Dental office backflow requirements in Upstate SC

The state cross-connection section does not name a dental office. Greer CPW lists dental clinics as a common high hazard. Anderson’s table uses dentist as an example on a low-hazard line. The letter on the account is the device.

Sources checked November 15, 2026.

If this page and the letter on the account disagree, follow the letter. What is backflow testing is the state test. Double check versus reduced pressure is the hazard split in the regulation and in the Greenville Water, Spartanburg Water, and Anderson manuals. A restaurant is a different line on the manuals that name one. Those lines are on Restaurant backflow. A dental office on another system uses that utility’s notice.

The state rule does not name a dental office

R.61-58.7(F) sorts a cross connection by hazard. Section (2) calls a low hazard a connection to another water source that is not hazardous to health and is not cross-connected inside its own system with a potentially dangerous substance. The minimum it names there is an approved double check valve assembly or a pressure vacuum breaker, except for the residential lawn policy in section (3). Section (4) calls a high hazard a connection to a service or other water system that has or may have any material dangerous to health. The protection it names is an air gap or an approved reduced pressure principle assembly.

A text reading of section (F) on November 15, 2026 did not contain the words dental, dentist, clinic, or cuspidor. The section does not print a dental-office rule or a day count that applies only to a clinic. The SCDES program page describes the cross-connection program and the tester course. The retrieved text of that page did not contain those four words.

The same regulation PDF uses “dental” outside section (F). R.61-58.6 and R.61-58.12 use it in the fluoride public-notice language, including dental fluorosis. R.61-58.7, in the finished-water fluoride paragraph and not in section (F), says a public water system which fluoridates must notify its service population and all local dental and public health practices before it stops fluoridating. R.61-58.11, in the rules for delivering lead public-education materials, names public and private hospitals and medical clinics, and family planning clinics, among the organizations that receive those materials. None of those sentences names a backflow assembly for a dental office.

Where the words appear

What each file checked on November 15, 2026 says about a dental office or a clinic. The notice for the account controls if a cell and the letter disagree.
Source Dental or clinic line Assembly that line names
R.61-58.7(F) Does not use dental, dentist, clinic, or cuspidor. By hazard, in sections (2) and (4). No dental row.
Greer CPW, plan amended April 2025, section 5.2 Dental clinics are on the common high-hazard list. The list says “include but not limited to.” A reduced pressure principle assembly, ASSE 1013, for the high-hazard category, subject to the on-site adjustment in that section.
Anderson Electric City, September 2008 policy, Table 1 One low-hazard line: medical facilities, with the policy’s examples of a doctor’s office, dentist, veterinarian, and chiropractor. The coordinator chooses. A low hazard may use a double check valve assembly or one of the high-hazard devices.
City of Pickens public-works page Dentists are on the list of common places that require a device, next to doctors, hospitals and health clinics, veterinarians, and chiropractors. The list does not name an assembly and does not mark high or low.
Seneca Light & Water, manual revised October 2021 The reduced-pressure bullet names medical and veterinary offices and clinics. It does not print dental, dentist, or cuspidor. The public page does not use those words. That bullet says a reduced pressure assembly is required on the uses it names. The supervisor still names the device.
Powdersville Water, September 2024 policy, section 7 The selection guide has a row labeled Clinics. It does not print dental or dentist. That row’s minimum is a reduced-pressure principle assembly. The section says the health hazard governs the final choice.
City of Westminster, September 12, 2024 policy, section 7 The selection guide has a row labeled Clinics. It does not print dental or dentist. That row’s minimum is a reduced-pressure principal assembly. The section says the health hazard governs the final choice.

A restaurant and a car wash sit on other rows. Greer CPW’s section 5.2 lists restaurants on the common low-hazard list and car washes on the common high-hazard list, in lines other than dental clinics. Anderson’s Table 1 lists restaurants, and car washes, on low-hazard lines other than the medical-facilities line. How the files that name a car wash classify it is on Car wash backflow. High-hazard commercial is the shop page already on this site.

Greer CPW

Section 5.2 of the cross-connection control plan amended April 2025 says a reduced pressure principle assembly (ASSE 1013) is used for a high hazard, and a double check valve assembly (ASSE 1015) is used for a low hazard. Common high-hazard facilities “include but not limited to” a list that includes hospitals, dental clinics, and mortuaries and funeral homes. The list continues with other facility types printed in that section. A dental clinic is on the high-hazard list. It is not on the common low-hazard list, which begins with restaurants, office buildings, and banks.

The same section says the containment requirements for the three hazard categories may be adjusted based on the internal plumbing found at the on-site inspection. The high-hazard mark is the list. It is not a sentence that the inspection cannot change the assembly. Greer CPW is the rest of that plan, including the ten-day report on a new assembly and the same-day report after a failure. Greenville County testers are General Testers from the July 9, 2026 SCDES list. That section of the report includes rows whose city is printed as Greer.

Appendix D is a partial list of typical facility types that require service-line protection. It says other facilities not on the list may still be required to install that protection, at the authority’s discretion. Item 1 is “Hospitals and Medical Facilities.” Item 2 is “Dental Clinics.” The appendix does not mark either item high or low. The dental-clinic classification is section 5.2, not Appendix D.

The questionnaire in Appendix A is headed “CCC QUESTIONAIRE.” The form prints that spelling. Under Mechanical Equipment it has a checkbox, “Dental Cuspidors,” and a separate checkbox, “Medical Treatment: Dialysis, Surgery, Therapy.” Those boxes are equipment the applicant marks. They are not the section 5.2 list. The test report in the same appendix has a blank, “Define Hazard,” and the examples in parentheses include medical facility. They do not print dental, dentist, or dental clinic. That blank is a place to write the hazard for the assembly being tested.

Anderson’s table

Table 1 of the September 2008 Cross Connection Control Policy is a list of typical service connections and the hazard level the policy associates with each use. The policy says the list is not complete, that it is a guide for Electric City personnel, and that every service is evaluated on its own. A footnote says the hazard tables are based on an American Water Works Association standard.

The low-hazard line reads “Medical Facilities (i.e. – doctor’s office, dentist, veterinarian, chiropractor, etc.).” A dentist is one example inside that line. Hospitals are a separate entry, on the high-hazard side of the table. “Laboratories (medical and others)” is also a high-hazard entry. The policy does not put the dentist example on either of those high-hazard lines.

The coordinator evaluates each facility and uses Table 1 as a guide. A high hazard requires an air gap, a reduced pressure principal assembly, or a pressure vacuum breaker that is not used where backpressure is expected. A low hazard may use any of those, or a double check valve assembly. The policy encourages an air gap for both when a physical separation is practical. The table’s low-hazard mark is the guide. It is not a sentence that every dental office in the city receives a double check. Deadlines for the test form are on Anderson, Pickens, and Oconee. Anderson County testers are General Testers from the July 9, 2026 SCDES list.

City of Pickens

The public-works page prints “A List of common places that require a backflow prevention devices,” and dentists are on that list, with doctors, hospitals and health clinics, veterinarians, and chiropractors. The list does not mark any place high or low, and it does not name the assembly. Two other names on that list are already on the high-hazard commercial page and are not repeated here. The same section says routine testing follows R.61-58 and that results go to the public-works post office box printed on the page. It does not print a due date. City of Pickens is the filing address and the two test forms. Pickens County testers are the General Testers in that county.

Seneca Light & Water

The backflow prevention page says the Cross-Connection Control Supervisor will notify the customer which device in the procedure manual best protects the system. A text reading of that page on November 15, 2026 did not contain dental, dentist, clinic, or cuspidor.

The manual revised October 2021 puts medical and veterinary offices and clinics on the reduced pressure assembly bullet, together with other uses named in the same bullet. The bullet says that assembly is required on those uses and that it requires annual testing by a certified tester. The bullet does not print dental, dentist, or cuspidor. The double-check bullet does not print those words either. The selection section says the supervisor names the device for the service. Seneca Light & Water is the installation section and the initial test that manual describes. Oconee County testers are the General Testers in that county on the July 9, 2026 list.

A clinic row that does not say dental

Section 7 of Powdersville Water’s cross-connection policy, revised September 2024, is a guide to selecting an assembly. It says the guide comes from past experience and that the health hazard should govern the final choice. The row labeled Clinics lists a reduced-pressure principle assembly as the minimum type of protection. The row does not print dental or dentist. Laboratories are a separate row, also a reduced-pressure principle assembly. Powdersville Water is the 90-day letter and the rest of that policy.

Section 3.5 of the same file says fees for testing will only be charged by Powdersville Water when the customer has failed to submit a current successful test report after a final notice and discontinuance of water service would impact public health, such as a medical clinic. That sentence is about when the utility charges its own testing fee. It does not name the assembly on a dental office. It does not print dental or dentist. The dollar amounts in Appendix A are on the Powdersville page. They are not a price for a tester the customer hires.

Section 7 of the City of Westminster’s Cross-Connection Control Policy, revised September 12, 2024, in the November 12, 2024 council packet, uses the same kind of guide. The row labeled Clinics lists a reduced-pressure principal assembly. The section says the health hazard should govern the final choice. The row does not print dental or dentist. The standard operating procedures in that packet, revised 08/09/2024, say special consideration should be given to hospitals and dialysis clinics, among other customers, during a water shutdown for a leak repair. That sentence is the shutdown. It is not section 7, and it does not name a dental office. City of Westminster is the 90-day letter and the rest of the policy.

Pages that name a hospital or a medical facility, and not a dentist

These files, read on November 15, 2026, do not print dental, dentist, or cuspidor. Silence in the file is not a finding that the account has no assembly. Use the notice.

  • City of Clinton’s water distribution page lists medical or industrial facilities among common risks, together with irrigation systems, garden hoses submerged in pools or containers, fire-sprinkler systems, commercial equipment, and boilers. The page says approved devices may require routine testing by a qualified professional. It does not name the assembly in that pair of sentences, and it does not print clinic. Clinton is the 2026 test form.
  • The City of Clemson water page and the backflow flyer name hospitals in an example list that also names fire protection systems, irrigation systems, gasoline refineries and stations, restaurants, and manufacturers. The sentence says the list includes, but is not limited to, those uses. It does not mark any of them high or low, and it does not name a double check or a reduced pressure assembly for that list. The flyer’s three-year sentence is homeowner irrigation. City of Clemson is the water page, both flyers, and the code section already summarized there. Pickens County testers are the General Testers in that county. Clemson’s filing rules are the city page, not the City of Pickens list.
  • Laurens County Water and Sewer Commission’s backflow page prints low-hazard examples of fire protection, trailer parks, churches, restaurants, and commercial irrigation, and high-hazard examples of fire protection with chemical addition, irrigation with chemical addition, and industries with potentially dangerous cross connections. A dental office is not in either sentence. The page says a business may be placed in the low-hazard residential class at the commission’s discretion and can be reclassified on notice. This page does not decide which class a particular dental office is in. The clocks are on Laurens.
  • Spartanburg Water’s manual revised June 4, 2026, section 7(a), names sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries, and plating plants as examples of premises protected by an air gap or a reduced-pressure principle assembly. A dental office is not in that list. Section 7(b) does not name a facility. The commercial and industrial page did not contain dental, dentist, or clinic. Spartanburg Water is the manual’s notice language. Spartanburg County testers are the General Testers in that county.

Files that do not use the words

A text reading on November 15, 2026 did not contain dental, dentist, clinic, or cuspidor in any of these files. Silence in the file is not a finding that the account has no assembly. Use the notice.

What to do with the letter

Hire a General Tester, the classification that may test for the public. County pages on this site copy that classification from the SCDES report printed July 9, 2026. Confirm the current card before you hire. A row on this site is not an appointment.

The letter names the assembly, the date, and where the report goes. How to read your notice is the reading for the forms Greenville Water, Spartanburg Water, and Anderson publish. A failed result is on Failed backflow test. A repair, and the retest after it, is on Backflow preventer repair. Who the Greenville Water, Spartanburg Water, and Anderson manuals count as a business account is on Backflow assembly testing.

The regulation does not set a price for the device or the test. None of the dental and clinic lines above print a test fee for a tester the customer hires. The cost guide is a third-party range for a test a customer hires. It is not a dental-office price and it is not a utility fee. Official links are on Resources.

Assembly testing for businesses Greer CPW

Sources checked November 15, 2026: R.61-58 on des.sc.gov, including section 58.7(F), the fluoride sentences in R.61-58.6, R.61-58.7, and R.61-58.12, and the lead public-education delivery list in R.61-58.11; the SCDES program page; Greenville Water’s backflow page and the manual created November 10, 2025, including section 5-1; Spartanburg Water’s manual revised June 4, 2026, including section 7, and the commercial and industrial page; Anderson Electric City’s September 2008 policy, including Table 1 and the device section that follows it; Greer CPW’s cross-connection control plan amended April 2025, read from the scan, including section 5.2, the adjustment sentence, Appendix A’s questionnaire and test form, and Appendix D items 1 and 2; Seneca Light & Water’s backflow page and the manual revised October 2021, including the double-check and reduced-pressure bullets; Laurens County Water and Sewer Commission’s backflow page; the City of Clinton water distribution page; the City of Pickens public-works page; the City of Clemson water page and the backflow flyer; Easley Combined Utilities’ water page and the specifications with a March 2025 cover; Powdersville Water’s September 2024 cross-connection policy, including sections 3.5 and 7; Blue Ridge Rural Water’s company policies PDF, section 14; Gaffney Board of Public Works’ water construction specifications; and the City of Westminster November 12, 2024 council packet, including the Cross-Connection Control Policy revised September 12, 2024, section 7, and the standard operating procedures revised 08/09/2024.