Greer CPW backflow testing
Greer Commission of Public Works publishes a cross-connection plan and a later customer-care policy. They do not describe the annual non-residential test the same way. Follow the letter on the account.
Sources checked October 14, 2026.
The plan linked from Greer CPW’s forms and resources page is the Cross-Connection Control Plan PDF. The cover says Amended April 2025. The same forms page links the Customer Care Policy Manual PDF. That manual says the revised policy is effective July 14, 2026. Both files, and the forms page, print the phone (864) 848-5500. The forms page and the manual list the office at 301 McCall Street, Greer, SC 29650.
The plan says it can change without notice to meet drinking-water regulations, and that the customer is responsible for the current copy. Current copies are available by calling the number above. If this summary and the letter on your account disagree, follow the letter and the current manual.
What the plan requires
Section 1.1 says the primary method of cross-connection control is a backflow prevention assembly on the customer’s service line. It says all commercial, industrial, and private fire protection customers are required to install, maintain, and test a backflow prevention assembly on that line.
Section 2.4 says the customer installs, tests, and maintains the assemblies Greer CPW requires. The customer pays for purchase, installation, annual testing, and maintenance, even when the customer does not own the plumbing past the service connection. The same section says to contact Greer CPW before buying or installing an assembly. It names auxiliary water systems, industrial fluids, recycled water, product manufacturing, fire protection, irrigation, and temperature-increasing devices as cross-connections. The customer also maintains thermal expansion tanks, relief valves, and pressure-reducing valves. Who installs, and who tests, on the other published Upstate manuals is on Backflow preventer installation.
Section 2.1 says customers are notified of the required annual test. Section 2.3 says the South Carolina Department of Environmental Services trains and certifies testers, keeps the tester list, and publishes the list of approved assemblies. What is backflow testing is the state rule those sentences sit under. The card types are on General vs Limited.
Two documents, two descriptions of the annual test
Section 8.2 of the April 2025 plan says customers with an existing assembly are notified by letter. The customer contacts a certified tester and has the test made within 30 days of that notice. The completed report is returned within 7 days of the test. The plan says all test forms are received within 37 days.
Section 180.40 of the customer-care policy effective July 14, 2026 says every non-residential account must have a backflow prevention device inspected annually by an SCDES-certified backflow prevention assembly tester. The next sentence says Greer CPW is currently using a third party to annually test backflow devices. It says the cost of installation, repair, or re-testing after a repair is the customer’s. It does not name the third party, and it does not print a dollar amount.
The plan tells the customer to hire the tester after the letter. The later customer-care policy says Greer CPW is using a third party for the annual non-residential test. This page does not choose between those sentences. Use the letter on the account, or call (864) 848-5500.
If the report is late
Section 8.4 says a customer who has not returned a completed test report within the 37-day period is non-compliant. Greer CPW then does one of two things.
- If the assembly is at the property line or the meter, Greer CPW hires a certified general tester. The general tester’s fee, plus the current Greer CPW administration fee, is added to the water bill. The plan does not print either amount.
- If the assembly is not at the property line or the meter, section 8.4 points to section 4.3.
Section 4.3 says water service is discontinued after written notice when assemblies are not installed, tested, or maintained as the policy requires. The letter says discontinuance will occur if the problem is not corrected within five days. During those five days the customer may come to the Greer CPW offices to be heard by a designate of the Commission. Removing or bypassing an assembly, or falsifying test results, is also grounds for discontinuance. Service stays off until the condition is corrected to the current plan. The customer pays applicable reconnection fees. The plan does not print those fees. It says Greer CPW is not liable for damages, losses, or claims arising from discontinuance of water service.
Section 10 says an appeal of a requirement is submitted in writing to the General Manager at least two weeks before a regularly scheduled Commission meeting. If an appeal is made, discontinuance does not occur until the Commission has decided.
The day counts Greenville Water and Spartanburg Water print are on Greenville Water and Spartanburg Water. Those clocks are not Greer’s.
A failed test
Section 8.2 says that if the assembly fails and cannot be repaired immediately, with repair parts on order as the plan’s example, the tester returns a copy of the test report explaining the failure the same day. After the repair, the assembly is tested immediately and the completed report goes back the same day. How the other published Upstate manuals treat that report is on Failed backflow test.
Section 8.1 says a new assembly is tested upon installation and before the customer uses it. The installer contacts a certified tester. Greer CPW must receive the report within 10 days of the water service starting.
Section 8.3 says Greer CPW may choose recently returned reports and retest those assemblies at its own expense. The customer is notified in advance. The plan describes that retest as a check on testers and on SCDES requirements.
Residential irrigation
Section 7.2 says Greer CPW will not require testing of double check assemblies on low-hazard residential irrigation. The plan cites amendments to R.61-58, cross-connection control, as of April 29, 2005, and names the Department of Health and Environmental Control in that paragraph. It says Greer CPW maintains dual check assemblies for those systems. Greer CPW installs them and changes them out on a ten-year basis. Existing residential irrigation dual checks are changed out over a five-year period, based on the latest double check assembly test date, which the plan says complies with the existing cross-connection policy. The initial change is billed to existing low-hazard residential customers at the cost set forth by Greer CPW. The plan does not print that cost.
Section 180.40 of the July 14, 2026 policy uses different words for a residential account that has an irrigation system. It says the account must have a backflow prevention device inspected every ten years, that Greer CPW will ensure this inspection is made, and that the inspection charge is added to the customer of record’s account. It does not print the charge.
The state irrigation split, and how Greenville Water, Spartanburg Water, and Anderson treat a lawn system, is on Irrigation backflow testing.
Which assembly
Section 5.2 assigns a reduced pressure principle assembly (ASSE 1013) to a high hazard, a double check valve assembly (ASSE 1015) to a low hazard, and a dual check (ASSE 1024) to a minimal hazard. It says those containment requirements may be adjusted after the on-site inspection of the internal plumbing. Double check versus reduced pressure is the state hazard split. RPZ testing is the reduced pressure assembly.
Examples section 5.2 lists as high hazard include hospitals, dental clinics, mortuaries and funeral homes, and car washes. Examples it lists as low hazard include restaurants, office buildings, and untreated lawn irrigation. Examples it lists as minimal hazard include single-family homes and small offices. The full lists are in section 5.2 and Appendix D. Appendix D says its list is partial, and that other facilities may be required to install service-line protection. The restaurant entry is in the section 5.2 low-hazard list. Appendix D does not name a restaurant. Restaurant backflow reads that line against the other utilities that name one. Dental office backflow reads the dental-clinic line against the other utilities that name a dentist or a clinic. Car wash backflow reads the car-wash line against the other utilities that name one. Car dealerships and automotive garages are on the low-hazard list in the same section. They are not that car-wash line. Automotive garage and car dealership backflow reads those two names against the other utilities that name a garage.
Section 6 says each private fire protection system is evaluated by a site and plan survey. High-hazard systems, including antifreeze, foam injection, and systems supplied from a lake, pond, stream, or any source other than Greer CPW, require a reduced pressure principle assembly (ASSE 1013 or 1047) as close as possible to the service connection and the property line. Low-hazard systems, described as simple wet or dry sprinklers, including systems that may have covered storage tanks or pumps supplied by Greer CPW, require a double detector check assembly (ASSE 1015 or 1048) in that location. When the assembly has to be inside the building, the plan says a double check valve assembly (ASSE 1015 or 1048) goes on the riser piping immediately above the floor. Fire-line backflow is the state rule and the other three manuals.
Section 7.1 says every commercial lawn irrigation system supplied by Greer CPW has an approved backflow prevention assembly, installed in accordance with the South Carolina Plumbing Code. The minimums it lists are a reduced pressure assembly (ASSE 1013) for treated irrigation, a double check valve assembly (ASSE 1015) for non-treated non-residential and residential irrigation, a pressure vacuum breaker (ASSE 1020) installed at least 12 inches above the highest point of the irrigation system, and a dual check (ASSE 1024) on non-treated residential irrigation. The plan presents that list as the minimums for system type and local risk assessment.
Section 5.5 says relief-valve drain piping on a reduced pressure assembly keeps an air gap of two times the relief-valve diameter, or 1 inch, whichever is greater. The relief valve is never submerged. Underground installation of that assembly is discouraged. It is allowed only case by case, and only where a gravity drain to the surface can be installed.
Section 9 says that where a backflow preventer or a dual check is on the service, heated water can no longer expand back into the main. The plan calls that thermal expansion. It names three methods: a bladder-type expansion tank, a special ball cock and relief valve in the water closet, or a remote thermal expansion relief valve. It says to discuss those with a licensed plumber, and that thermal expansion control follows the South Carolina Plumbing Code. Questions go to (864) 848-5500. The 1971 and 1985 sentences in that section, and the matching sections in the other manuals, are on Thermal expansion.
New service and the inspection
Section 3.1 is the sequence for a new connection. The applicant buys the water service and completes a cross-connection questionnaire. Greer CPW reviews it and writes to the applicant with the assembly required, if any. The assembly and its enclosure are installed to the plan. The applicant notifies Greer CPW at least two days before the inspection at (864) 848-5500. If the installation is satisfactory, the meter or service is unlocked and turned on. If it is not, the customer corrects the deficiencies, and a follow-up inspection is completed before the service is turned on. Inspection vs testing is that split on Greenville Water’s manual.
Section 3.2 says an existing service is evaluated for the degree of hazard. A service line is reassessed at least every five years, or when ownership changes, unless it is already protected by an approved reduced pressure assembly (ASSE 1013) or a properly installed air gap. Residential and low-hazard connections, and non-residential connections with a minimal hazard, are reassessed every 15 years along with the meter replacement program. For an assembly the review requires, the customer notifies Greer CPW two days before the inspection at the same phone number.
How the report is filed
The questionnaire in Appendix A says to email or mail it to backflow@greercpw.com, Attention Backflow Coordinator, P.O. Box 216, Greer, SC 29652. The customer-care manual prints that post office box as the correspondence address.
The test report in the same appendix is the Backflow Device Test Report Form. The assembly line includes RP, DCVA, DDCVA, AG, and other, plus size, manufacturer, model, serial number, location, and the hazard. The certification line says the test must be performed by a general, limited, or inspector tester certified by the South Carolina Department of Health and Environmental Control, and that the tester sends the original passing or failing report to the CPW Cross Connection Control Department. Section 2.3 of the same plan names the South Carolina Department of Environmental Services as the agency that certifies testers. The form in the PDF still prints the older department name. How to read your notice walks through the forms Greenville Water, Spartanburg Water, and Anderson publish. Greer’s form is the one in this PDF.
Neither the plan nor the customer-care policy describes an online filing portal.
Finding a tester
Greenville County testers are General Testers from the SCDES report dated July 9, 2026. That section of the report includes rows whose city is printed as Greer. Spartanburg County testers are the Spartanburg section of the same report. Confirm the card is still current before you hire. A row on this site is not an appointment.
The cost guide is a third-party range for a test. It is not a Greer CPW fee. The tester’s fee, the administration fee, the residential irrigation charge, and the reconnection fees are named in the documents above and are not printed there as dollar amounts.
Greenville County testers Greer CPW cross-connection plan
Sources checked October 14, 2026: Greer CPW’s forms page, the Cross-Connection Control Plan PDF (cover dated Amended April 2025), and the Customer Care Policy Manual PDF linked from that page (revised policy effective July 14, 2026).