What SCDES requires of a backflow test kit

A General Tester in South Carolina has to have a backflow prevention assembly test kit, in the tester’s possession or owned by the employer. At recertification the regulation uses that tester’s own differential pressure gauge. This page is what those documents require of the kit. It does not name a manufacturer, and it does not list a price.

Sources checked October 21, 2026.

If you need an assembly tested, you hire a General Tester. You do not buy the kit. What is backflow testing is the annual-test rule. General vs Limited is who may test for the public. County lists from the July 9, 2026 SCDES report start at Greenville County.

Who has to have a kit

The certified-tester definition in R.61-58 says a General Tester has completed an approved backflow prevention training and certification course sponsored or approved by the Department, and has personal possession of, or the employer owns, a backflow prevention assembly test kit. That person tests assemblies for the general public.

The same definition says a Limited Tester, an Inspector Tester, and a Manufacturer’s Agent have the same qualifications as the General Tester, with a different limit on whose assemblies they test. The kit is part of those qualifications. Section (8) of R.61-58.7(F) names the four classifications and points to that definition. How the cards differ is on General vs Limited.

The gauge, and how accurate it has to be

R.61-58.7(F)(8)(a) says each certified tester’s license expires three years from the date of issue. To renew it, the tester successfully completes a written examination and performs the prescribed test on an approved reduced pressure principle assembly, a double check valve assembly, and a pressure vacuum breaker, using the tester’s own differential pressure gauge. The regulation says the gauge must be accurate within 2 percent of full scale or plus or minus 0.3 pounds per square inch differential (PSID). A gauge found to be inaccurate or malfunctioning has to be calibrated or repaired as needed before certification will be renewed.

The SCDES program page states the same accuracy line in its own words: within 2 percent of full gauge scale or ±0.3 psi differential. The wet lab on that page is the same three assemblies.

Those two sentences are the check at renewal. They are not the same sentence as the annual line in the study guide. The cover letter in the 2025 recertification study guide says test equipment and gauges are required to be certified or calibrated annually. The gauges section of that guide repeats the annual sentence. It also says to treat gauges as instruments, to snug needle valves rather than overtighten them, to open every valve and shake the hoses out at the end of a test, and to store the gauge with the valves open. The guide does not name a calibration shop, and it does not print a fee for that annual check. The three-year check in the regulation and the annual line in the study guide are spelled out on Backflow test kit calibration.

Anderson’s September 2008 policy defines a differential gauge as an approved and calibrated gauge. Its calibration sentence says the tolerance is plus or minus 2 percent, equal to 0.3 psid. That wording is Anderson’s. It is not a restatement of the regulation’s “2 percent of full scale or plus or minus 0.3 PSID.”

Seneca Light & Water’s manual, revised October 2021, suspends a certified tester from testing when the gauge is out of the tolerance in the gauge manufacturer’s specifications. The tester may continue after the gauge is replaced or repaired and calibrated to that specification. The manual does not print the state’s 2 percent line in that paragraph. How Seneca keeps its own permitted list is on Seneca Light & Water.

Three-valve kits and five-valve kits

SCDES links two 2025 procedure files from the program page: the three-valve test procedures and the five-valve test procedures. Each file has a sheet for a double check valve assembly by pressure differential, a sheet for a double check by direction of flow, a sheet for a pressure vacuum breaker by direction of flow, and a sheet for a reduced pressure principle assembly by pressure differential. This page does not reprint the steps. The reduced-pressure sheet in each file is followed, in the order that sheet prints, on RPZ testing step by step. The pressure-vacuum-breaker sheet in each file is on Pressure vacuum breaker. The PDF remains the procedure.

The documents do not use one hose count for every sentence:

  • The Bureau of Water letter dated June 1, 2018, linked from the program page, calls the two remaining double-check options a differential pressure test, which it describes as 2 hoses, and a direction of flow test, which it describes as 1 hose.
  • The study guide says the differential-pressure test of a double check uses the differential gauge with two hoses, closes only shutoff valve number 2, and leaves shutoff valve number 1 open. It says the first test is the tightness of shutoff number 2, because flow through the assembly can make the gauge read higher and produce a false pass.
  • Anderson’s definition says a differential-pressure test requires a three-hose or a five-hose differential gauge. Its acceptable-methods paragraph recognizes only the differential-pressure method for a reduced pressure assembly, using that three-hose or five-hose gauge. For a pressure vacuum breaker it accepts differential pressure or direction of flow using the differential gauge.
  • The three-valve pressure-differential sheet for a double check includes steps that attach a high-side hose, a low-side hose, and a vent or bypass hose.

Where a hose count in one of those documents does not match another, use the sheet for the gauge in your hand and the letter your utility accepts. This page does not pick a brand of three-valve or five-valve gauge.

The vertical tube is not the kit the state still allows

The June 1, 2018 letter says the vertical tube test procedure for a double check valve assembly is not allowed as of December 31, 2018. From January 1, 2019 the two options it names both use the differential gauge. The letter says the vertical tube procedure was taught in South Carolina and not elsewhere, that industry standards require a differential gauge on a double check, and that water systems want a numerical value for the check springs rather than only knowing both checks hold the minimum of 1.0 psi. The letter is addressed to certified testers and public water systems. It still says “SCDHEC.” Tester cards are now SCDES cards.

The 2025 direction-of-flow sheets for a double check still use the words “vertical tube” in the steps, including a step that moves the vertical tube from one test cock to another. The letter and those sheets are both linked from the program page. This page does not rewrite a step to make them match.

Anderson’s 2008 policy still describes a direction-of-flow test with a vertical sight tube — one paragraph spells it “Vertical Site Tube” — or with a differential gauge using only the high hose. The appendix says a differential gauge is required on reduced pressure assemblies and pressure vacuum breakers, and optional on double check valve assemblies. The same appendix says the test-kit line is the make and model of the differential gauge, and the method line is “Direction of Flow” or “Differential Pressure.” The unacceptable-methods paragraph says Electric City Utilities and SC DHEC no longer recognize the transfer-of-pressure, single-gauge, or ten-pound back-pressure methods for a double check. The policy file read on October 21, 2026 is still the 2008 revision. The later letter is the one the SCDES program page still publishes. Double check versus reduced pressure is the longer account of that split. RPZ testing is Anderson’s rule that a reduced pressure assembly uses the differential-pressure method only.

What the study guide says a passing gauge reading is

The study guide prints minimum differentials. It does not print the maximums in Anderson’s Table 2.

  • On a double check, both check valves hold tight at 1.0 psid or greater. The three-valve and five-valve pressure-differential sheets say the gauge reading for that check tightness should be 1 PSID or above.
  • On a reduced pressure assembly, the study guide says the first check’s acceptable value is 5.0 psid or greater, the second check is 1.0 psid or greater, and the relief valve has to keep the zone between the checks at least 2.0 psid less than supply pressure. The five-valve reduced-pressure sheet says to record check number 1 as tight if the gauge reads 5 PSID or above. The three-valve reduced-pressure sheet labels that check as 5 psid or greater and check number 2 as 1 psid or greater.
  • On a pressure vacuum breaker, the study guide says the high hose on test cock number 2 is the air-inlet test, and the high hose on test cock number 1 is the check-valve test. The five-valve vacuum-breaker sheet records 1.0 psid or greater on the check and 1.0 psid or better when the air inlet opens. Those lines, and the three-valve sheet’s matching lines, are on Pressure vacuum breaker.

Anderson’s Table 2 adds maximums the study guide does not print. Those bands stay on RPZ testing and Double check versus reduced pressure. They are not a statewide number from R.61-58.7(F).

What the form asks about the kit

SCDES’s sample test form has a line for test type and a line for the gauge serial number. It says many jurisdictions require their own form.

Greenville Water’s blank field test form leaves blanks labeled “Method of Testing” and “Test Kit Used.” It does not print a gauge serial number. Filing for that utility is on Greenville Water.

Easley Combined Utilities’ backflow device test report has the same two blanks, method of testing and test kit used. The rest of that form is on Easley Combined Utilities.

Anderson’s appendix, cited above, asks for the make and model. A field-by-field reading of the forms already on this site, including Spartanburg Water’s test-kit line, is on How to read your notice.

No brand and no kit price in these documents

The text of the regulation, the program page, the study guide, the course overview, the 2025 procedure sheets, the sample form, the vertical-tube letter, and the utility forms cited above does not name a gauge manufacturer. A form that asks for make and model is the tester recording the gauge that was used. It is not an SCDES endorsement.

None of those documents prints a purchase price for a test kit. The cost guide keeps a third-party range for a test a customer hires. That range is not a price for a gauge.

The course overview says the certification class covers assembly testing and basic troubleshooting, and that repair classes are separate. Students have to demonstrate the field procedure for a reduced pressure assembly, a double check, and a pressure vacuum breaker without the written procedures in front of them. Class dates and the three-year card are on General vs Limited. A General Tester who wants a listing started from the state report uses For testers.

Official links are on Resources.

General vs Limited Greenville County testers

Sources checked October 21, 2026: R.61-58 on des.sc.gov; the SCDES Cross Connection Control program page; the 2025 recertification study guide; the SCDES tester-certification course overview; the June 1, 2018 vertical-tube letter linked from that program page; the 2025 three-valve and five-valve test-procedure PDFs; the SCDES sample test form; Greenville Water’s blank field test form; Easley Combined Utilities’ backflow device test report; Anderson Electric City’s September 2008 cross-connection policy; Seneca Light & Water’s backflow manual revised October 2021.