is a residential meter drawing. It does not name a backflow device. The tap application linked from the engineering page does not ask about irrigation, a well, or a backflow device. Residential backflow testing is the homeowner page for the utilities that have published a house rule. This page does not add a residential dual-check rule from the meter drawing.
October 2008 specifications
The engineering page links SCS-October-08.pdf under Standard Construction Specifications. The cover reads “Standard Construction Specifications For SJWD Water District, Lyman, South Carolina.” It names Stephen M. Caston, P.E., as Executive Director, and Billy Y. Cothran III, P.E., as Director of Engineering, and it prints P.O. Box 607, Lyman, S.C. 29365, and (864) 439-4423. The PDF was created October 15, 2008. The cover does not print the words October 2008.
Section 02600, Piping General Requirements, item 13, is headed “Cross Connection Control (Backflow Prevention Devices).” It says there shall be no connection between the distribution and any pipes, pumps, hydrants, or tanks whereby unsafe water or other contamination materials may be discharged or drawn into the system. The sentence prints “contamination materials.” It says no bypasses shall be allowed unless the bypass is also equipped with an equal, approved backflow prevention device. The sentence prints “by-passes” and “back-flow.”
A high hazard category cross connection requires an air gap separation or an approved reduced pressure backflow preventer. Air gap separation is the state rule and the inch minimums other Upstate manuals print. This section does not print an inch minimum for the air gap.
Reduced pressure principle assemblies shall not be installed in any location subject to possible flooding. That includes pits or vaults which are not provided with a gravity drain to the ground’s surface that is capable of exceeding the discharge rate of the relief valve. The same item says that, generally, if the assembly is installed in a pit, the drain line shall be 2 times the size of the line entering the device, and the drain cannot empty into any type of ditch, storm drain, or sewer which could flood water back into the pit.
All piping up to the inlet of the device must be suitable for potable water and NSF approved. Black steel pipe cannot be used on the inlet side of the device. Backflow preventer installation is how the other published manuals describe a new assembly.
Fire line sprinkler systems and dedicated fire lines, except those in the high hazard category, “shall be protracted by an approved double check valve assembly.” The word in the file is “protracted.” The sentence does not name a reduced pressure assembly for the high-hazard exception. Fire-line backflow is the state rule and the other published manuals.
The 2022 specifications
The business page links a different file, SCS-2022.pdf, under the same label, Standard Construction Specifications. The cover again reads “Standard Construction Specifications For SJWD Water District, Lyman, South Carolina.” It names Billy Y. Cothran III, P.E., as Chief Executive Officer, and Kim Fortner, P.E., as Chief Operating Officer, with the same post office box and telephone. The PDF was created February 16, 2022. The cover does not print “2022.” The server last-modified date on November 5, 2026 was February 25, 2023.
This file does not repeat section 02600 item 13. Section 02660, part 3.3, item K, says no cross connections between water lines and any pipes, valves, tanks, or pumps that are not part of the potable water system are allowed. Section 3.12, in the tablet method of chlorination, says water used to fill the new main shall be supplied through a temporary connection that shall include an appropriate cross-connection control device, consistent with the degree of hazard, for backflow protection of the active distribution system. That sentence is about filling a new main. It is not an annual test of a customer’s assembly, and it does not name the assembly.
The engineering page still links the October 2008 file. The business page links the 2022 file. Neither file says it replaces the other. The engineering page says the documents may not be the latest versions.
The business page’s standard details, created March 1, 2023, is one sheet of hydrant and blow-off details. The title block reads SJWD Water District, P.O. Box 607, Lyman, SC 29365, and 864-439-4423, with a date of 1/13/2022. The sheet does not use the word backflow. The water-line extension policy linked from the engineering page is Article 10, with an “Approved October 2006” line. It does not print a backflow sentence.
The vault detail
The engineering page and the business page both link Vault Details. The title block reads SJWD Water District, P.O. Box 607, Lyman, South Carolina 29365, and 864-439-4423. The PDF was created October 29, 2008. A text extract was empty. The notes below were read from the drawing.
Note 1 says the vault shall be in a non-traffic area outside the road right-of-way, completely on the customer’s property, and that vault ownership and maintenance are the responsibility of the customer or property owner. Note 5 says the vault shall not be located where it is subject to ground-water runoff, storm-drain collection and discharge, or constant water infiltration. It says the vault shall be able to drain by gravity or by alternate means, and that piping shall not be submerged. That “alternate means” sentence is this drawing’s. The gravity-drain sentence for a reduced pressure assembly in a pit is the October 2008 specification above. The drawing does not say one replaces the other.
Note 8 says all backflow prevention devices shall be approved by S.C. DHEC and by the SJWD Cross Connection Control Department. Note 9 says that for high health hazard locations, a reduced pressure type backflow prevention device shall be used, and that the reduced pressure device must be located above grade or in a vault with acceptable drainage. Note 10 says SJWD will install a meter transponder when a detector check is part of the backflow assembly. Note 11 says all backflow prevention devices must be successfully tested prior to final acceptance by SJWD. Note 12 says service will not be turned on until an agreement is executed between the owner and SJWD, and the vault is completed and accepted by the SJWD inspector.
The legend names a double check valve assembly and a double check valve assembly with a detector check. It says the strainer is provided at cost by SJWD. It does not print a dollar amount. The sheet does not print a test fee.
Private fire protection
The commercial checklist page links Private Fire Protection Systems. The file is headed Article 9. The body says “the District” and does not print the words SJWD. The PDF was created August 15, 2007. Its server last-modified date on November 5, 2026 was February 25, 2023.
Section 9.20 says the district shall have the right to conduct a cross-connection inspection on the premises at any time, and that the applicant must install and maintain the system so as to prevent leakage, waste, and backflow into the district’s system. It points to Article 7 for the related requirements. Section 9.40 says engineering calculations and plans showing the required backflow-prevention equipment are submitted for approval before a private fire-protection system is installed or revised. It says the connection shall not be made until the charges outlined in Appendix A have been received and the vault requirements have been met, and that no piping shall be covered before a district inspection. Appendix A is not in this file.
Section 9.60 says the district requires approved backflow prevention devices to maintain the integrity of the distribution system and to comply with DHEC regulations. Any fire service connection supplied by the district shall have an approved backflow prevention device. The type and the degree of protection shall be determined by the district. An approved reduced-pressure backflow prevention device is required for any fire system with corrosion inhibitors or antifreeze compounds in the system. The customer is responsible for installation, testing, and maintenance of the devices. The section refers to Article 7 for the details. Article 9 does not print a test interval, a day count, or a test fee.
The engineering page, the business page, and the commercial checklist page did not link a file headed Article 7 on November 5, 2026. The testing interval that section points to was not in the files read for this page.
Section 9.70 says a fire booster pump must keep suction pressure high enough to maintain at least 25 pounds per square inch in the affected area of the district’s system, and that in no case shall the pressure drop below 20 pounds per square inch in that area. The applicant may not install a pump that takes water directly from the district’s system without prior written permission. The section does not name the backflow assembly on that pump. Those two figures, set next to the other files that print a different number, are on Booster pumps and backpressure.
The same checklist page links Private Fire Protection Standby Fees. The sheet is headed “MONTHLY PRIVATE FIRE PROTECTION CHARGE” and “Billed separately from normal water usage.” The header reads SJWD Water District, PO Box 607, Lyman, SC 29365, 864-439-4423. The PDF was created October 15, 2008. Inside the district, and then outside, the table prints $4.85 and $6.06 for a 2-inch line, $14.70 and $18.38 for 3-inch, $80.60 and $100.75 for 6-inch, $168.72 and $210.90 for 8-inch, $290.07 and $362.59 for 10-inch, and $458.80 and $573.50 for 12-inch. It does not print a 4-inch row. Those amounts are the monthly charge on this sheet. They are not a fee for a backflow test.
The home page links a 2024 Budget & Rates sheet dated January 1, 2024 through December 31, 2024. That sheet prints monthly water rates and usage rates. It does not print a private fire-protection charge or a backflow test fee. It does not say the 2008 table is still the amount on a bill. Use the amount on the bill. The cost guide is a third-party range for a hired test. It is not either of these sheets.
Finding a tester
Spartanburg County testers are General Testers from the SCDES report dated July 9, 2026. This site does not copy a tester list from SJWD. A row here is not an appointment. Confirm the card is still current, and confirm with the district that the tester’s category is one it will accept on the form above. A Spartanburg County address can be on Spartanburg Water, on Inman-Campobello, or on this district. Use the name on the bill.
Official links are on Resources.
Spartanburg County testers SJWD engineering page
Sources checked November 5, 2026: the SJWD home page, including the 1956 and mill-town sentences, the “over 87,000 residents” sentence, the contact block, and the link to the 2024 Budget & Rates PDF; the engineering page, including the “may not be the latest versions” line and the links to SCS-October-08.pdf, the vault detail, the test form, the approved-devices PDF, the water-line extension policy, and the tap application; the business page, including the same caution, the contact block, and the links to the test form, SCS-2022.pdf, StandardDetails3-1-2023.pdf, the vault detail, and the typical water service detail; the commercial checklist page, including the links to the approved-devices PDF, Private Fire Protection Systems, and Private Fire Protection Standby Fees; the test form PDF (created January 12, 2012; server last-modified February 25, 2023); the approved-devices PDF (combined December 1, 2008; server last-modified February 25, 2023), including the February 22, 2005 SCDHEC notice and the undated FAQ; SCS-October-08.pdf (created October 15, 2008), section 02600 item 13; SCS-2022.pdf (created February 16, 2022; server last-modified February 25, 2023), section 02660 part 3.3 item K and section 3.12; the vault detail PDF (created October 29, 2008), notes 1, 5, and 8 through 12 and the strainer legend, read from the drawing because a text extract was empty; the typical water service detail (created June 14, 2023); the tap application PDF; the water-line extension policy (Article 10, “Approved October 2006”); StandardDetails3-1-2023.pdf (created March 1, 2023); Article 9 (created August 15, 2007; server last-modified February 25, 2023), sections 9.20, 9.40, 9.60, and 9.70; the monthly private fire-protection charge sheet (created October 15, 2008); the 2024 Budget & Rates sheet (dated January 1, 2024 through December 31, 2024), which does not print a test fee or a fire-protection charge; and the SCDES drinking-water record for SJWD Middle Tyger WTP, SC4220006, including the principal county, the Wellford street address, the two telephone numbers, the water-purchases table, and the service-area status marks. The engineering, business, and checklist pages did not link a file headed Article 7. sjwd.org was opened only far enough to identify it as San Juan Water District in California, and its files were not used.