Blue Ridge Rural Water backflow testing
Section 14 says testable backflow devices are tested annually at the device owner’s expense. It does not print a due date or a place to send the report.
Sources checked October 31, 2026.
The policies file is linked from Blue Ridge Rural Water’s company bylaws and policies page. The link text on that page is “Blue Rural Water Company Policies.” The file is the Company Policies PDF. Section 14 is Cross Connection Control. It starts after section 13’s adoption line, September 1, 2007. Section 14 does not print an adoption date of its own. The PDF linked on October 31, 2026 carries a modification stamp of July 30, 2026. The file properties title is “2020 Company Policies.”
The developers page links BRRWC’s Standard Specifications. The PDF is headed Specifications, Water Distribution System, for Blue Ridge Rural Water Company, Inc. The pages are dated 9-30-2025. The cross-connection paragraph is on the page marked WDS 9. That file is a construction specification. It is not a customer test letter.
The service area page says the service area is in northern Greenville County, South Carolina, and that the boundaries are not exact. It says to contact the office before relying on the boundary for a particular property. The location and hours page prints the office at 2241 Fews Chapel Rd., Greer, SC 29651, the main number (864) 895-1719, and the same number for water emergencies, available 24/7. Office hours on that page are Monday through Thursday, 7:30 am to 5:00 pm, and Friday, 7:30 am to 12:00 pm.
Section 15 of the policies PDF says the company owns and operates three water systems: Blue Ridge System (PWSID# 2320003), Cliffs Glassy Mountain System (PWSID# 2350023), and Cliffs Valley North System (PWSID# 01-45-165). The service area page does not repeat those three names. This summary does not merge the two statements into one map. Greenville Water deadlines do not transfer to a Blue Ridge Rural Water account. If this summary and the letter on the account disagree, follow the letter and the current PDF.
What section 14 says about the test
Section 14 says Blue Ridge Rural Water maintains a cross connection control program. It says all testable backflow devices are tested annually. It says a tester licensed by the South Carolina Department of Health and Environmental Control will test all testable devices annually, at the device owners expense. It says device owners are notified of testing by mail. It says records are maintained and kept on file.
The section does not say whether the owner hires that tester or the company sends one. It does not print a number of days after the notice, a late fee, a disconnection step, or an address, email, or portal for the finished report. How to read your notice walks through the letters other Upstate utilities publish. Use the letter on the account for the date and for where that letter says to send the report. Questions go to (864) 895-1719.
The policy still names the South Carolina Department of Health and Environmental Control. General vs Limited is the state card. What is backflow testing is the state rule, R.61-58.7(F). Section 14 does not name General, Limited, or Inspector. Greenville County testers are General Testers from the SCDES report dated July 9, 2026. This site does not copy a tester roster from Blue Ridge Rural Water. A row here is not an appointment. Confirm the current card before you hire.
Section 14 does not print a dollar amount for the test. The cost guide is a third-party range for a test a customer hires. It is not a Blue Ridge Rural Water fee.
Hazard and the device
Section 14 says device selection is based on degree of hazard. It prints four categories:
- High hazard: an existing or potential threat to the drinking water supply of a physical or toxic nature that would be a danger to public health.
- Low hazard: a hazard that does not constitute a threat to health, but may cause an actual or potential threat to the physical properties of the water and cause a nuisance or be aesthetically objectionable.
- Low hazard residential lawn irrigation: a lawn irrigation system without chemical addition or an unapproved auxiliary water supply.
- High hazard lawn irrigation: any lawn irrigation system that includes chemical additions, or is connected to another water source, which is not an approved public water system.
The device lines in the same section say an approved Reduced Pressure Principal Assembly (RP device) is used at all high hazard locations. They say an approved Double Check Valve Assembly (DCVA device) or an approved dual check valve is used at all low hazard locations. They say an approved dual check, non-testable, is used at all new residential connections. Double check versus reduced pressure is the state hazard split. RPZ testing is the reduced pressure assembly on the other published manuals. Section 14 spells the assembly “principal.”
Section 14 does not mention an air gap. The specifications do. That difference is in the next section of this page.
The low-hazard irrigation line uses the words “unapproved auxiliary water supply.” It does not add a private-well disconnect sentence. Auxiliary water and private wells is how Spartanburg Water and Anderson word a well. Those sentences are not section 14.
Residential irrigation
Section 14 says all low hazard residential lawn irrigation connections protected by residential dual check valves will be changed at ten-year intervals or when meters are changed out, whichever comes first. That sentence says the dual check is changed. It does not call the change a test, and it does not print a charge for the change.
A double check valve assembly is a testable device under the annual-test sentence above. The ten-year sentence is the one for residential dual checks. Irrigation backflow testing is the state irrigation split and the other published Upstate manuals. The ten-year clocks Greer CPW prints are not this sentence.
The irrigation system policies page says irrigation water is independently metered, and that an irrigation system installed after February 2004 needs a separate meter. That page prints meter and meter-box charges. It does not name a backflow assembly. Those charges are not a price for the annual test in section 14.
A high-hazard lawn irrigation connection, as section 14 defines it, sits under the high-hazard device line: an approved reduced pressure principal assembly at all high hazard locations. The section does not print a separate model number for that irrigation case.
Inspections that are not the assembly test
Section 14 says all employees continually attempt to locate unprotected cross connections by visual inspections of the system. The same section says a Blue Ridge Rural Water Company certified operator visually inspects a new water service connection at the time of meter installation, and visually inspects an existing service connection as meters are being read or as system operations are being conducted. Those sentences describe a visual inspection by the company’s operator. They do not describe the annual test of a testable assembly. Inspection vs testing is that split on Greenville Water’s manual.
What the September 30, 2025 specifications add
The cross-connection paragraph on WDS 9 says there shall be no connection between the distribution system and any pipes, pumps, hydrants, or tanks whereby unsafe water or other contamination materials may be discharged or drawn into the system. It says no bypasses shall be allowed unless the bypass is also equipped with an equal, approved back-flow prevention device.
It says high hazard category cross connections shall require any air gap separation or an approved reduced pressure backflow preventer. The printed word is “any.” The sentence does not print an inch minimum. The one-inch and two-inch minimums on Air gap separation are the other published manuals, not this paragraph. Section 14, above, names a reduced pressure principal assembly for every high hazard location and does not mention an air gap. This page does not choose between those two sentences. Use the letter on the account, or call (864) 895-1719, before you buy an assembly.
The same paragraph says reduced pressure principal backflow prevention assemblies shall not be installed in any area location subject to possible flooding. That includes pits or vaults which are not provided with a gravity drain to the ground’s surface that is capable of exceeding the discharge rate of the relief valve. If the assembly is installed in a pit, the drain line shall be a minimum of 2 times the size of the line entering the backflow prevention device. The drain cannot empty into any type of ditch, storm drain, or sewer, which could flood water back in the pit. All piping up to the inlet must be suitable for potable water. The pipe must be AWWA or NSF approved. Black steel pipe cannot be used.
The fire-line sentence says fire line sprinkler systems and dedicated fire lines, except those in the high hazard category, shall be protected by an approved double check assembly. The sentence does not name the assembly for the high-hazard category it excepts. Fire-line backflow is the state rule and the other published manuals. Use the notice for the device on that account. The specifications do not say who files an annual test.
A hydrant meter
The hydrant meter rental page says the hydrant meter includes a backflow device, spelled “devise” on that page, that is at no time to be removed from the hydrant. It says the company can and will make periodic on-site checks that the hydrant meter and backflow devices are operated properly. The rental charges and the time limit are printed on that page. They are not a price for the annual assembly test in section 14. How that rental compares with the other utilities that print a hydrant meter is on Temporary hydrant meters.
What these pages do not include
On October 31, 2026, the bylaws page, the policies PDF, the developers page, the specifications PDF, the irrigation policies page, the service area page, the location and hours page, the hydrant meter rental page, the other forms page, and the customer notice page did not include a blank backflow test report or a filing address for a finished test. The other forms page is a tap-forfeit form. The customer notice page is a pressure-increase notice. It is not a backflow test letter. This check did not open every file in the documents folder.
Section 14 does not describe a failed test, a repair window, or a retest. How Greenville Water, Spartanburg Water, and Anderson treat a result that does not pass is on Failed backflow test. Those clocks are not Blue Ridge Rural Water’s.
Other notes for Anderson, Pickens, and Oconee accounts, and the pointer that used to say a Blue Ridge page had not been confirmed, are on Anderson, Pickens, and Oconee. Official links are on Resources.
Greenville County testers Company policies PDF
Sources checked October 31, 2026: the company bylaws and policies page and the Company Policies PDF linked there (section 14, Cross Connection Control, and the three system names in section 15; file properties title “2020 Company Policies,” modification stamp July 30, 2026); the developers page and the Standard Specifications PDF linked there (pages dated 9-30-2025, cross-connection paragraph on the page marked WDS 9); the service area page; the location and hours page; the irrigation system policies page; the hydrant meter rental page; the other forms page; and the customer notice page. Section 14 does not print its own adoption date.