Easley Combined Utilities backflow testing
The water page says Easley Combined Utilities kept its February 2005 cross-connection policy after the state minimum changed. The blank test form does not print a due date or a place to send it.
Sources checked October 18, 2026.
The public page is Water on the Easley Combined Utilities site. The cross-connection section is a slideshow titled Cross Connection & Backflow Prevention. The same page links a PDF the button labels Backflow Prevention Test. The file title is Backflow Device Test Report, and the form itself is headed BACKFLOW DEVICE TEST REPORT FORM. The page also links Standard Water & Sewer Specifications. The cover of that PDF says March 2025. The file linked on October 18, 2026 carries a PDF modification stamp of April 24, 2026. The February 2005 policy named in the slideshow was not a separate file on the water page.
The water page prints the office at 110 Peachtree St., P.O. Box 619, Easley, SC 29641. It prints the phone as 864-859-4013 on the outage line and as 1-864-859-4013 on the office line, and it prints customerservice@easleyutilities.com. The specifications cover prints the same street, post office box, and 864-859-4013. The slideshow does not name the Cross Connection Officer, and it does not print a separate phone or email for that officer.
The water page says ECU furnishes drinking water to its 13,300 retail water customers from an 18 MGD plant, that raw water comes from Saluda Lake, and that ECU has an emergency connection with the Greenville Water System. That connection is an emergency supply. It is not Greenville Water’s testing program. Greenville Water deadlines do not transfer to an Easley Combined Utilities account. If this summary and the letter on the account disagree, follow the letter and the current page.
What the water page calls backflow
The first slide says backflow is the reversal of the flow of water, or a mixture of water and other undesirable substances, from any source into the distribution pipes of the potable water system. It says that reversal can let drinking water become contaminated. The same slide says SCDHEC regulations require, as a minimum, dual check valve backflow assemblies on residential lawn sprinkler systems. What is backflow testing is the state rule, R.61-58.7(F). The later slides on the same page describe a local policy that the utility says it did not relax to that minimum.
The policy the page describes
The Backflow Regulations slide says that when SCDHEC promulgated lawn-sprinkler backflow rules in 2005, the minimum protection was a double check valve assembly. It says Easley Combined Utilities approved its Cross Connection Control Policy in February 2005 to comply with the regulation then in effect. It says a later update let a dual check valve assembly serve as the minimum, and let a local utility keep the double check valve assembly if the local governing body enacted that requirement. The slide says that when the state requirement was relaxed, ECU chose not to change its Cross Connection Control Policy.
That policy is not linked from the water page. This summary does not add clauses from a file that was not there. The sentences above are the water page’s account of the policy.
Dual check and the annual test
The Dual-Check Valves slide says dual check valves are not testable, and that SCDHEC mandated a routine change-out schedule for the local utility. It says a reasonable change-out frequency was determined to be once every three years, and that a change-out requires a plumber and a new check valve assembly. It does not say ECU is on that three-year schedule for a particular account.
The same slide says double check valves are testable assemblies. It says ECU’s policy requires that they be tested every year, and that manufacturers recommend the same. It says the results are sent to ECU’s Cross Connection Officer. It says a double check is, by its nature, a higher level of protection against cross-connection contamination. Double check versus reduced pressure is the state hazard split. Irrigation backflow testing is the state irrigation rule and the other published Upstate manuals. ECU’s annual-test sentence is the one on this water page.
The slide does not print a number of days after the notice, a late-test fee, or a disconnection step. How to read your notice walks through the forms other Upstate utilities publish. Use the letter on the account for the date and for where that letter says to send the report.
The cost comparison on the page
The Cost Analysis slide says a 10-year comparison was made of dual check and double check installations, including change-out and testing. It says that comparison found it less expensive for the customer to install and maintain a double-check valve assembly. It says allowing dual-check valves increases the cost to the customer and lowers the protection on the system. The slide does not print a dollar amount for the device, the plumber, the annual test, or the change-out.
The cost guide is a third-party range for a test a customer hires. It is not this comparison, and it is not an Easley Combined Utilities fee. No test fee was printed on the water page, the test form, or the specifications sections read for this page.
The test form
The Backflow Device Test Report is one page. The blanks are:
- Date, account name or business name, and account address
- Account number and meter number
- Device name, model number, serial number, size, and device location
- Tested by, printed
- Check No. 1, Check No. 2, and an air-inlet valve or relief valve, each marked Leaked or Closed Tight, with a differential-pressure line, and an “Opened at ___ lbs.” line on the air-inlet or relief valve
- Shutoff valves marked #1 Gate or Ball and #2 Gate or Ball, each Leaked or Closed Tight
- A row for repairs and new materials, and a repeat of the checks for the test after repairs
- A line that the data are certified correct, then tester signature, certification number, company name, and company telephone number
- Category: General, Limited, or Inspector Tester
- Method of testing, test kit used, and comments
The form does not print a pass or fail line, an assembly-type checkbox, a due date, a fee, or an address, email, or fax for the finished report. The water page says the results go to the Cross Connection Officer and does not say how. Ask Easley Combined Utilities, at the phone on the water page, before you rely on a filing method from an older letter. General vs Limited is the state card. The form lists all three categories. Confirm the current SCDES card before you hire.
What the March 2025 specifications add
Section 05 of the specifications is Water System Piping and Appurtenances. It is a construction specification, not a customer notice. Subsection 2.10 is reduced-pressure backflow preventers. It says to provide a reduced-pressure backflow preventer approved by SCDES. It says to install the preventer, depending on size, in a vault or a meter box as the drawings indicate. If an above-ground installation is required, it says to install the device in a hot box. RPZ testing is that assembly on the other published manuals. Backflow preventer installation is how those manuals describe a new assembly.
Subsection 3.6 is Cross Connection Control. It says to provide an air gap wherever possible. That subsection does not print a minimum distance. The distances the other manuals print are on Air gap separation. It says there are to be no connections between the distribution system and any pipes, pumps, hydrants, or tanks from which unsafe water or other contaminated materials may be discharged or drawn into the water system. It says not to include a bypass unless the bypass has an approved double check backflow prevention device.
The fire-line sentence says to protect potable waterlines from contamination by fire-line sprinkler systems and dedicated fire lines, except those in the high-hazard category, by an approved double check valve assembly. The sentence does not name the assembly for the high-hazard category it excepts. Fire-line backflow is the state rule and the other published manuals. Use the notice for the device on that account.
The same subsection says a reduced-pressure principle assembly shall not be installed in an area subject to flooding. That includes a pit or vault without a gravity drain to the ground surface that can exceed the discharge rate of the relief valve. It says that, generally, a drain line in a pit is two times the size of the line entering the device. It says the drain cannot empty into a ditch, a storm drain, or a sewer that could flood water back into the pit. It says all piping up to the inlet of the device must be suitable for potable water, that the pipe must be AWWA or NSF approved, and that black steel pipe cannot be used on the inlet side.
Finding a tester
Pickens County testers are General Testers from the SCDES report dated July 9, 2026. That section of the report includes rows whose city is printed as Easley. This site does not copy a tester list from Easley Combined Utilities. A row here is not an appointment. Confirm the card is still current, and confirm with the utility that the tester’s category is one it will accept on the form above.
Other notes for Anderson, Pickens, and Oconee accounts are on Anderson, Pickens, and Oconee. Official links are on Resources.
Pickens County testers Easley Combined Utilities water page
Sources checked October 18, 2026: the Easley Combined Utilities water page, including the Cross Connection & Backflow Prevention slideshow on that page (What is Backflow, Backflow Regulations, Dual-Check Valves, and Cost Analysis); the Backflow Device Test Report PDF linked from that page; and the Standard Water & Sewer Specifications PDF linked from that page (cover dated March 2025; PDF modification stamp April 24, 2026), Section 05 subsections 2.10 and 3.6. The February 2005 Cross Connection Control Policy named on the water page was not linked there.