Fire-line backflow testing in Upstate SC

A dedicated fire line serves only fire protection. South Carolina requires an approved backflow assembly on that line. The hazard decides the assembly. Your utility’s notice names the one on the account.

Sources checked October 11, 2026.

If this page and the letter on your account disagree, follow the letter and the manual it cites. What is backflow testing is the general annual-test rule. RPZ testing is the reduced pressure principle assembly. Double check versus reduced pressure is how those two assemblies differ before the fire-line rules below. This page is the fire-line case on the three Upstate utilities that publish a manual.

What the state rule requires

R.61-58 defines a dedicated fire line as a water line connected to a public water system, designed and used solely for a fire protection system. That definition says the line must have an acceptable and approved backflow prevention device, and it must not connect downstream of that device to water lines or fixtures used for potable water.

R.61-58.7(F)(5) is the fire-sprinkler paragraph:

  • Fire-line sprinkler systems, except those in the high-hazard category, are protected by an approved double check valve assembly.
  • High-hazard fire sprinkler systems include, but are not limited to, antifreeze systems, foam systems, and systems charged from or tied into ponds, lakes, streams, or any water source other than the approved public water supply.
  • A high-hazard fire sprinkler system has to meet section (4): an air gap or an approved reduced pressure principle assembly. Section (4)(b) says those assemblies are not installed where flooding is possible. That includes a pit or vault without a gravity drain to the ground surface that can pass more water than the relief valve discharges. The minimum distance each manual prints for that air gap is on Air gap separation.

Section (7) is the test. When a double check valve assembly, a pressure vacuum breaker, or a reduced pressure principle assembly protects the public system, a certified tester tests it after installation and before the customer uses it. Except for the low-hazard residential irrigation schedule in section (3), each of those assemblies is tested at least once a year. After any repair, the assembly is tested again immediately. The tester sends the written report to the water system.

R.61-58.1(B)(14) says a dedicated fire line protected by an approved backflow prevention device at the point of connection to the distribution line will not require a Department permit to construct. That sentence is about the Department’s construction permit. It does not replace a utility’s plan review, contract, or a local encroachment permit. Greenville Water’s section 6-1, below, still lists those steps before a tap.

Section (6) says the Department publishes a list of approved assemblies and updates it at least once a year. Assemblies used in South Carolina have to be on that list.

Detector assemblies on the state list

A double check valve assembly and a detector assembly are not the same part. Greenville Water’s manual and Spartanburg Water’s manual both define a double detector check assembly as a main-line double check with a small bypass that includes a double check and a meter, used to detect leakage or unauthorized use of water on fire lines.

The January 1, 2026 approved-assembly list separates two factory-built versions for fire sprinkler systems:

  • A Type I double check detector assembly or reduced pressure detector assembly has two assemblies, one on the main line and one on the bypass. Both are tested. A meter on the bypass detects water use. The list says that meter should be read periodically if the detector assembly is to be of any value. It does not print a reading schedule. The Type I section says these assemblies are designed for fire-line sprinkler use and are built from double check valve assemblies and reduced pressure principle assemblies approved elsewhere on the list.
  • A Type II assembly has one double check or one reduced pressure principle assembly on the main fire line. The bypass is installed at or near test cock number 3, and that bypass has a single check valve after the water meter.

Both types have to be assembled by the manufacturer and shipped as a complete unit. A field alteration has to meet the manufacturer’s specifications or those of the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research.

SCDES’s sample test form labels a reduced pressure detector assembly as RPDA, ASSE #1047, and a double check detector assembly as DCDA, ASSE #1048. The form says many jurisdictions require their own form.

Greenville Water

The manual (PDF created November 10, 2025; the policy inside was adopted September 6, 2022) says most commercial, industrial, irrigation (as noted), and private fire-protection customers install, maintain, and test the assembly on the service. Questions in the manual go to the Cross Connection Control Department at (864) 241-6100. Greenville Water’s backflow page says the utility does not install or test backflow preventers.

Section 6 is the fire-suppression section.

Section 6-1 is how a new private fire-protection service is opened. Three copies of plans go to the Cross Connection Control Department. The minimum the manual lists on those plans:

  • Private fire-protection piping, internal and underground, with a material list, and the direction valves and fire hydrants open.
  • The street beside the property and the distance to the nearest intersection.
  • The size of the water main in the street.
  • A fire-protection pit on private property near the public right-of-way. The plan and elevation include pit dimensions, a note that the pit is precast concrete or concrete block, the access hatch (the manual names Bilco, Halliday, or an approved equal with a slamlock), the type of double check valve assembly, and the location of the test cocks.
  • The property owner’s name, address, and phone number. If the owner is a company, the official’s name and title.

Before the tap, section 6-1.2 requires Greenville Water’s plan approval, payment of applicable tapping fees, a copy of the State, City, or County encroachment permit, two original fire-protection contracts signed by the customer (the manual says faxed copies will not be accepted), and a finished pit that matches the approved plans and has passed Greenville Water’s final pit inspection. That section does not print a dollar amount for the tapping fee. Excavation, backfill, final valve-box adjustment, and pavement replacement are the contractor’s work. When the system is put into service, the contractor notifies Greenville Water so the tapping valve can be checked fully open. Greenville Water then assigns an account number and returns a copy of the fire-protection contract.

Section 6-2 says each private fire-protection system is evaluated by a site or plan survey. The assembly has to match the hazard, on every connection to Greenville Water.

  • Section 6-2.1: a high hazard includes, but is not limited to, antifreeze systems, foam injection systems, and systems supplied from or connected to lakes, ponds, streams, or any source other than Greenville Water. That case requires a reduced pressure principle assembly, as close as possible to the service connection and the property line.
  • Section 6-2.2: a low hazard includes a simple wet or dry fire sprinkler system. That case requires a double check valve assembly, as close as possible to the service connection and the property line.

The definitions section describes a double detector check. Section 6-2.2’s low-hazard sentence names a double check valve assembly. This page does not treat those two names as the same device. Use the assembly named on the notice and on the approved plans.

In isolated cases the assembly has to be inside the building. Section 6-2.2 says a double check valve assembly is then installed on the riser piping immediately above the floor. An interior assembly is not used when that location would take more than 50 feet of pipe from the water-main tap to the riser.

Section 7 says a certified tester tests backflow prevention assemblies. A new testable assembly is tested at installation, before the customer uses it, and the report has to reach Greenville Water within 10 days of the water service starting. Existing assemblies are tested at least annually. The customer has the test made within 45 days of the scheduled due date. Notice timing and the non-compliance fee are on the Greenville Water page. Who installs a new assembly is on Backflow preventer installation.

Spartanburg Water

The manual revised June 4, 2026 (PDF created June 5, 2026) is linked from Spartanburg Water’s commercial and industrial page, in the Cross Connection Control and Backflow section. On October 11, 2026 the older path /ccc-and-backflow redirected to that page. The section still names Matthew Jamison, Field Operations Manager, at (864) 598-7213 or ccc@spartanburgwater.org.

Section 9.5 says each private fire-protection system is evaluated by a site or plan survey. The assembly has to match the hazard, on every connection to Spartanburg Water.

  • A high hazard includes, but is not limited to, antifreeze systems, foam injection systems, and systems supplied from or connected to lakes, ponds, streams, or any source other than Spartanburg Water. That case requires a reduced pressure assembly or an air gap, as close as possible to the service connection and the property line.
  • The manual defines a remote high-hazard fire system as a fire system with an isolated section that has an antifreeze system or another chemical injection system. It is acceptable to protect that system with a reduced pressure assembly at the chemical addition or at the water connection.
  • A low hazard includes simple wet or dry fire sprinkler systems. The same paragraph says these systems may also include covered storage tanks or pumps supplied by Spartanburg Water. A double detector check assembly is required, as close as possible to the service connection and the property line. That paragraph does not print a pounds-per-square-inch floor. The 20, 25, 30, and 50 psi lines in other files, and Seneca’s rule that a booster pump is not used with a pressure vacuum breaker, are on Booster pumps and backpressure.

In isolated cases the assembly has to be inside the building. A double check valve assembly is then installed on the riser piping immediately above the floor. That location has to be on the building drawings and approved in writing by Spartanburg Water.

Section 9.6 says no backflow prevention assembly is removed, bypassed, or downgraded without prior written approval from Spartanburg Water.

Section 10.2 says existing approved backflow assemblies are tested annually, excluding low-hazard residential lawn irrigation systems. The notice tiers and the administrative fee are on the Spartanburg Water page. The published field test report is the form linked from the same public page.

Anderson Electric City

The September 2008 Cross Connection Control Policy says Table 1 is a guide and that every service is evaluated on its own. On that table:

  • Fire protection systems with injection are listed as high hazard.
  • Fire protection systems without injection are listed as low hazard.
  • Fire protection that uses onsite storage is listed as low hazard.

Section (5) of the state rule treats a system charged from or tied into a pond, lake, stream, or any source other than the approved public supply as high hazard. The policy says the table does not replace a case-by-case evaluation. Use the notice Electric City sends for the account.

The fire-lines paragraph covers dedicated fire lines that are not metered. Those lines must have a reduced pressure principle detector assembly or a double detector check valve assembly at or near the earliest reasonable point beyond the service connection. The type depends on the hazard in Table 1. The paragraph does not state a separate device for a metered fire line. Check the notice for that account.

If there is no water meter, as on a fire line, the device-installation section says the device goes on the customer’s property next to the right-of-way boundary. Butterfly valves are not permitted except on fire-flow device applications, and only when the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research has approved that valve.

Commercial, industrial, and dedicated fire lines are tested when the device is installed and every 12 months after that. Results have to meet Table 2. The tester has a current SC DHEC card and is in good standing with Electric City. Current cards are SCDES cards, as the program page describes. Reminder letters go out about 30 days before the test is due. Table 2 prints minimums for a reduced pressure assembly and for a double check valve assembly. It does not print a separate detector-assembly row. The reduced-pressure bands are on RPZ testing. The 10-day test-form rule is on the Anderson, Pickens, and Oconee page.

Appendix 2 includes a form line, “Name of Alarm Company Called,” for devices on dedicated fire lines. The explanation says the tester writes the name of the business called so that business knows an alarm may sound during the test. The policy does not name that business.

If your water system is not one of these three

Greer CPW’s fire-suppression categories are on Greer CPW. Seneca Light & Water’s fire-sprinkler assemblies are on Seneca Light & Water. The double-check sentence in Easley Combined Utilities’ March 2025 specifications, and the high-hazard exception that sentence does not fill in, are on Easley Combined Utilities. The double-check sentence for fire line sprinkler systems and dedicated fire lines in Blue Ridge Rural Water’s September 30, 2025 specifications, and the high-hazard exception that sentence does not fill in, are on Blue Ridge Rural Water. Inman-Campobello’s specifications, section 2L-03, require at least a double detector check valve assembly on a dedicated fire line. The monthly fire-protection charges on the rates page are a supply-line fee, not a test fee. That page is Inman-Campobello. SJWD’s October 2008 specifications, section 02600 item 13, say fire line sprinkler systems and dedicated fire lines, except those in the high hazard category, shall be protracted by an approved double check valve assembly. The word in the file is “protracted.” Article 9 requires an approved reduced-pressure device when the fire system contains corrosion inhibitors or antifreeze. The monthly amounts on SJWD’s charge sheet are a supply-line fee, not a test fee. That page is SJWD. The City of Clemson’s backflow flyer says all fire lines are required to have an approved backflow prevention device. It does not name the assembly. That page is City of Clemson. The City of Walhalla’s section 310-305 requires at least a testable double check valve or a reduced pressure backflow preventer on a sprinkler system or a similar business or commercial fire-protection device, on the customer’s side of the connection. A missed test on that device is billed at $75 when the city sends a contract tester. That page is City of Walhalla. The City of Westminster’s section 10 prints a double check for fire Classes 1, 2, and 3, and an air gap or a reduced-pressure assembly for Classes 4 and 5. Section 10.2 then requires a double check and a UL-approved meter on every new or renovated fire sprinkler system. The definition says a double detector check cannot be used in a new installation. That page is City of Westminster. Walhalla’s $75 is not Westminster’s Appendix A. This page does not state a fire-line rule for any utility that has not published the document cited here. Section (5) still applies. The assembly, the test date, and the place the report goes are on that utility’s notice.

Who can test it

In R.61-58, a certified tester holds an up-to-date card from the Department. The classification that tests for the general public is the General Tester. A Limited Tester tests only assemblies the employer owns. General vs Limited has the course and the gauge rule.

County pages copy General Testers from the SCDES report printed July 9, 2026. Start with Greenville County, Spartanburg County, or Anderson County. Confirm the current card before you hire. A row on this site is not an appointment, and it is not a list of fire-sprinkler contractors.

This site does not publish a fire-line price. The cost guide keeps a third-party range for the test, labeled as that site’s range, and keeps utility fees separate. Official links are on Resources.

Greenville County testers RPZ testing

Sources checked October 11, 2026, with the Inman-Campobello sentence checked November 3, 2026 against section 2L-03 of the complete specifications and the monthly fire-protection table on the rates and rules page, the SJWD sentence checked November 5, 2026 against section 02600 item 13 of SCS-October-08.pdf, section 9.60 of the private fire-protection file, and the monthly private fire-protection charge sheet, the Clemson sentence checked November 6, 2026 against the Backflow Prevention PDF linked from the city water page, and the Walhalla sentence checked November 7, 2026 against section 310-305 of Ordinance 2026-06 in the May 26, 2026 council packet: R.61-58 on des.sc.gov, including the dedicated-fire-line definition, R.61-58.1(B)(14), and R.61-58.7(F)(5); the SCDES program page; the January 1, 2026 approved-assembly list; the SCDES sample test form; Greenville Water’s backflow page and November 10, 2025 manual; Spartanburg Water’s commercial and industrial page, in the Cross Connection Control and Backflow section, and the June 4, 2026 manual; and Anderson Electric City’s September 2008 policy. The Westminster sentences were checked November 13, 2026 against section 10, section 10.2, and the double detector check definition in the Cross-Connection Control Policy revised September 12, 2024, in the November 12, 2024 council packet.