Upstate South Carolina

Upstate Backflow

Annual backflow testing directory. Not a water utility.

Backflow assembly testing for businesses in Upstate SC

On these three systems a business account is on a testable assembly when the utility’s rule says so. The annual test is a certified tester’s written report on that assembly. The letter names the assembly and the date. These documents do not say how long the visit takes.

Sources checked October 26, 2026.

If this page and the letter on your account disagree, follow the letter and the manual it cites. What is backflow testing is the state rule for any testable assembly. What is a backflow preventer is how to tell the parts apart. A house, including a multi-dwelling that Spartanburg Water puts on a testable assembly, is on Residential backflow testing. Shops the Anderson table marks as a high hazard stay on High-hazard commercial. This page is the business account: who the manuals count, what the tester is checking, and who may sign the report.

What the annual assembly test is

R.61-58.7(F) section (7) applies when a double check valve assembly, a pressure vacuum breaker, or a reduced pressure principle assembly is installed to protect a public water system from a customer’s service. A certified tester tests the assembly after installation and before the customer uses it. Except for the low-hazard residential lawn case in section (3), each assembly is tested at least once a year. After a repair of any kind, the assembly is tested again immediately. The public water system receives a written report of the inspection and testing results, submitted by the certified tester who made the test.

The SCDES Cross Connection Control page says every public water system keeps records of the location, type, and size of each assembly and of the annual testing results, and that all testing is done by a state-certified tester. Assemblies used in South Carolina have to be on SCDES’s list of approved backflow prevention assemblies. The filename on the state site spells “equipment” the way the URL shows.

The test uses a differential gauge on the test cocks. What SCDES requires of that gauge is on Backflow test kits. The field order on the 2025 reduced-pressure sheets is on RPZ testing step by step. Double check versus reduced pressure is which assembly the hazard calls for. A utility’s look at a new installation is a different visit from this test. Inspection vs testing is that split on Greenville Water.

Which account is a business account

The three manuals do not share one definition.

Greenville Water’s manual (PDF created November 10, 2025; the policy inside was adopted September 6, 2022) says most commercial, industrial, irrigation (as noted), and private fire-protection customers install, maintain, and test the assembly on the service line. Greenville Water’s backflow page says customers whose water presents a backflow hazard must install a device or assembly and have it tested annually under SCDES and Greenville Water standards. The same page says Greenville Water does not install or test backflow preventers. It does not print a separate definition of “commercial.”

Spartanburg Water’s commercial and industrial page, in the Cross Connection Control and Backflow section, and section 6 of the manual revised June 4, 2026 (PDF created June 5, 2026), use four lines:

  • A residential customer with a 3/4-inch to 1-inch service has a residential dual check installed by Spartanburg Water.
  • A commercial customer has an approved testable assembly based on the degree of hazard the cross-connection technicians identify.
  • An industrial customer has an approved testable assembly on the same basis.
  • A multi-dwelling customer has an approved testable assembly on the same basis.

The public page says certain types of commercial and industrial backflow assemblies must be tested annually by an SCDES-certified tester. Section 10.2 says all existing approved backflow assemblies are tested annually, excluding low-hazard residential lawn irrigation. The definitions section says a single-family dwelling requires a dual check, and that a commercial, industrial, or multi-family site is evaluated for the degree of hazard and then receives the appropriate testable assembly. Questions go to Matthew Jamison, Field Operations Manager, at (864) 598-7213 or ccc@spartanburgwater.org.

Anderson’s September 2008 policy defines the words in its appendix:

  • Commercial is a customer account associated with a customer other than a single-family residence. The policy’s examples are home-based businesses, standalone businesses, duplexes and multi-plexes supplied through only one meter, subdivision homeowner associations, and industries.
  • Industrial is a customer account associated with an industry or large-scale production of a good.
  • Residential is a dwelling that shelters a single family, including a duplex or multi-plex with an individual meter for each unit. The same entry says properties owned by a company or by multiple cooperative owners, with homeowner associations given as the example, are classified as commercial.

A home-based business and a duplex on one meter are commercial under that appendix. A duplex with a meter on each unit is residential under the same appendix. Those sentences are Anderson’s. They are not Greenville Water’s and they are not Spartanburg Water’s. Use the manual the letter cites.

The commercial, industrial, and dedicated-fire-line heading in that policy says those lines are tested when the device is installed and every 12 months after that, by a tester the policy describes as currently certified by SC DHEC and in good standing with Electric City Utilities. The policy still prints “SC DHEC.” Current cards are SCDES cards. Reminder letters go out about 30 days before the test is due. The 12-month fire-line sentence is also on Fire-line backflow. Commercial in-ground irrigation is a separate 12-month heading, summarized on Irrigation backflow testing. The policy says Table 1 is a guide and that each facility is evaluated on its own. The notice names the assembly.

The assembly at the service

Greenville Water defines containment as an approved backflow prevention assembly at the water service connection, usually immediately downstream of the meter. Section 5-2 says the usual place is a box near the meter or inside a building in a mechanical area, before the first connection off the service line, and that the standard procedure is containment.

Spartanburg Water section 5 says the preferred method is containment: an approved assembly immediately downstream of the meter, or immediately inside the building and before the first connection off the service line. Section 6 says that, when an assembly is required, one is installed on each service line, directly behind the meter box, near the property line, or immediately inside the building, and approved by a Spartanburg Water cross-connection technician. The same section says premises with internal cross connections that cannot be permanently corrected, with intricate plumbing, or where entry to all portions is not readily accessible for inspection, are protected by an approved assembly in the service line.

Anderson defines containment as an approved assembly at the service connection where it is physically and economically unfeasible to find and permanently eliminate or control every cross connection inside the customer’s system, or as an approved assembly on the line that supplies a portion of the customer’s system where the cross connections cannot be controlled at the point they occur.

On Greenville Water, section 2-2 gives the plumbing official the International Plumbing Code from the service connection out to the ends of the customer’s system. That internal plumbing review is not the annual assembly test the water system asks for. The letter is the water system’s assembly.

A new business tells the utility how the water will be used

Spartanburg Water section 8.1 says that when the customer applies and purchases the water service, the customer provides information on the use of the water at the new connection. Spartanburg Water evaluates the new service and tells the customer which assembly is required, including an installation timeline. The customer installs it. Spartanburg Water inspects the site before the meter or service is turned on. Section 5 says the assembly is tested by an SCDES-approved tester when it is installed and before the system is placed in service.

Anderson’s new-customers section says all new customers for a device first contact Electric City’s Water Operations Department and supply specific information on the proposed business, industry, irrigation, or dedicated fire line. The device has to meet the policy, based on the hazard type in Table 1. New construction needs a set of plans for each structure showing the meter location, the service size, the type of device including make and model, the size, and the location. The policy says the only exemptions to those new-construction requirements are single-family residential customers and in-ground irrigation systems for residential and commercial customers. The irrigation section still has its own device and test. The installer, contractor, or owner meets an Electric City representative for an inspection before water is turned on. Who does that inspection, and the tester’s three days after service is on, are on Backflow preventer installation.

Greenville Water section 2-1 says the utility evaluates new and existing service connections to determine whether an assembly is required. Section 2-4 says the customer should contact the Cross Connection Control Department before buying or installing an assembly. The number in the manual’s introduction is (864) 241-6100. The public page lists the main number 864-241-6000. The site inspection before the meter is turned on is on the installation page.

Who may test it

In R.61-58, a General Tester has finished an approved course, has a test kit, and tests assemblies for the general public. A Limited Tester has the same course qualifications and tests only assemblies the employer owns. A Limited Tester does not provide testing to the general public. An Inspector Tester works for a public water system and does not sell testing to the public. General vs Limited is the full set, including the Manufacturer’s Agent.

A business that hires someone is hiring a General Tester, unless the utility’s own sentence adds a limit. County pages on this site list General Testers from the SCDES report printed July 9, 2026. They do not list Limited Testers.

Two of the manuals add a local sentence:

  • Spartanburg Water section 5 describes an approved tester as an independent contractor certified by SCDES to test assemblies for Spartanburg Water customers, and says a report that is incomplete or illegible will be rejected. A Limited Tester employed by the business is not described there as that independent contractor. Confirm with the contact above before an employee’s card is used for the due date.
  • Anderson’s appendix says a certified tester must be in good standing with Electric City Utilities and with SC DHEC, which is the name the policy still prints. The commercial, industrial, and fire-line heading repeats “in good standing with Electric City Utilities.” The policy does not define that phrase. Confirm with the coordinator at (864) 231-5230.

More than one assembly on the same property

Spartanburg Water’s “each service line” sentence means a property with more than one service can have more than one assembly, and section 10.2’s annual test applies to the approved assemblies, excluding low-hazard residential lawn irrigation. A dedicated fire line is its own assembly on Fire-line backflow. A lawn system is its own case on Irrigation backflow testing.

Anderson prints the 12-month commercial and industrial test, the 12-month dedicated fire line, and the 12-month commercial in-ground irrigation test as separate headings. A passing report on one of them is not a report on the others.

Greenville Water’s introduction names commercial, industrial, irrigation (as noted), and private fire protection as customers who install, maintain, and test the assembly on the service. Section 7 says existing backflow prevention assemblies are tested at least once a year. The letter can name more than one device. Each named assembly follows the date on that letter.

The report

The tester submits the written report. How to read your notice walks through the public forms Greenville Water, Spartanburg Water, and Anderson publish.

  • Greenville Water: certified testers upload results in the portal. A tester new to that utility emails a picture of the certification to bfp@greenvillewater.com. Both instructions are on the backflow page. The day counts and the non-compliance fee are on Greenville Water.
  • Spartanburg Water section 10.2: the customer is responsible for the test by the due date and for the tester transmitting a report that shows compliance within 7 days of the test. The notice tiers are on Spartanburg Water.
  • Anderson: the tester sends the form to the Cross Connection Control Coordinator. The 10-day and 90-day sentences are on Anderson, Pickens, and Oconee.

After a repair of any kind, section (7)(c) says the assembly is tested immediately. What each manual requires when a result does not pass is on Failed backflow test. Who arranges the repair is on Backflow preventer repair.

How long the test takes

R.61-58.7(F), the SCDES program page, Greenville Water’s backflow page and November 10, 2025 manual, Spartanburg Water’s commercial page and June 4, 2026 manual, and Anderson’s September 2008 policy require the test and the written report. They do not print a number of minutes for the visit. Ask the tester when the appointment is scheduled.

Greenville Water section 5-4.6 and Spartanburg Water section 9.3 tell a customer who cannot shut the service off to test or repair the assembly to install an equal assembly in parallel, or a separate parallel service line with its own protection. Anderson’s installation section does not allow a branch, tap, tee, wye, or bypass between the meter and the device. Those sentences are also on Backflow preventer repair. The detector bypass on a fire line, and Powdersville Water’s parallel-installation section, are on Bypass and parallel assemblies.

This site does not publish a price for a business test. The cost guide keeps a third-party range, labeled as that range, separate from any utility fee.

If the utility is not one of these three

Greer CPW’s commercial and industrial sentences are on Greer CPW. Seneca Light & Water’s are on Seneca Light & Water. Easley Combined Utilities’ annual test of a double check is on Easley Combined Utilities. This page does not add a business rule for a utility whose document is not cited here. Section (7) still applies to a testable assembly. The device, the date, and the place the report goes are on that utility’s notice.

Finding a tester

Start with the county on the account: Greenville, Spartanburg, Anderson, Pickens, Oconee, Laurens, Cherokee. Confirm the tester’s current SCDES card before you hire. A row on this site is not an appointment.

Official links are on Resources.

Find a Greenville County tester Read the notice