What is a backflow preventer?

A backflow preventer is the approved device or assembly that sits between a public water system and a source of contamination. The letter from your utility names which one is on the account. This page is how to tell those parts apart.

Sources checked October 22, 2026.

If this page and the letter on your account disagree, follow the letter and the manual it cites. What is backflow testing is the annual test. Backflow preventer installation is who puts the assembly in. Double check versus reduced pressure and RPZ testing are the two testable assemblies customers ask about most. This page is the device itself.

The words the rule uses

R.61-58 definition (9) says a backflow prevention device is any device approved by the Department for use in preventing backflow under prescribed limited conditions of use. The definitions in that file do not give “backflow preventer” or “backflow prevention assembly” a separate entry.

Section (F)(1)(b) of R.61-58.7 uses both words in the duty itself. No person may install or keep a cross connection between a public water system and any other non-public water system, a sewer, or a line from a container of liquids or other substances, unless an approved backflow prevention device or assembly sits between the public system and the source of contamination.

The SCDES Cross Connection Control page describes the same program in its own words. It says every public water system surveys for unprotected cross connections and controls them through the proper use of backflow prevention assemblies. It says testing is done by a state-certified tester, and that assemblies used in South Carolina have to be on SCDES’s list of approved backflow prevention assemblies. The certification section of that page says the course covers how cross connections should be protected or eliminated using approved assemblies, devices, or methods.

Greenville Water’s backflow page uses “backflow prevention device or assembly” and “backflow preventers” for the same requirement. That page says customers whose water presents a backflow hazard must install one and have it tested annually under SCDES and Greenville Water standards. The same page says Greenville Water does not install or test backflow preventers.

What the preventer is there to stop

A cross connection, in definition (40) of R.61-58, is any actual or potential connection or structural arrangement between a public water supply and any other source or system through which it is possible to introduce into any part of the potable system any used water, industrial fluid, gas, or substance other than the intended potable water. Bypass arrangements, jumper connections, removable sections, swivel or changeover devices, and other temporary or permanent devices through which backflow can occur are cross connections under that definition. A pipe around an assembly, a second assembly in parallel, and the small bypass on a fire-line detector are separated on Bypass and parallel assemblies.

The three manuals define backflow. They do not share one sentence:

  • Greenville Water’s Cross Connection Control Manual (PDF created November 10, 2025) defines backflow as the reversal of flow in a water distribution system as a result of back pressure or back siphonage. Back pressure, in that manual, is a pressure higher than the supply pressure, caused by a pump, elevated tank, elevated piping system, boiler, or any other means that may cause pressures greater than the public water supply. Back siphonage is backflow caused by negative or reduced pressures in the supply piping. The manual says decreases in the public supply piping are usually the result of increased supply demands, such as firefighting or water main breaks, or of loss of pressure because water mains are shut off for maintenance. Greenville Water’s public page states the customer version of the same idea: backflow is the unwanted reverse flow of water or other substances in a plumbing system, which can contaminate potable water.
  • Spartanburg Water’s manual revised June 4, 2026 (PDF created June 5, 2026) defines backflow as the undesirable reversal of the intended direction of flow in a potable water distribution system as a result of a cross connection. Backpressure is any elevation of pressure in the downstream piping system, caused by a pump, elevated tank or piping, steam, air pressure, or any other cause, above the water supply pressure at the point which would cause or influence a reversal of the normal direction of flow. Back-siphonage is the flow of water or other liquid, mixtures, or substances into the potable water system from any source other than its intended source, caused by a reduction of pressure in the potable water system.
  • Anderson’s September 2008 policy defines backflow as the undesirable reversal of flow of water in a potable water distribution system as a result of a cross connection. Back pressure is a pressure higher than the water purveyor’s supply pressure, caused by a pump, elevated or pressurized tank, boiler, or any other means that may cause a backflow. Backsiphonage is backflow caused by negative or reduced pressure in the supply piping.

Use the manual your utility cites. A pump in those definitions, the state design standard’s 25 and 20 psi lines, and the different figures Powdersville Water, Westminster, and SJWD print for a fire pump are on Booster pumps and backpressure.

Greenville Water defines containment as an approved backflow prevention assembly at the water service connection to the customer’s premises, usually immediately downstream of the meter. That is the usual place the preventer that protects the public system sits on that utility. Where Greenville Water, Spartanburg Water, and Anderson Electric City allow the assembly to sit, and who installs it, is on Backflow preventer installation.

A testable assembly and a dual check are different parts

Section (7) of R.61-58.7(F) names the assemblies a certified tester tests when they protect the public system from a customer’s service: a double check valve assembly, a pressure vacuum breaker, and a reduced pressure principle assembly. The test is after installation and before the customer uses the assembly, at least once a year except for the low-hazard residential irrigation case in section (3), and again immediately after any repair. The written report goes to the water system. That test is What is backflow testing.

Section (3) names a different part for low-hazard residential lawn irrigation. The minimum device that sentence allows is a residential dual check. If the utility’s written policy uses dual checks, the policy sets how often those devices are changed out. If the policy requires a testable assembly instead, the policy sets the test schedule. A residential irrigation system that adds chemicals, or that is also connected to a water source other than an approved public system, is a high hazard under section (3)(b) and follows section (4). Lawn schedules for Greenville Water, Spartanburg Water, and Anderson are on Irrigation backflow testing. The house service, separate from that lawn schedule, is on Residential backflow testing.

The manuals describe the dual check as the part without the test hardware:

  • Greenville Water’s definition calls a residential dual check an assembly of two independently operating spring-assisted check valves. It says this assembly is not equipped with shutoff valves or test cocks, and that it is used for selectively approved low-hazard connections.
  • Spartanburg Water calls it a device of two independently operating spring-assisted check valves, not equipped with shutoff valves or test cocks, for selectively approved low-hazard connections, and residential only. The customer definition in the same section says a single-family dwelling requires a dual check device, and that a commercial, industrial, or multi-family site is evaluated for the degree of hazard and then receives the appropriate testable assembly. Who installs that dual check is on the installation page.
  • Anderson’s appendix defines a residential dual check valve as a device of two independently operating spring-assisted check valves that can be located with the meter yoke or independent of it. It says this device is not typically equipped with a shutoff valve or test cocks, and that it is used for selectively approved low-hazard connections. The same appendix defines ASSE 1024 as the performance standard for dual check backflow preventers. The policy still says “SC DHEC.”

The January 1, 2026 approved-assembly list is a catalog of assemblies. The sections in the file read on October 22, 2026 are double check valve assemblies, Type I and Type II detector assemblies, reduced pressure principle assemblies, and pressure vacuum breakers together with spill-resistant pressure vacuum breakers. That file does not use the words “dual check.” A dual check on a service is the device the irrigation policies describe. Assemblies used in South Carolina have to be on the list. The filename on the state site spells “equipment” the way the URL shows.

How to match the part on the property to the letter

The definitions give a short field check. The letter still controls if a marking and the letter disagree.

  • Two shutoff valves, one at each end, and test cocks, with no relief valve between the checks: the double check valve assembly the manuals define. Greenville Water and Spartanburg Water both describe two independently operating spring-assisted check valves, resilient-seated test cocks, and resilient-seated or ball shutoff valves. Anderson describes two internally loaded check valves, spring loaded or internally weighted, between two tightly closing resilient-seated shutoff valves, with resilient-seated test cocks, used to protect against a non-health hazard. The hazard split is on Double check versus reduced pressure.
  • Those same shutoff valves and test cocks, plus a hydraulically operating relief valve between the checks and beneath the first check: the reduced pressure principle assembly. Greenville Water’s definition says it stays accessible for in-line testing in a location that is never subject to flooding, and that it is approved for high-hazard cross connections. RPZ testing is that assembly. The state regulation, the January 2026 list, the sample form, and the three manuals read for this page do not use the letters RPZ. They use reduced pressure principle assembly, often shortened to RP. The sample form’s label for that assembly is “Reduced Pressure Backflow Preventer.”
  • One spring-loaded check, an air-inlet valve, shutoff valves at each end, and two test cocks: Spartanburg Water’s definition of a pressure vacuum breaker. That definition says the assembly is approved only for back-siphonage, that it is installed 12 inches above any downstream piping, outlets, or flood level rim, and that Spartanburg Water approves it for high-hazard cross connections. Section (9) of R.61-58.7(F) says that where a pressure vacuum breaker is used, it is installed at least 12 inches above the highest downstream piping and is not subject to backpressure. Section (2) names an approved double check valve assembly or a pressure vacuum breaker as the minimum on a low hazard, except as section (3) provides for residential lawn irrigation. Greenville Water’s definition list, in the manual read on October 22, 2026, does not include a pressure vacuum breaker. Where those sentences do not read the same way, use the notice. Anderson’s statement that a pressure vacuum breaker is not used where backpressure is expected is on the irrigation page. The height sentences and the 2025 field order are on Pressure vacuum breaker.
  • A main-line double check with a small bypass that includes another double check and a meter: Greenville Water’s and Spartanburg Water’s definition of a double detector check, used on fire lines. Anderson’s definition says the bypass may have a meter. Fire-line backflow covers detector assemblies, including the Type I and Type II difference on the state list.
  • Two checks, and no test cocks: the residential dual check described above. It is the device section (3) allows for low-hazard residential irrigation when the utility’s policy uses dual checks. It is not one of the three assemblies section (7) lists for the annual test.
  • An open vertical gap between the end of a supply pipe and the flood rim of a tank or fixture: an air gap. Greenville Water and Spartanburg Water both define it as the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet and the flood rim of the receptacle, at least twice the diameter of the water supply outlet and never less than one inch. Anderson’s definition uses the flood level rim and says these separations must be at least twice the diameter of the water supply outlet but never less than two inches. Each manual lists the air gap with the other means of preventing backflow. The three minimums are not the same number. The distances, the relief-valve drain gap, and where each manual places the separation are on Air gap separation. Use the manual the notice cites.

SCDES’s sample test form is titled a backflow prevention assembly test and maintenance form. The certification line says the device was tested. The form’s labels are a reduced pressure backflow preventer (RP, ASSE #1013), a reduced pressure detector assembly (RPDA, ASSE #1047), a double check valve assembly (DC, ASSE #1015), a double check detector assembly (DCDA, ASSE #1048), a pressure vacuum breaker (PVB, ASSE #1020), and a spill-resistant vacuum breaker (SRVB, ASSE #1056). The form has lines for make, model, size, serial number, and exact location. It says many jurisdictions require their own form. A field reading of the utility forms is on How to read your notice.

The January 1, 2026 list groups pressure vacuum breakers with spill-resistant pressure vacuum breakers. That section says they are approved for protecting the potable system from back siphonage only, whether a health hazard or a non-health hazard is involved, that they are not designed for backpressure, and that they must be installed 12 inches above any downstream plumbing. The definition sections of the three manuals read for this page do not define a spill-resistant vacuum breaker. If the letter names one, follow the letter.

Anderson’s policy names parts it does not accept as protection for the public system: atmospheric vacuum breakers, barometric loops, a double check with an intermediate atmospheric vent, and hose-bib vacuum breakers. The policy says those may be used for internal protection, and that an additional device is still required under the policy. That sentence is Anderson’s. The same limit, applied to lawn systems, is on Irrigation backflow testing.

What has to be on the state list

Section (6) of R.61-58.7(F) says the Department prepares and publishes a list of backflow prevention assemblies approved for use in South Carolina, and updates that list at least once a year. The January 1, 2026 file is the list linked from the program page. Its opening notice says local plumbing laws apply, the manufacturer’s installation instructions are followed, and SCDES may add an assembly or remove one. Note 3 on that list applies to a reduced pressure principle assembly: the relief port must never be submerged or subject to a toxic environment, which prohibits a pit that cannot drain by gravity to the ground surface, and a vertical orientation is not acceptable unless the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research has approved it. Those installation limits are also on Backflow preventer installation and RPZ testing. The notice names the assembly for the account. This page does not name a manufacturer.

What you do with it

A testable assembly is tested by a person holding an up-to-date backflow prevention assembly tester card from the Department. The classification that tests for the general public is the General Tester. General vs Limited is how those cards differ. County pages copy General Testers from the SCDES report printed July 9, 2026. Start with Greenville County. Confirm the current card before you hire. A row on this site is not an appointment.

The regulation does not set a price for the device or for the test. The cost guide keeps a third-party range for a test a customer hires, labeled as that range. Official links are on Resources.

What a backflow test is Double check versus reduced pressure

Sources checked October 22, 2026: R.61-58 on des.sc.gov, the SCDES program page, the January 1, 2026 approved-assembly list, the SCDES sample test form, Greenville Water’s backflow page and November 10, 2025 manual, Spartanburg Water’s June 4, 2026 manual, and Anderson Electric City’s September 2008 policy.