Car wash backflow requirements in Upstate SC
The state cross-connection section does not name a car wash. Greer CPW lists car washes as a common high hazard. Anderson’s table lists them as low hazard. The letter on the account is the device.
Sources checked November 16, 2026.
If this page and the letter on the account disagree, follow the letter. What is backflow testing is the state test. Double check versus reduced pressure is the hazard split in the regulation and in the Greenville Water, Spartanburg Water, and Anderson manuals. A restaurant is a different line on the manuals that name one. Those lines are on Restaurant backflow. A dental office is a different line on the manuals that name one. Those lines are on Dental office backflow. A car wash on another system uses that utility’s notice.
The state rule does not name a car wash
R.61-58.7(F) sorts a cross connection by hazard. Section (2) calls a low hazard a connection to another water source that is not hazardous to health and is not cross-connected inside its own system with a potentially dangerous substance. The minimum it names there is an approved double check valve assembly or a pressure vacuum breaker, except for the residential lawn policy in section (3). Section (4) calls a high hazard a connection to a service or other water system that has or may have any material dangerous to health. The protection it names is an air gap or an approved reduced pressure principle assembly.
A text reading of the regulation PDF on November 16, 2026 did not contain the words car wash. Section (F) does not print a car-wash rule or a day count that applies only to a car wash. The annual test in section (7) is the test for an assembly installed to protect the public system, except for the residential lawn policy in section (3). It is not a separate car-wash schedule. The SCDES program page describes the cross-connection program and the tester course. The retrieved text of that page did not contain the words car wash.
Where the words appear
| Source | Car-wash line | Assembly that line names |
|---|---|---|
| R.61-58.7(F) | Does not use the words. | By hazard, in sections (2) and (4). No car-wash row. |
| Greer CPW, plan amended April 2025, section 5.2 | Car washes are on the common high-hazard list. The list says “include but not limited to.” | A reduced pressure principle assembly, ASSE 1013, for the high-hazard category, subject to the on-site adjustment in that section. |
| Anderson Electric City, September 2008 policy, Table 1 | Car washes are their own low-hazard line. Auto garages and shops are a different low-hazard line. | The coordinator chooses. A low hazard may use a double check valve assembly or one of the high-hazard devices. |
| Seneca Light & Water, manual revised October 2021 | Car washes are one use on the reduced-pressure bullet. The public page does not use the words. | That bullet says a reduced pressure assembly is required on the uses it names. The supervisor still names the device. |
| City of Pickens public-works page | Car washes are on the list of common places that require a device. | The list does not name an assembly and does not mark high or low. |
A car dealership and an automotive garage are not the car-wash line at Greer CPW. Those two names are on the common low-hazard list in the same section. Anderson’s table keeps auto garages and shops on a low-hazard line other than car washes. Seneca’s reduced-pressure bullet names auto repair garages and oil-changing garages together with car washes. This page does not give one of those marks to the other. How the files that name a garage or a dealership classify it is on Automotive garage and car dealership backflow.
Greer CPW
Section 5.2 of the cross-connection control plan amended April 2025 says a reduced pressure principle assembly (ASSE 1013) is used for a high hazard, and a double check valve assembly (ASSE 1015) is used for a low hazard. The plan was read from the scan. Common high-hazard facilities “include but not limited to” a list that includes car washes. The same list includes hospitals, dental clinics, and mortuaries and funeral homes, and it continues with other facility types printed in that section. A car wash is on the high-hazard list. It is not on the common low-hazard list.
The common low-hazard list in that section names restaurants, car dealerships, and automotive garages, among other uses. A car dealership is not the car-wash bullet. An automotive garage is not the car-wash bullet. The same section says the containment requirements for the three hazard categories may be adjusted based on the internal plumbing found at the on-site inspection. The high-hazard mark is the list. It is not a sentence that the inspection cannot change the assembly. Greer CPW is the rest of that plan, including the ten-day report on a new assembly and the same-day report after a failure. Greenville County testers are General Testers from the July 9, 2026 SCDES list. That section of the report includes rows whose city is printed as Greer.
Appendix D is a partial list of typical facility types that require service-line protection. It says other facilities not on the list may still be required to install that protection, at the authority’s discretion. Item 17 is “Car washes.” The appendix does not mark that item high or low. The car-wash classification is section 5.2, not Appendix D.
The questionnaire in Appendix A is headed “CCC QUESTIONAIRE.” The form prints that spelling. Its mechanical-equipment checkboxes do not include a car wash. The test report in the same appendix has a blank, “Define Hazard,” and the examples in parentheses are beauty shop, restaurant, irrigation, car lot, medical facility, and so on. Those examples do not print car wash. A car lot on that blank is not item 17 and it is not the section 5.2 high-hazard list. That blank is a place to write the hazard for the assembly being tested.
Anderson’s table
Table 1 of the September 2008 Cross Connection Control Policy is a list of typical service connections and the hazard level the policy associates with each use. The policy says the list is not complete, that it is a guide for Electric City personnel, and that every service is evaluated on its own. A footnote says the hazard tables are based on an American Water Works Association standard.
The introduction, before the table, says there have been numerous high-profile backflow and backsiphonage incidents associated with industry, boiler systems, wastewater treatment facilities, car washes, and in-ground irrigation systems, and that those incidents have led to illnesses and deaths. It does not print a count. It does not say that every use on that list caused a death. That sentence is not Table 1.
“Car Washes” is its own line on the low-hazard side of Table 1. It is not the restaurant line, and it is not the medical-facilities line. “Auto Garages and Shops” is a different low-hazard line. The policy does not put a car wash on the high-hazard side of the table.
The coordinator evaluates each facility and uses Table 1 as a guide. A high hazard requires an air gap, a reduced pressure principal assembly, or a pressure vacuum breaker that is not used where backpressure is expected. A low hazard may use any of those, or a double check valve assembly. The policy encourages an air gap for both when a physical separation is practical. The table’s low-hazard mark is the guide. It is not a sentence that every car wash in the city receives a double check. Deadlines for the test form are on Anderson, Pickens, and Oconee. Anderson County testers are General Testers from the July 9, 2026 SCDES list.
Seneca Light & Water
The backflow prevention page says the Cross-Connection Control Supervisor will notify the customer which device in the procedure manual best protects the system. A text reading of that page on November 16, 2026 did not contain the words car wash.
The manual revised October 2021 puts car washes on the reduced pressure assembly bullet, together with other uses named in the same bullet. The bullet says that assembly is required on those uses, that it is a high-hazard device, and that it requires annual testing by a certified tester. The same bullet names auto repair garages and oil-changing garages. It names one more facility type that is already on the high-hazard commercial page. This page does not repeat that name. The double-check bullet does not print car wash. The next bullet on the double-check assembly says every commercial customer applying for water service after January 1, 2009 has a double check valve assembly, unless the supervisor waives it as unnecessary. That sentence does not name a car wash. The manual says the supervisor names the device for the service. Seneca Light & Water is the installation section and the initial test that manual describes. Oconee County testers are the General Testers in that county on the July 9, 2026 list.
City of Pickens
The public-works page prints “A List of common places that require a backflow prevention devices,” and car washes are the first name on that list. The list does not mark any place high or low, and it does not name the assembly. Two other names on that list are already on the high-hazard commercial page and are not repeated here. The same section says routine testing follows R.61-58 and that results go to the public-works post office box printed on the page. It does not print a due date. City of Pickens is the filing address and the two test forms. Pickens County testers are the General Testers in that county.
Files that do not use the words
A text reading on November 16, 2026 did not contain the words car wash in any of these files. Silence in the file is not a finding that the account has no assembly. Use the notice.
- Greenville Water’s backflow page and the manual created November 10, 2025. Section 5-1 says a reduced pressure principle assembly or an air gap is used for a high hazard, and a double check valve assembly or a dual check is used for a low hazard. The section does not name a facility type. Greenville Water is the notice and the portal. Greenville County testers are the General Testers in that county.
- Spartanburg Water’s manual revised June 4, 2026, section 7(a), names sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries, and plating plants as examples of premises protected by an air gap or a reduced-pressure principle assembly. A car wash is not in that list. Section 7(b) does not name a facility. The cross-connection page and the commercial and industrial page did not contain the words. Spartanburg Water is the manual’s notice language. Spartanburg County testers are the General Testers in that county.
- The City of Clemson water page and the backflow flyer name fire protection systems, irrigation systems, gasoline refineries and stations, restaurants, hospitals, and manufacturers. The sentence says the list includes, but is not limited to, those uses. A car wash is not in that list. The pages do not name a double check or a reduced pressure assembly for that list. The flyer’s three-year sentence is homeowner irrigation. City of Clemson is the water page, both flyers, and the code section already summarized there.
- Laurens County Water and Sewer Commission’s backflow page prints low-hazard examples of fire protection, trailer parks, churches, restaurants, and commercial irrigation, and high-hazard examples of fire protection with chemical addition, irrigation with chemical addition, and industries with potentially dangerous cross connections. A car wash is not in either sentence. The clocks are on Laurens.
- City of Clinton’s water distribution page lists medical or industrial facilities among common risks, together with irrigation systems, garden hoses submerged in pools or containers, fire-sprinkler systems, commercial equipment, and boilers. The page does not print car wash. Clinton is the 2026 test form.
- Easley Combined Utilities’ water page and the standard specifications with a March 2025 cover. The water page’s backflow sentences are the definition of backflow and the residential lawn dual-check line. Easley Combined Utilities is that page, the test form, and the specifications.
- Powdersville Water’s cross-connection policy, revised September 2024. Section 7 is a selection guide. It does not print car wash. Powdersville Water is the 90-day letter and the rest of that policy.
- The City of Westminster’s Cross-Connection Control Policy, revised September 12, 2024, in the November 12, 2024 council packet. A text reading of that packet did not contain the words car wash. Section 2.2’s examples of material dangerous to health do not name a car wash. City of Westminster is the 90-day letter and the rest of the policy.
- Blue Ridge Rural Water’s company policies PDF. Section 14 says device selection is based on degree of hazard. A high hazard location uses an approved reduced pressure principal assembly. A low hazard location uses an approved double check or an approved dual check. The section does not name a car wash. Blue Ridge Rural Water is the rest of section 14.
- Gaffney Board of Public Works’ water construction specifications. Gaffney is the test form and those specifications.
What to do with the letter
Hire a General Tester, the classification that may test for the public. County pages on this site copy that classification from the SCDES report printed July 9, 2026. Confirm the current card before you hire. A row on this site is not an appointment.
The letter names the assembly, the date, and where the report goes. How to read your notice is the reading for the forms Greenville Water, Spartanburg Water, and Anderson publish. A failed result is on Failed backflow test. A repair, and the retest after it, is on Backflow preventer repair. Who the Greenville Water, Spartanburg Water, and Anderson manuals count as a business account is on Backflow assembly testing.
The regulation does not set a price for the device or the test. None of the car-wash lines above print a test fee for a tester the customer hires. The cost guide is a third-party range for a test a customer hires. It is not a car-wash price and it is not a utility fee. Official links are on Resources.
Assembly testing for businesses Greer CPW
Sources checked November 16, 2026: R.61-58 on des.sc.gov, including section 58.7(F); the SCDES program page; Greenville Water’s backflow page and the manual created November 10, 2025, including section 5-1; Spartanburg Water’s manual revised June 4, 2026, including section 7, the cross-connection page, and the commercial and industrial page; Anderson Electric City’s September 2008 policy, including the introduction, Table 1, and the device section that follows the table; Greer CPW’s cross-connection control plan amended April 2025, read from the scan, including section 5.2, the adjustment sentence, Appendix A’s questionnaire and test form, and Appendix D item 17; Seneca Light & Water’s backflow page and the manual revised October 2021, including the double-check and reduced-pressure bullets; Laurens County Water and Sewer Commission’s backflow page; the City of Clinton water distribution page; the City of Pickens public-works page; the City of Clemson water page and the backflow flyer; Easley Combined Utilities’ water page and the specifications with a March 2025 cover; Powdersville Water’s September 2024 cross-connection policy, including section 7; Blue Ridge Rural Water’s company policies PDF, section 14; Gaffney Board of Public Works’ water construction specifications; and the City of Westminster November 12, 2024 council packet, including the Cross-Connection Control Policy revised September 12, 2024.