Double check valve versus reduced pressure
Both are testable backflow assemblies, with shutoff valves and test cocks. The hazard on the account decides which one the utility requires. The letter names the assembly.
Sources checked October 11, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is the device, including the air gap and the residential dual check. RPZ testing is the reduced pressure assembly in more detail. What is backflow testing is the annual-test rule for every testable assembly. This page is the difference between the two assemblies on the three Upstate utilities that publish a manual.
The names on the brass
Customers say double check, DC, or DCVA for one device, and RP, RPZ, or reduced pressure zone for the other. R.61-58.7(F) uses double check valve assembly and reduced pressure principle assembly. Greenville Water’s Cross Connection Control Manual (PDF created November 10, 2025) and Spartanburg Water’s manual revised June 4, 2026 (PDF created June 5, 2026) shorten those to DCVA and RP. None of the state or utility documents read for this page use the letters RPZ. Match the tag on the assembly to the letter from the utility.
A residential dual check is a third device. Both manuals define it as two spring-assisted check valves with no shutoff valves and no test cocks, used on selectively approved low-hazard connections. It is a different part from a double check valve assembly, and it is a different visit from the test this page describes. Lawn schedules for that device are on Irrigation backflow testing.
A double detector check is a fire-line assembly: a main-line double check with a small bypass that includes another double check and a meter. Greenville Water and Spartanburg Water both define it that way. Fire-line backflow covers detector assemblies. Use the name printed on the notice.
What each assembly contains
Greenville Water’s definitions, and Spartanburg Water’s section 4, describe the two assemblies in the same words:
- A reduced pressure principle assembly is two independently acting, spring-assisted check valves with a hydraulically operating differential relief valve between the checks and beneath the first check. It has resilient-seated test cocks and resilient-seated or ball shutoff valves at each end. It stays accessible for in-line testing, in a place that is never subject to flooding. Both manuals say it is approved for high-hazard cross connections.
- A double check valve assembly is two independently operating, spring-assisted check valves, with resilient-seated test cocks and resilient-seated or ball shutoff valves at each end. It stays accessible for in-line testing and maintenance. Both manuals say it is approved for low-hazard cross connections.
The relief valve is the part the double check does not have. The reduced-pressure rules below are about discharge, a drain, and flooding. The double-check rules are about the two checks holding.
Greenville Water’s definition says each assembly needs approval from SCDHEC and Greenville Water. Spartanburg Water’s definition says SCDES and Spartanburg Water. Tester cards are now issued by SCDES, as the program page describes. How those cards differ is on General vs Limited.
Anderson’s September 2008 policy defines a double check valve assembly as two internally loaded check valves, spring loaded or internally weighted, between two tightly closing resilient-seated shutoff valves, with resilient-seated test cocks. That definition says the assembly is used to protect against a non-health hazard, which the policy calls a pollutant. The policy still says “SC DHEC.”
SCDES’s sample test form labels a double check valve assembly as DC, ASSE #1015, and a reduced pressure backflow preventer as RP, ASSE #1013. The form says many jurisdictions require their own form.
The January 1, 2026 approved-assembly list catalogs them in separate sections, double check valve assemblies and reduced pressure principle assemblies. Assemblies used in South Carolina have to be on that list. Note 3 on that list applies to a reduced pressure principle assembly: the relief port must never be submerged or subject to a toxic environment, which prohibits a pit that cannot drain by gravity to the ground surface, and a vertical orientation is not acceptable unless the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research has approved it. Note 9 applies to a reduced pressure principle assembly, a pressure vacuum breaker, or a double check valve assembly: resilient-seated ball valves or resilient-wedge gate valves. Butterfly valves on that note are acceptable when the same USC foundation has approved them.
How the state rule assigns them
| Source | High hazard | Low hazard |
|---|---|---|
| R.61-58.7(F) | Air gap, or an approved reduced pressure principle assembly. Section (4)(b) keeps that assembly out of a location that can flood. | Approved double check valve assembly or pressure vacuum breaker, except the residential dual-check policy in section (3). |
| Greenville Water, section 5-1 | Reduced pressure principle assembly or an air gap. | Double check valve assembly or dual check. |
| Spartanburg Water, section 9.1 | Reduced pressure principle assembly, a pressure vacuum breaker for back-siphonage only, or an air gap. | Double check valve assembly or double detector valve assembly. |
| Anderson Electric City, 2008 policy | Air gap, reduced pressure principal assembly, or a pressure vacuum breaker where backpressure is not expected. | Any of those devices, or a double check valve assembly. |
Section (2) calls a low hazard a connection between an approved public water system and another water source that is not hazardous to health, that does not meet the standards of the approved system, and that is not cross-connected inside its own system with a potentially dangerous substance.
Section (4)(a) calls a high hazard a connection to a service or other water system that has or may have any material dangerous to health, handled under pressure or subject to negative pressure.
Section (4)(b) says reduced pressure assemblies are not installed where flooding is possible. That includes a pit or vault without a gravity drain to the ground surface that can pass more water than the relief valve discharges.
Two cases move a connection into section (4) even when the everyday use looks ordinary:
- Section (3)(b): residential lawn irrigation that adds chemicals, or that is also connected to a water source which is not an approved public water system.
- Section (5): fire-line sprinkler systems in the high-hazard category. The rule’s examples include antifreeze systems, foam systems, and systems charged from or tied into a pond, lake, stream, or any source other than the approved public supply. Other fire-line sprinkler systems are protected by an approved double check valve assembly.
Section (9) is the pressure vacuum breaker, the other assembly the low-hazard sentence allows. Where it is used, it is installed at least 12 inches above the highest downstream piping and is not subject to backpressure. Spartanburg Water’s section 9.1 places that vacuum breaker on the high-hazard side, and only for back-siphonage. Where that sentence and section (4) do not read the same way, use the notice Spartanburg Water sent for the account. The height sentences, and the order on the 2025 pressure-vacuum-breaker sheets, are on Pressure vacuum breaker.
Greenville Water’s definitions describe a high hazard as an existing or potential threat of a physical or toxic nature that would be a danger to public health, and a low hazard as one that does not constitute a threat to health but may affect the physical properties of the water, cause a nuisance, or be aesthetically objectionable.
Spartanburg Water’s commercial and industrial page says a residential customer with a 3/4-inch to 1-inch service will have a residential dual check valve installed by Spartanburg Water, and that commercial, industrial, and multi-dwelling customers get an approved testable assembly based on the degree of hazard the cross-connection technicians identify. That page does not name which hazard receives a double check and which receives a reduced pressure assembly. Section 9.1 does. On October 11, 2026 the older path /ccc-and-backflow redirected to that commercial and industrial page.
Anderson’s policy encourages an air gap for both high and low hazards when a physical separation is practical. The minimum distance that policy prints, and the one-inch floor in the Greenville Water and Spartanburg Water definitions, are on Air gap separation. The policy says the coordinator evaluates each facility and uses Table 1 as a guide.
Greer CPW’s hazard categories, and the assembly the April 2025 plan names for each, are on Greer CPW. What Easley Combined Utilities’ water page says about keeping a double-check policy is on Easley Combined Utilities. This page does not state a device rule for Seneca, or for any utility that has not published the document cited here. Use the notice from that utility.
Anderson’s facility table
Table 1 in the September 2008 policy lists typical service connections and the hazard level the policy associates with each use. The policy says the list is not complete, that it is a guide for Electric City personnel, and that every service is evaluated on its own. A footnote says the hazard tables are based on an American Water Works Association standard. Greenville Water’s manual and Spartanburg Water’s manual, in the sections read on October 11, 2026, do not print a facility list of this kind.
Examples Table 1 marks high hazard include hospitals, chemical plants, boilers, cooling towers and chillers, landscape irrigation with injection of any type, and fire protection systems with injection. Examples it marks low hazard include restaurants, commercial food preparation facilities, and bars; car washes; medical facilities, with the policy’s examples of a doctor’s office, dentist, veterinarian, and chiropractor; lawn irrigation without injection; and fire protection systems without injection. Shops the same table marks high hazard, already discussed on this site, stay on the high-hazard commercial page. How that restaurant line differs from the other utilities that name one is on Restaurant backflow. The dentist example on the medical-facilities line is on Dental office backflow. The car-wash line, read against the other utilities that name one, is on Car wash backflow. A row on the table is the guide. The notice names the assembly.
Where the assembly can sit
Greenville Water section 5-4 is the checklist for both a DCVA and an RP: on Greenville Water’s approved list, resilient wedge gate or ball valves at each end, four test cocks, no bypass unless an equal assembly is in the bypass, the manufacturer’s instructions, and an enclosure or building on the customer’s property, kept accessible for testing. Section 5-5 is only for the RP. If pressure swings make the relief valve discharge often enough to be a nuisance, the customer should add a check valve ahead of the assembly. Relief-valve drain piping keeps an air gap of two times the relief-valve diameter, or 1 inch, whichever is greater, and the piping is sized to carry more than the relief valve discharges. The relief valve is never submerged. Underground installation is discouraged and is allowed only in unusual cases with a gravity drain to the surface that is large enough.
Spartanburg Water section 9.3 is the shared checklist, including the same bypass rule, and it says no black iron or black steel piping is installed on the supply side of any assembly. Section 9.4 repeats the relief-valve air gap of two times the diameter or 1 inch, whichever is greater, says the relief valve will never be submerged, and allows an underground reduced-pressure installation only in exceptional cases, one site at a time, where a gravity drain can be installed.
Anderson’s device-installation section allows a below-ground double check in a box sized for the conditions, with at least 2 inches of pea gravel under the device, test cocks pointed up, and at least 6 inches between the floor of the box and the device. A larger pit needs a gravity floor drain. A sump pump is not a substitute. A double check or reduced pressure assembly above ground or inside a building sits no lower than 12 inches and no higher than 36 inches above grade or the floor, and it stays reachable for testing without a ladder.
The same section’s reduced-pressure rules are separate:
- RP assemblies are above ground unless Electric City Utilities specifies otherwise.
- The relief opening points toward the ground. The policy allows no vertical or angled installation.
- An RP inside a building or in a pit needs a floor drain by gravity, sized at least twice the relief-valve diameter. A sump pump is not a substitute.
- The assembly is not placed in a flood plain or where the relief valve can be submerged.
- The relief valve is not piped solid to a drain. The air gap is at least twice the opening size and never less than 2 inches.
The state list’s vertical-orientation exception is a USC approval. Anderson’s policy, in the sentence above, allows no vertical or angled RP installation. On an Anderson account, follow the policy and the notice. Who installs the assembly, and why the certified test is a later step, is on Backflow preventer installation.
What the test reports
Section (7) covers a double check valve assembly and a reduced pressure principle assembly the same way. A certified tester tests the assembly after installation and before the customer uses it. Except for the low-hazard residential irrigation schedule in section (3), each assembly is tested at least once a year. After any repair, the assembly is tested again immediately. The tester sends the written report to the water system.
Renewing a tester card, in section (8)(a), includes a wet-lab test of a reduced pressure principle assembly, a double check valve assembly, and a pressure vacuum breaker on the tester’s own differential gauge. The program page describes the same three assemblies in the recertification wet lab.
Greenville Water’s manual and Spartanburg Water’s manual, in the sections read on October 11, 2026, do not print a passing psi for either assembly. The pass or fail is the result the certified tester enters on the form those utilities accept. Notice timing is on the Greenville Water and Spartanburg Water pages.
Anderson’s Table 2 is that utility’s minimum. It is not a statewide number from R.61-58.7(F). For a double check valve assembly, both check valves must close tight and hold at least 1.0 psi. For a reduced pressure assembly, Table 2 lists check number 1 at 5.0 psi minimum and 11.0 psi maximum, check number 2 at 1.0 psi minimum and 4.0 psi maximum, and the relief valve at 2.0 psi minimum and 5.0 psi maximum. The policy recognizes only the differential-pressure method for an RP, using a three-hose or five-hose gauge. If an RP is in a pit, the tester inspects the pit drain at the annual test. Those reduced-pressure bands are also on RPZ testing. The 10-day test-form rule is on the Anderson, Pickens, and Oconee page.
The method for a double check is where the documents diverge, and this page does not pick a winner:
- Anderson’s 2008 policy accepts a direction-of-flow test with a vertical sight tube, or a differential-pressure test. Its definition of the direction-of-flow test says the sight tube creates a pressure equal to 1.0 psi, or the tester uses a differential gauge with only the high hose. The policy says Electric City Utilities and SC DHEC no longer recognize the transfer-of-pressure, single-gauge, or ten-pound back-pressure methods for a double check.
- A Bureau of Water letter dated June 1, 2018, linked from the SCDES program page as “Vertical Tube Test Procedure No Longer Allowed,” says the vertical tube test procedure for a double check valve assembly is not allowed as of December 31, 2018. From January 1, 2019 the letter names two options, both with a differential gauge: a differential pressure test, which it describes as 2 hoses, and a direction of flow test, which it describes as 1 hose. The letter says water systems want a numerical value for the check springs, rather than only knowing both checks hold the minimum of 1.0 psi.
- SCDES’s 2025 procedure sheets, the three-valve PDF and the five-valve PDF, are also linked from that program page. They are the tester’s steps. This page does not reprint them. The three-valve pressure-differential sheet for a double check says the gauge reading for check tightness should be 1 PSID or above. The five-valve pressure-differential sheet for a double check says the same. The reduced-pressure sheets in those files label check 1 at 5 PSID or above and check 2 at 1 PSID or above. The direction-of-flow sheets in those same files still use the words “vertical tube” in the steps. Anderson’s Table 2 maximums are not printed in the state lines just cited.
The tester uses the procedure SCDES and the utility accept for that account. County lists of General Testers copied from the July 9, 2026 SCDES report start at Greenville County. Confirm the current card before you hire. A row on this site is not an appointment.
The regulation does not set a price for either test. The cost guide keeps a third-party range separate from any utility fee. Official links are on Resources.
RPZ testing Greenville County testers
Sources checked October 11, 2026: R.61-58 on des.sc.gov, the SCDES program page, the June 1, 2018 vertical-tube letter linked from that page, the 2025 three-valve and five-valve test-procedure PDFs linked from that page, the SCDES sample test form, the January 1, 2026 approved-assembly list, Greenville Water’s November 10, 2025 manual, Spartanburg Water’s commercial and industrial page and June 4, 2026 manual, and Anderson Electric City’s September 2008 policy.