Town of Pendleton backflow testing
Section 50.035 has a certified tester check a backflow prevention device every year, at the owner’s expense. A device that fails is repaired or replaced, and the section sets a compliance date of not more than 30 days after the test.
Sources checked November 8, 2026.
The Town of Pendleton’s drinking-water system is not Anderson Electric City. Electric City’s 10-day form, 90-day return, and 20-business-day repair line do not transfer to a Pendleton account. Powdersville Water is a different system. Use the name on the water bill.
The SCDES drinking-water record for Pendleton Town of, SC0410006, lists the principal county as Anderson and the primary-source code as SWP. The status is A. The activity date on that record is 06-01-1977. That date is the record. It is not the adoption date of the ordinance below. The purchases table lists Anderson Regional Joint Water System, SC0420011, as the seller. A purchase row is the seller. It is not a backflow rule for a Pendleton account.
The town’s 2025 Annual Drinking Water Quality Report, developed May 5th, 2026, prints System # 0410006. It says the water source is Anderson Regional Joint Water Systems, Hartwell Lake Filter Plant, supplied by surface water from the U.S. Army Corps of Engineers’ Hartwell Lake Reservoir. Questions about that report go to (864) 646-9409. The report does not use the word backflow, and it does not use the words cross connection.
Who the pages name
The government page prints 310 Greenville St, Pendleton, SC 29670, telephone 864-646-9409, and info@townofpendleton.org. The Ordinances item in that menu redirects to the code library American Legal hosts for the town. The sentences below are that code.
The SCDES record prints an owner telephone 864-646-9409 at 600 E Queen St, Attn: James Ford, Pendleton, SC 29670. The emails on that owner row are WATERDEPT@TOWNOFPENDLETON.ORG and TOPHERLIVERIGHT1@GMAIL.COM. It prints David Gailey with the job title OPERATOR, and Chris Liveright with no job title on that row. The administrative-contact row prints James Ford at 310 Greenville St, Pendleton, SC 29670-1419, telephone 864-646-9409, with jamesf@townofpendleton.org and WATERDEPT@TOWNOFPENDLETON.ORG. Those rows are the drinking-water record. They are not a filing instruction for a test report. Section 50.035 says the certified tester submits a copy to the Director. It does not print an email address.
The utility billing page says, “If you are a Sandy Springs Water customer, only the sewer rate apply to you.” The same page prints Sandy Springs Water at 864-646-7729 in the irrigation paragraph. That sentence is the billing page. A Pendleton sewer charge is not, by itself, proof that the drinking water is this system. Section 50.035 is the town water ordinance.
Section 50.035
Section 50.035 is headed “CROSS-CONNECTION CONTROL/ BACKFLOW PREVENTION.” The history line is Ord. 11-01, passed 1-3-11, amended by Ord. 19-04, passed 5-6-19, Ord. 22-07, passed 5-2-22, and Ord. 23-06, passed 4-4-23.
The authority sentence says the town adopts the program in accordance with the State Safe Drinking Water Act, 1976 Code of Laws of South Carolina, Section 44-55-10 et seq., and then prints the word “add” before “the South Carolina Primary Drinking Water Regulations promulgated by the S. C. DHEC (Regulation 61-58).” The code still names DHEC. Current tester cards are issued by the South Carolina Department of Environmental Services. What is backflow testing is the state rule for a testable assembly. Confirm with the town that the card is one it will accept.
The section defines the Director as the Director of the Water Supply System for the Town of Pendleton, including personnel authorized to act on behalf of the Director. The town designates that individual or position. The section does not print a person’s name in the definition. The Director enforces the program and keeps the records. The user allows the property to be inspected and follows this chapter and DHEC regulations.
If the Director requires containment, the user is responsible for water quality beyond the outlet end of the containment device and implements internal protection for each offending fixture, “for the purpose of protecting the health of his or her employees as well as the safety/portability of his or her product.” “Portability” is the word the section prints.
Section 50.031 says users required to provide cross-connection control or backflow prevention devices shall comply with section 50.035. It does not name the assembly.
Devices the section names
The backflow-preventer definition lists an air gap, a reduced pressure backflow preventer, a double check valve assembly, a pressure vacuum breaker, an atmospheric vacuum breaker, a hose bib vacuum breaker, a residential dual check, and a double or dual check with an intermediate atmospheric vent. What is a backflow preventer is how the state rule and the other published manuals name those devices. The notice names the one on the account.
The section’s own marks:
- An air gap is at least twice the diameter of the supply-side pipe, and never less than one inch. The section approves it for a high hazard. Air gap separation is the inch floor in the other published manuals. Pendleton’s floor is the one-inch sentence in this definition.
- A reduced pressure backflow preventer is approved for a high hazard. It may never be installed where flooding is possible, or where the relief valve can be submerged. RPZ testing is the annual test of that assembly on other systems. It is not a test-procedure sheet in this section.
- A double check valve assembly is approved for a low hazard. Double check versus reduced pressure is the difference those other manuals draw. This section does not print their psi bands.
- A pressure vacuum breaker is approved only against back-siphonage, where the section says “low (to intermediate)” hazards exist. The parentheses are in the definition. The section does not print a 12-inch height. Pressure vacuum breaker is that height in the state rule. It is not a sentence in section 50.035.
- A residential dual check has no shut-off valves and no test cocks. The section approves it for a low hazard and says it is normally a containment device at or in the meter box. Residential backflow testing is the house-service case on other systems.
- An atmospheric vacuum breaker and a hose bib vacuum breaker are approved where only back-siphonage is being addressed. The hose bib definition says it is normally a low hazard. The atmospheric vacuum breaker definition says low and intermediate hazards. A double or dual check with an intermediate atmospheric vent is described as available in small sizes through 3/4 inch, with no test cocks or gate valves, usually for internal protection, and approved for low to intermediate hazards.
The section defines an intermediate hazard. The hazard subsection then says the town classifies threats as “high” or “low.” It does not print a third installation category in that subsection. It says the device has to be consistent with DHEC regulations and the program. It does not name a restaurant, a dental office, or a car wash. High-hazard commercial is how other manuals sort a shop. It is not this section.
Existing accounts and new services
For existing users, the Director surveys all existing nonresidential customers, using billing records, telephone calls, interviews, and inspections, and decides which facilities need a device, which device, and how long installation may take. A newly installed reduced pressure backflow preventer or double check valve assembly required on an existing facility is tested by a certified tester upon installation and once a year after that. The section says a firm but reasonable time period is established by the Director for that installation and testing. It does not print a number of days for that period.
The Director does not allow an existing cross connection to remain unless an approved backflow preventer matches the degree of hazard. The Director decides whether the device goes at the meter or inside the facility near the connection. The owner meets the compliance schedules and is responsible for all fees and required device testing. The section does not print a dollar amount for those fees.
For a new user, the Director uses an on-site evaluation, an inspection, interviews, and a plan review. Where increased hazards do not call for stronger protection, the minimum is a residential dual check. A newly installed double check valve assembly or reduced pressure backflow preventer is tested by a certified tester before the Director issues final approval of occupancy.
The owner notifies the Director of any existing, proposed, or modified cross connection the owner knows about and the Director has not found. If the Director determines that a serious threat to the public health exists, water service may be terminated immediately and stay off until the Director determines the threat no longer exists. That sentence does not print a dollar amount or a number of days.
The annual test
The testing subsection says the Director requires annual testing by a certified tester of all backflow prevention devices. Testing is at the owner’s expense. The Director may require more frequent testing based on the age and condition of the device, a history of test failures, or the degree of hazard. The section does not print a dollar amount for that test. It does not print a day count for a reminder letter. How to read your notice walks through the blank forms other Upstate utilities publish. Section 50.035 does not include one. Use the form or the letter the town sends.
A certified tester, in this section, is a person holding an up-to-date backflow prevention device tester certification card issued by DHEC. The section does not name a General Tester or a Limited Tester. General vs Limited is the state card.
The tester furnishes the owner a written report and submits a copy to the Director. The town keeps those reports for five years. The section does not print an email address, a portal, or a blank form. On November 8, 2026 the public works page linked new utility service, billing, waste and recycling, the wastewater plant, 811, street-light outages, and curbside recycling. It did not link a backflow test form. The new-service page linked from it did not use the word backflow.
Each newly installed device is tested after installation and before the owner uses it, then annually unless the Director requires a shorter interval. The section says “all backflow prevention devices.” It does not print the low-hazard residential irrigation exclusion in R.61-58.7(F). Irrigation backflow testing is that state split and the schedules other manuals print. It is not a five-year or three-year line in section 50.035.
Section 50.024 says the town will install, when feasible, a separate meter for water that does not go through the sewer, and that the user is charged for water used, with no sewer charge, plus a minimum monthly customer base charge. Fees are the charges the town publishes from time to time. The section does not name an assembly, and it does not print a test interval. Its history line begins with Ord. 14-09, passed 12-1-14. It is not the history line on section 50.035.
The section does not state how long the field test takes.
A failed test
Any backflow prevention device that fails during a test must be repaired or replaced at the owner’s expense, then retested at the owner’s expense. A high-hazard cross connection is not left unprotected because a device malfunctions. The section sets a compliance date of not more than 30 days after the test date for successful repair, replacement, and testing of the device or devices in question. That date is this section. It is not the 20 business days in Electric City’s policy. Failed backflow test is that other window. The cost guide is a third-party range for a hired test. It is not a price in section 50.035.
Dollar amounts that are not a test fee
Section 50.035(J)(1) says a connection to the town’s water supply without the town’s approval is unlawful. Each day the connection exists before approval is a separate offense, punishable by a fine of up to $1,000 per day. That $1,000 is this offense. It is not a price for a tester the customer hires, and it is not printed as a test fee.
Division (J)(2) says a person in violation of the chapter, or of the regulations that establish the program, is served with written notice of the violation and given a reasonable time limit to correct it. The section does not print a number of days for that “reasonable” limit. Failure to correct within the time the notice states is unlawful and is subject to the penalties in (J)(1).
The billing page’s rate chart is effective July 1, 2025. It prints water and sewer charges, a $0.75 DHEC line, and garbage pickup. It also prints a non-refundable connection fee of $20.00 for a new inside water user and $30.00 for a new outside water user. None of those amounts is stated as a backflow test fee. The page does not use the word backflow.
Section 50.074A is a different device. It applies to a user of the Pendleton sanitary sewer system whose private sewer line is below or near the collection line, has previously back flowed or surcharged, or is, after study and determination by the Pendleton Water Department, in danger of a backflow or surcharge during periods of heavy rain. New residential construction is included when it is below or near the collection line, or when it is in that heavy-rain case. The section prints “back flowed” as two words. It does not put new construction into the “previously back flowed” case. After written notice, which may be mailed to the occupant, the user installs within 30 days, at the user’s expense, a town-approved swing check backflow preventer fixture. The section spells the later word “preventor.” Failure to install it within 60 days thereafter is a violation. The fine is not more than $500, or imprisonment of no more than 30 days, and each day is a separate violation. That $500, those day counts, and that swing check are section 50.074A. They are not the annual drinking-water test in section 50.035. The history line on 50.074A begins with Ord. 19-04, passed 5-6-19.
Records and a tester
The Director keeps survey and inspection files, including the owner’s name, address, phone number, and the location of a device if one is present; copies of the test reports; the most current list of DHEC-approved devices; and a current list of certified testers. The records are open for inspection during normal business hours. The section does not say that list is the SCDES report. This site does not copy a tester list from the Town of Pendleton.
Anderson County testers are General Testers from the SCDES report dated July 9, 2026. A row here is not an appointment. Confirm the card is still current, and confirm with the town that the tester’s category is one it will accept. An Anderson County address can be on Electric City, on Powdersville Water, or on this system. Use the name on the bill.
Official links are on Resources.
Anderson County testers Pendleton section 50.035
Sources checked November 8, 2026: the Town of Pendleton government page, including 310 Greenville St, 864-646-9409, info@townofpendleton.org, and the Ordinances link, which redirected to codelibrary.amlegal.com/codes/pendleton/latest/overview; section 50.035 at that code library, including the word “add,” the spelling “portability,” the device list, the high-or-low classification, the nonresidential survey, the residential-dual-check minimum, the annual test of all backflow prevention devices, the five-year report file, the 30-day compliance date, and the fine of up to $1,000 per day, with history Ord. 11-01, passed 1-3-11, through Ord. 23-06, passed 4-4-23; section 50.031; section 50.024, including the separate meter and the absence of an assembly or a test interval, history beginning Ord. 14-09, passed 12-1-14; section 50.074A, including the swing check, the spelling “preventor,” the 30-day and 60-day lines, and the fine of not more than $500, history beginning Ord. 19-04, passed 5-6-19; the public-works page and the new-utility-service page linked from it, which did not use the word backflow and did not link a test form; the utility billing page, including the Sandy Springs sentence, 864-646-7729, the rate chart effective July 1, 2025, the $0.75 DHEC line, and the $20.00 and $30.00 connection fees; the 2025 Annual Drinking Water Quality Report PDF on townofpendleton.org, developed May 5th, 2026, including System # 0410006, the Hartwell Lake Filter Plant sentence, (864) 646-9409, and the absence of the word backflow; and the SCDES drinking-water record for Pendleton Town of, SC0410006, including the principal county, the SWP code, status A, the activity date 06-01-1977, the Queen Street owner row, the two owner emails, the operator job title, the Greenville Street administrative-contact row, and the purchases table listing Anderson Regional Joint Water System as the seller. Section 50.035 does not print a test fee.