Seneca Light & Water backflow testing

Seneca Light & Water publishes a backflow page and an October 2021 procedure manual. The notice gives 45 days to have the assembly tested. The manual’s late-test step is a second clock.

Sources checked October 16, 2026.

The public page is Backflow Prevention on the City of Seneca site. It links the Backflow Manual PDF, revised October 2021. The page and the manual both say the program was established and implemented in 1985. Both say the requirements can change, and that the owner is responsible for the current revision. If this summary and the letter on the account disagree, follow the letter and the current manual.

The office block on that page lists Seneca Light & Water at 251 E North 2nd St., Seneca, SC 29678, open Monday through Friday, 8:00 a.m. to 5:00 p.m. It lists the phone 864-885-2723, the fax 864-888-0865, customerservice@seneca.sc.us, and the mailing address P.O. Box 4773, Seneca, SC 29679. The same block names Josh Riches as Director of Utilities and Chris Morgan as Water/Sewer Superintendent. The October 2021 manual ends with an administration page that names a director, a superintendent, and a cross-connection supervisor and prints office and cell numbers. The backflow page checked for this edition does not repeat that block. Use the number on the current page, or the number on your letter.

What the manual requires

The manual says any actual or potential connection between the public supply and a source of contamination or pollution is a hazard, and that Seneca Light & Water will require a testable backflow device. The Cross-Connection Control Supervisor notifies the customer which device in the manual applies. The introduction says that missing those requirements within a suitable time frame results in disconnection until the device is installed and tested. That sentence does not print a number of days. The numbered clocks are in the testing section below.

Installations must meet requirements set by the South Carolina Department of Health and Environmental Control, the Southern Building Code Congress International Standard Plumbing Code (current version), and Seneca Light & Water. The page and the manual still print the older department name. Tester cards are now issued by the South Carolina Department of Environmental Services. What is backflow testing is the state rule the manual cites as R.61-58.7(F).

The city page says approved assemblies are listed by that department’s approval, and it asks customers to confirm a particular assembly with the Cross-Connection Control Department before buying it. The PDF linked there is a state notice dated January 1, 2021. The newer file on the state site is the January 2026 list linked from Resources. Confirm the assembly with Seneca Light & Water before purchase.

The 45-day notice

Section III.A.1 covers an existing service that already has a backflow preventer. When an account is established, a work order goes to the Cross Connection Supervisor, who sets the meter and makes the initial test. Assemblies are tested annually after that, at the owner’s expense. The supervisor sends a notice reminding the customer to have the assemblies tested. The notice gives the customer 45 days to have the assembly tested. The manual says those tests are performed by a DHEC-certified tester adhering to the Seneca Light & Water Code of Ethics. The manual does not attach that code. It says Seneca Light & Water may require testing more often, depending on the degree of hazard.

The note under that paragraph is a second clock. If the customer does not have the device tested and the test report returned within 45 days after the due date, Seneca Light & Water has the device tested by a certified tester at the customer’s cost. The cost of the tester, and administrative fees, are added to the bill. The manual says testers for that step are chosen from the previous year’s results. It does not print a dollar amount for the tester or for the administrative fee.

Greenville Water and Spartanburg Water print their own day counts. Those clocks are not Seneca’s. How to read your notice walks through the forms those utilities publish. The October 2021 manual does not include a blank public test form.

The fee schedule

The Light & Water menu on the city site links a fee schedule PDF. Under Water Tap & User Fees, a row labeled Backflow Prevention Assembly Test has two columns, FY 2026 and FY 2027. Residential is $0.00 in the FY 2026 column and “20% of testing charge” in the FY 2027 column. Commercial is $0.00 and “25% of testing charge.” The schedule does not define “testing charge,” and it does not say whether the row is the tester’s price, an administrative add-on, or another charge. It does not say which fiscal year is in effect. Use the current file and the bill.

The cost guide is a third-party range for a test a customer hires. It is not this fee schedule, and it is not the tester cost the manual adds to a late account.

Who may test, and how the report is filed

Section III.A.2 says assemblies that protect the Seneca Light & Water system are tested only by certified testers whose names appear on Seneca Light & Water’s list of Permitted Backflow Prevention Assembly Testers. The October 2021 manual says that list may be obtained at www.senecalightandwater.com. On October 16, 2026 that host opened the city’s Seneca Light & Water page. The backflow page links Permitted Backflow Testers List. Opened the same day, that address was a PDF titled “Permitted Backflow Testers List,” City of Seneca SC, with name, city, and phone columns. This site does not copy those rows.

Section III.A.3 says the tester enters results through Seneca Light & Water’s online testing portal. The tester is set up to enter tests after completing the mandatory backflow orientation given by the City of Seneca Cross-Connection Control Supervisor. The manual does not print the portal’s address. It says test reports will not be accepted in the office by mail, fax, or email unless the Cross-Connection Control Supervisor gives permission.

A row on the Oconee County tester page is a General Tester from the SCDES report dated July 9, 2026. That list and Seneca Light & Water’s permitted list are different documents. The City of Walhalla is a different water system. Walhalla’s SCDES record lists Seneca City of as a seller. Seneca’s 45-day notice and permitted-tester list do not transfer to a Walhalla account. Walhalla’s ordinance is on City of Walhalla. General vs Limited explains the state card. Confirm the current SCDES card, and confirm the tester is on Seneca’s permitted list, before you hire. A row on this site is not an appointment.

The manual says Seneca Light & Water may remove a tester from the permitted list for falsifying records, unauthorized repairs, failing to demonstrate proper test procedures, lack of knowledge of the program, or failing to follow its rules. A tester whose gauge is out of the tolerance in the gauge manufacturer’s specifications is suspended until the gauge is replaced or calibrated.

After a repair

Section III.A.5 says state rules and Seneca Light & Water require a test after any repair. The certified tester who performs that test enters the results in the online portal within seven days after testing.

Section III.A.6 says that when an assembly malfunctions or fails an annual, periodic, or random test and the whole assembly has to be replaced, the replacement follows the program requirements in effect at that time. Routine repairs of a check valve, relief valve, gate or ball valve, or seat do not require the assembly to be re-piped. If the assembly is moved, or if Seneca Light & Water finds that it no longer matches the hazard and it is scheduled for replacement, the replacement is an approved assembly meeting the current requirements. How Greenville Water, Spartanburg Water, and Anderson describe a failed test is on Failed backflow test. Seneca’s seven-day portal entry is the sentence above.

Section III.A.4 says the department conducts random follow-up tests. The customer is notified in advance. The same paragraph says Seneca Light & Water personnel may perform follow-up testing at any time and for any reason to protect water quality.

If the service has no assembly yet

Section III.B says the Cross-Connection Supervisor surveys the system and sometimes finds an unprotected service. An assembly required on an existing service must be installed within 45 days from the date of written notification. If it is not, Seneca Light & Water has an assembly installed and tested by a certified tester, at the customer’s cost, plus administrative fees. The manual says high hazards may require a more timely installation. It does not print that shorter period.

A plumber, contractor, or installer who changes out a backflow preventer must notify the Cross-Connection Control Department. The device is tested after the change-out. Department personnel then inspect it, record the make, model, size, serial number, and location, and the manual says that inspection is made within two days.

New installations

The installation section says every new installation is inspected and approved by a Seneca Light & Water representative. Upon approval, Seneca Light & Water performs the initial test. An annual test is required after that. Section III.C repeats that the department inspects all new backflow preventer installations and performs the initial test at that time. Annual tests after that are by a DHEC-certified tester adhering to the code of ethics named above.

The assembly goes on the customer’s side of the meter and before the first service connection. It is installed to the manufacturer’s specifications and approved by Seneca Light & Water. It has to be readily accessible for in-line maintenance and testing. The manual recommends protecting an above-ground assembly from freezing, and it says the manufacturer’s identification plate, the test cocks, the air-inlet valve bonnet, and the relief-valve vent opening are not covered with insulation. Heat tape may be used where power is available. No connection is permitted on any of the four test cocks. The shutoff valves are attached to the device, not on an outside wall, unless a variation is granted for piping constraints. Exceptions to the clearance rules have to be authorized by the department before the work. Backflow preventer installation is how Greenville Water, Spartanburg Water, Anderson, and Greer CPW describe a new assembly. Seneca’s initial test is the one in this manual.

Other requirements in the manual: bypass piping is not permitted unless it has an approved assembly of the same class as the main line. Vertical installation is not permitted unless the manufacturer’s specifications allow it, and Seneca Light & Water approves it first. No contractor, plumber, tester, or anyone else may replace an assembly with a straight pipe, or remove an assembly, without permission from the Cross-Connection Control Department.

Which assembly

The selection section describes three assemblies. Each one, the manual says, requires annual testing by a certified tester. The supervisor still names the device for the service.

A pressure vacuum breaker is described as versatile, for high-hazard systems, and used most often on irrigation where the water source is uphill. It cannot be used against backpressure. The manual’s example is lake pumps for irrigation. The installation section says it is installed vertically, at least 12 inches above the highest downstream outlet, irrigation head, or zone. It protects against back siphon only. Booster pumps are not used with it. It may be used for a high or low hazard that is not subject to backpressure. The air-inlet valve bonnet is not covered with insulation. Irrigation backflow testing is the state irrigation split and the other published Upstate manuals. Seneca’s 12-inch height is the sentence in this manual.

A double check valve assembly, the manual says, is required on all irrigation systems, on water meters supplying more than two residential units, on restaurants, on a water supply line of two inches or greater, on swimming pools, on beauty and barber salons, on public or private schools, on retail stores, and on all fire-line sprinkler systems. The same bullet names other facility types. Read that bullet in the manual. The restaurant line, set next to the other utilities that name one, is on Restaurant backflow. The next bullet says every commercial customer applying for water service after January 1, 2009 has a double check valve assembly, unless the Cross-Connection Control Supervisor waives it as unnecessary.

A double check should be at least 12 inches above ground. It may be below ground in a covered box with at least 6 inches of clearance under the assembly and 4 inches on all sides. Double check versus reduced pressure is the state hazard split.

A reduced pressure assembly is described as a high-hazard device. The manual says it is the only type approved there for applying fertilizer or other chemicals to an irrigation system. It says that assembly is required on chemical plants, industries using hazardous chemicals, funeral homes, hospitals, medical and veterinary offices and clinics, car washes, sewage treatment plants, labs, fire-line sprinklers that use antifreeze, irrigation systems injected with pesticides or fertilizers, auto repair garages, and oil-changing garages. The same bullet names one more facility type. Read it in the manual. The dental-office question, for the utilities that print one, is on Dental office backflow. The reduced-pressure bullet does not print dental or dentist. The car-wash name on that bullet, set next to the other utilities that name one, is on Car wash backflow. Auto repair garages and oil-changing garages on that bullet, set next to the other utilities that name a garage, are on Automotive garage and car dealership backflow.

A new or replaced reduced pressure device cannot be installed in a pit below ground. An exception has to be authorized before the work. Working space is 12 inches plus the nominal size of the device, on all sides. The device is protected from freezing. If the facility needs uninterrupted water, the manual says two or more reduced pressure assemblies are necessary so one can be shut down. RPZ testing is that assembly on the other published manuals.

An air gap, in this manual, is a vertical separation between the end of the supply and the flood-level rim of the receiving vessel. The vertical distance is at least twice the diameter of the supply pipe. How that distance compares with the other published manuals is on Air gap separation.

Fire sprinklers

The fire-service section requires an approved assembly on all fire sprinkler systems, wet and dry. An unmetered fire-protection assembly has a detector meter with an approved assembly. High-temperature assemblies are certified by the manufacturer for elevated temperatures. Systems using foam, antifreeze, anti-corrosive additives, or another substance Seneca Light & Water determines is a health hazard use a reduced pressure principle assembly with a metered bypass that also has a reduced pressure principle assembly. The manual labels that arrangement RPDA. Shutoff valves are outside-stem-and-yoke valves, as the manual says the National Fire Protection Association requires.

No lines, gauges, jockey pumps, booster pumps, or Siamese connections are installed before the assembly. The same manual says booster pumps shall not be used with a pressure vacuum breaker. How that sentence sits next to the pressure numbers in other files is on Booster pumps and backpressure. On an unmetered fire main, nothing is connected between Seneca Light & Water’s connection at the water main and the fire-service assembly, except a domestic service line that has its own assembly and tees off before the fire-service assembly. Fire-line backflow is the state rule and the other three manuals.

The same backflow page links an SL&W district backflow locations PDF. This page does not copy that file. Temporary use of a fire hydrant, including the permitting page and the rental-deposit rows, is on Temporary hydrant meters.

Oconee County testers Seneca Light & Water backflow manual

Sources checked October 16, 2026, with the Walhalla cross-reference checked November 7, 2026 against the SCDES record for Walhalla City of, SC3710004: the City of Seneca backflow prevention page; the Backflow Manual PDF linked from that page (revised October 2021); the fee schedule PDF linked as Rates from the Light & Water menu on that page; the approved-assembly PDF linked from that page (notice dated January 1, 2021); and the permitted-tester list linked from that page, which opened as a PDF the same day. www.senecalightandwater.com, named in the manual, opened the city’s Seneca Light & Water page the same day.