Residential backflow testing in Upstate SC

A house is on the annual certified test when the account has a testable assembly. A residential dual check is a different device. The letter from the utility names which one is on the service.

Sources checked October 22, 2026.

If this page and the letter on your account disagree, follow the letter and the manual it cites. What is backflow testing is the state rule for a testable assembly. What is a backflow preventer is how to tell the parts apart. Lawn and in-ground irrigation schedules stay on Irrigation backflow testing. A commercial or industrial account is on Backflow assembly testing for businesses. This page is the house: a single-family service, a multi-dwelling, and a private pool. A private well or another supply on the same property is on Auxiliary water and private wells.

Two devices a house can have

R.61-58.7(F) section (7) names the assemblies a certified tester tests when they protect the public system from a customer’s service: a double check valve assembly, a pressure vacuum breaker, and a reduced pressure principle assembly. The test is after installation and before the customer uses the assembly. Except for the low-hazard residential lawn schedule in section (3), each of those assemblies is tested at least once a year. After any repair, the assembly is tested again immediately. The public water system receives a written report, submitted by the certified tester who made the test.

A residential dual check is the other device. Greenville Water’s manual and Spartanburg Water’s manual revised June 4, 2026 both define it as two independently operating spring-assisted check valves, with no shutoff valves and no test cocks. Anderson’s September 2008 policy says the device is not typically equipped with a shutoff valve or test cocks, and that it can sit with the meter yoke or apart from it. Section (7) does not name that device. Where a manual sets a change-out for a dual check on a lawn system, that schedule is on the irrigation page.

A short field check, with the letter still in control if a marking and the letter disagree:

  • Shutoff valves and test cocks mean one of the testable assemblies in section (7). A relief valve between the checks is the reduced pressure principle assembly on RPZ testing. Two checks and no relief valve are the double check on Double check versus reduced pressure.
  • Two checks and no test cocks match the residential dual check above.

What the state rule asks of a house

Section (1) says every public water system initiates and maintains a cross-connection control program, and that no person may install or keep a cross connection between a public water system and any other non-public water system, a sewer, or a line from a container of liquids or other substances, unless an approved backflow prevention device or assembly sits between the public system and the source of contamination.

Section (2) sets the minimum on a low hazard at an approved double check valve assembly or a pressure vacuum breaker, except as section (3) provides for residential lawn irrigation. Section (3) is only that lawn case. A house service that is not lawn irrigation follows the hazard the utility assigns, and a testable assembly on that service follows section (7).

The SCDES Cross Connection Control page says testing is done by a state-certified tester, and that assemblies used in South Carolina have to be on SCDES’s list of approved backflow prevention assemblies. The filename on the state site spells “equipment” the way the URL shows.

In R.61-58, a certified tester is a person holding an up-to-date backflow prevention assembly tester card issued by the Department. The General Tester is the classification that provides testing to the general public. A Limited Tester tests only assemblies the employer owns and does not provide testing services to the general public. General vs Limited is how those cards differ.

Greenville Water

Greenville Water’s backflow page says every connection can let non-potable water into the public system, whether it is a residential home or an industrial business. It says customers whose water presents a backflow hazard must install a backflow prevention device or assembly and have it tested annually under SCDES and Greenville Water standards. The same page says Greenville Water does not install or test backflow preventers. The program on that page includes determining whether a customer must install a device, and which type.

The manual’s introduction says the policy was adopted September 6, 2022. It says most commercial, industrial, irrigation (as noted), and private fire-protection customers install, maintain, and test the assembly on the service. Section 5-3 is the note, and it applies to newly installed residential irrigation systems only. That lawn case, including the dual check on the meter setter, is on Irrigation backflow testing. The introduction does not put an ordinary house on that irrigation sentence.

The responsibility section says Greenville Water evaluates connections, and the customer provides and maintains backflow prevention assemblies commensurate with the degree of hazard. Section 2-4 says the customer installs, tests, and maintains the assemblies Greenville Water requires, and is responsible for the costs. If a letter names a testable assembly, the customer hires a certified tester and the tester files the report. Notice timing and the non-compliance fee are on Greenville Water. If no letter has named an assembly, questions in the manual go to the Cross Connection Control Department at (864) 241-6100. The main number on the public page is 864-241-6000.

Spartanburg Water

On October 22, 2026 the older path /ccc-and-backflow redirected to Spartanburg Water’s commercial and industrial page. The cross-connection section on that page says a residential customer with a 3/4-inch to 1-inch service will have a residential dual check valve installed by Spartanburg Water. Commercial, industrial, and multi-dwelling customers get an approved testable assembly based on the degree of hazard the cross-connection technicians identify. The same section says certain types of commercial and industrial backflow assemblies must be tested annually by an SCDES-certified tester. Questions go to Matthew Jamison, Field Operations Manager, at (864) 598-7213 or ccc@spartanburgwater.org.

The manual (revised June 4, 2026; PDF created June 5, 2026) repeats those four customer lines in section 6. The definitions section adds a shorter pair: a single-family dwelling requires a dual check device, and a commercial, industrial, or multi-family site is evaluated for the degree of hazard and then receives the appropriate testable assembly. Replacement of residential dual checks coincides with the meter change-out schedule used by Field Technical Services.

Section 6 prints the dual-check line for a residential customer with a 3/4-inch to 1-inch service. It does not print a second size. The customer definition still says a single-family dwelling requires a dual check. If the meter on the account is outside that range, use the notice, or ask the contact above.

Section 10.2 says all existing approved backflow assemblies are tested annually, excluding low-hazard residential lawn irrigation systems. That exclusion is the lawn case on the irrigation page. A multi-dwelling gets a testable assembly under section 6, and section 10.2 is the annual test for approved assemblies. The notice tiers and the administrative fee are on Spartanburg Water. A single-family dual check has no test cocks, and section (7) of the state rule does not name that device. If a letter names a testable assembly on a house, follow the letter.

Anderson Electric City

The September 2008 policy says residential customers are still required by regulation to be protected. It names swimming pools, pesticide aspirator applicators, garden ponds, and fountains as reasons. For a residential service that does not have an in-ground irrigation system, backflow protection is supplied by Electric City at or near the meter. The policy says Electric City will install and maintain these devices at no additional expense to the customer.

All standard residential domestic services have a residential dual check, approved under ASSE 1024. Electric City provides it on a meter yoke or as a stand-alone device on new or renewed services. As older unprotected residential services are repaired or renewed, an ASSE 1024 device is installed at that time. The policy says that exception is allowed by SC DHEC. Current tester cards are SCDES cards, as the program page describes. The policy still says “SC DHEC.”

A privately owned swimming pool on a single-family residence is protected by the same ASSE 1024 residential dual check, on a meter yoke or as a stand-alone device, on new or renewed services. The policy encourages residents to install a double check valve assembly and says that assembly is not required at this time. It also encourages residents not to leave a hose that is connected to a hose bib submerged in the pool, and it calls that an avoidable cross connection.

In-ground irrigation, including a system fed only from the domestic service, is a different case. The device and the test interval are on Irrigation backflow testing. Above-ground sprinklers on the domestic meter are on that page as well. Questions in the policy go to the Cross Connection Control Coordinator at (864) 231-5230. Deadlines already summarized for Anderson customers are on Anderson, Pickens, and Oconee.

A duplex or multi-plex with its own meter for each unit is inside the residential definition. A complex on one meter is the multi-occupancy definition, and the policy says that arrangement will be treated as a master-metered system. The appendix calls the same account a bulk water system. Table 1 lists that line, and multi-family housing complexes, as separate low-hazard lines. The coordinator still chooses the device. That reading is on Master-metered and bulk water. Spartanburg Water’s multi-dwelling sentence stays in the section above.

If the water system is not one of these three

Greer CPW’s residential sentences are on Greer CPW. Seneca Light & Water’s are on Seneca Light & Water. Easley Combined Utilities’ water page, including the residential lawn-sprinkler sentences, is on Easley Combined Utilities. Inman-Campobello’s tap applications say the district installs a dual check for a 1-inch residential tap, and that any other meter of 1 inch or larger requires a testable device. Those sentences are on Inman-Campobello. This page does not state a house rule for a utility that has not published the document cited here. Section (7) still applies to a testable assembly. The device, the date, and the place the report goes are on that utility’s notice.

Heated water after the device is in

Heated water can stop moving back into the utility main once a checking device is on the service. Greenville Water’s section 8 names a backflow preventer. Spartanburg Water’s section 13 and Greer CPW’s section 9 also name a dual check. Powdersville Water’s section 11 names a backflow assembly, a pressure reducing valve, or any other checking device. Those sections are on Thermal expansion.

When the letter says the assembly has to be tested

Read the date, the service address, and the device on the letter. How to read your notice walks through the public forms Greenville Water, Spartanburg Water, and Anderson publish. The blank form is the report. The letter is the notice.

Hire a General Tester. County pages copy General Testers from the SCDES report printed July 9, 2026. Start with Greenville County, Spartanburg County, or Anderson County. Confirm the tester’s current SCDES card before you hire. A row on this site is not an appointment. Who installs a new assembly, and why that work is a separate step from the test, is on Backflow preventer installation.

The tester sends the written report to the water system. After a repair of any kind, section (7) says the assembly is tested again immediately. What the three manuals require when a result does not pass is on Failed backflow test. Who arranges a repair is on Backflow preventer repair.

This site does not publish a price for a residential test. The cost guide keeps a third-party range, labeled as that range, separate from any utility fee. Official links are on Resources.

Find a Greenville County tester Read the notice

Sources checked October 22, 2026: R.61-58 on des.sc.gov, the SCDES program page, Greenville Water’s backflow page and November 10, 2025 manual, Spartanburg Water’s commercial and industrial page and the manual revised June 4, 2026, and Anderson Electric City’s September 2008 policy. The Inman-Campobello sentence was checked November 3, 2026 against the cross-connection questionnaire in the South Carolina and North Carolina tap applications.