Restaurant backflow requirements in Upstate SC
The state cross-connection rule does not name a restaurant. Six published Upstate files do, and they do not assign one assembly to every restaurant. The letter on the account is the device.
Sources checked November 14, 2026.
If this page and the letter on the account disagree, follow the letter. What is backflow testing is the state test. Double check versus reduced pressure is the hazard split in the regulation and in the Greenville Water, Spartanburg Water, and Anderson manuals. Backflow assembly testing is who those three manuals count as a business account. A restaurant on another system uses that utility’s notice.
The state rule does not name a restaurant
R.61-58.7(F) sorts a cross connection by hazard. Section (2) calls a low hazard a connection to another water source that is not hazardous to health and is not cross-connected inside its own system with a potentially dangerous substance. The minimum it names there is an approved double check valve assembly or a pressure vacuum breaker, except for the residential lawn policy in section (3). Section (4) calls a high hazard a connection to a service or other water system that has or may have any material dangerous to health. The protection it names is an air gap or an approved reduced pressure principle assembly.
A text reading of section (F) on November 14, 2026 did not contain the word restaurant. The section does not print a commercial-kitchen rule, a bar rule, or a day count that applies only to a food-service account. The SCDES program page describes the cross-connection program and the tester course. The program text on that page does not name a restaurant. The retrieved page’s site menu includes a link titled “Don’t Waste Food SC: Restaurants & Hospitality.” That link is not a backflow rule.
Where the word appears
| Source | Restaurant line | Assembly that line names |
|---|---|---|
| R.61-58.7(F) | Does not use the word. | By hazard, in sections (2) and (4). No restaurant row. |
| Greenville Water, November 10, 2025 manual, and the backflow page | Does not use the word. | Section 5-1 assigns an assembly by hazard category. It does not name a restaurant. |
| Spartanburg Water, manual revised June 4, 2026 | Does not use the word. | Sections 7 and 9.1 assign an assembly by hazard. Section 7’s examples do not include a restaurant. |
| Anderson Electric City, September 2008 policy, Table 1 | One low-hazard line: restaurants, commercial food preparation facilities, and bars. | The coordinator chooses. A low hazard may use a double check valve assembly or one of the high-hazard devices. |
| Greer CPW, plan amended April 2025, section 5.2 | Restaurants are on the common low-hazard list. The list says “include but not limited to.” | A double check valve assembly, ASSE 1015, for the low-hazard category, subject to the on-site adjustment in that section. |
| Seneca Light & Water, manual revised October 2021 | Restaurants are one use on the double-check bullet. The public backflow page does not use the word. | That bullet says a double check valve assembly is required on those uses. The supervisor still names the device. |
| Laurens County Water and Sewer Commission backflow page | Restaurants are one example of a low hazard. | An approved double check valve assembly for a low hazard that is not in the residential dual-check class. The commission can reclassify a business. |
| City of Pickens public-works page | Restaurants are on the list of common places that require a device. | The list does not name an assembly and does not mark high or low. |
| City of Clemson water page and backflow flyer | Restaurants are one example of a use that could contaminate drinking water. The list says “includes, but is not limited to.” | The pages do not name a double check or a reduced pressure assembly for that list. |
A dental office is a different account from the restaurant line. How the files that name one classify it is on Dental office backflow. A car wash sits on other rows in the same files. How those rows classify it is on Car wash backflow. High-hazard commercial is the shop page already on this site.
Anderson’s table
Table 1 of the September 2008 Cross Connection Control Policy is a list of typical service connections and the hazard level the policy associates with each use. The policy says the list is not complete, that it is a guide for Electric City personnel, and that every service is evaluated on its own. A footnote says the hazard tables are based on an American Water Works Association standard.
The low-hazard line reads “Restaurants, Commercial Food Preparation Facilities, and Bars.” It is one line. The policy does not split a restaurant from a bar or from a commercial food-preparation facility inside that line.
The coordinator evaluates each facility and uses Table 1 as a guide. A high hazard requires an air gap, a reduced pressure principal assembly, or a pressure vacuum breaker that is not used where backpressure is expected. A low hazard may use any of those, or a double check valve assembly. The policy encourages an air gap for both when a physical separation is practical. The table’s low-hazard mark is the guide. It is not a sentence that every restaurant in the city receives a double check. Deadlines for the test form are on Anderson, Pickens, and Oconee. Anderson County testers are General Testers from the July 9, 2026 SCDES list.
Greer CPW
Section 5.2 of the cross-connection control plan amended April 2025 says a reduced pressure principle assembly (ASSE 1013) is used for a high hazard, and a double check valve assembly (ASSE 1015) is used for a low hazard. Common low-hazard facilities “include but not limited to” a list that begins with restaurants, office buildings, and banks. Common high-hazard facilities on the same page include food and beverage plants. A food or beverage plant is a different bullet from a restaurant.
The same section says the containment requirements for the three hazard categories may be adjusted based on the internal plumbing found at the on-site inspection. Greer CPW is the rest of that plan, including the ten-day report on a new assembly and the same-day report after a failure.
Appendix D is a partial list of typical facility types that require service-line protection. It says other facilities not on the list may still be required to install that protection, at the authority’s discretion. The appendix does not name a restaurant. Item 14 is “Food or beverage processing plants.” That item does not mark high or low. The restaurant classification is section 5.2, not Appendix D.
The test report in Appendix A has a blank, “Define Hazard,” with examples in parentheses: beauty shop, restaurant, irrigation, car lot, medical facility, and so on. That blank is a place to write the hazard for the assembly being tested. It is not the section 5.2 list.
Seneca Light & Water
The backflow prevention page says the Cross-Connection Control Supervisor will notify the customer which device in the procedure manual best protects the system. A text reading of that page on November 14, 2026 did not contain the word restaurant.
The manual revised October 2021 puts restaurants on the double check valve assembly bullet, together with other uses named in the same bullet. The bullet says that assembly is required on those uses and that it requires annual testing by a certified tester. The next bullet says every commercial customer applying for water service after January 1, 2009 has a double check valve assembly, unless the supervisor waives it as unnecessary. The reduced-pressure bullet names other facility types and does not name a restaurant. The selection section says the supervisor names the device for the service. Seneca Light & Water is the installation section and the initial test that manual describes. Oconee County testers are the General Testers in that county on the July 9, 2026 list.
Laurens County Water and Sewer Commission
The backflow and cross-connection page prints three classifications. Low hazard is a connection that is not cross-connected with a potentially dangerous substance. The examples printed there are fire protection, trailer parks, churches, restaurants, and commercial irrigation systems. High hazard is a connection that has or may have any material in the water dangerous to health. The examples printed there are fire protection with chemical addition, irrigation systems with chemical addition, and industries with potentially dangerous cross connections. A restaurant is not in that high-hazard sentence.
The low-hazard residential class is a single residence, or a business with only residential-type plumbing. The page says a business may be placed in that class at the commission’s discretion and can be reclassified on notice. The restaurant example is in the low-hazard list. This page does not decide which class a particular restaurant is in.
Every new low-hazard residential connection is a residential dual check. Every other low-hazard connection is an approved double check valve assembly. Every high-hazard connection is an air gap or an approved reduced pressure principle backflow preventer. The 60-day notice and the 15-day clocks are on Laurens. They apply to a testable device on that commission’s system. They are not a separate restaurant schedule. The City of Clinton is a different system in the county. Clinton’s water page, read the same day, does not use the word restaurant.
Laurens County testers are General Testers from the July 9, 2026 list.
City of Pickens
The public-works page prints “A List of common places that require a backflow prevention devices,” and restaurants are on that list. The list does not mark any place high or low, and it does not name the assembly. The same section says routine testing follows R.61-58 and that results go to the public-works post office box printed on the page. It does not print a due date. City of Pickens is the filing address, the two test forms, and the city check valve at the connection. Pickens County testers are the General Testers in that county.
City of Clemson
The water page says backflow and cross-connection could contaminate drinking water through pollutants, contaminants, and system or plumbing hazards. The examples are fire protection systems, irrigation systems, gasoline refineries and stations, restaurants, hospitals, and manufacturers. The sentence says the list includes, but is not limited to, those uses. It does not mark any of them high or low.
The same section says two kinds of assemblies are required for all business customers that present a potential hazard. External assemblies protect the water system from a cross connection with the water on the customer’s premises. Internal assemblies protect the customer from potentially hazardous cross connections within the customer’s system. The page does not name a double check or a reduced pressure assembly in that pair. It says the utilities department checks the plans of each new business.
The backflow flyer repeats that example list, including restaurants. It says commercial accounts generally require the business to have backflow prevention. It does not name the assembly. The flyer’s three-year sentence is homeowner irrigation on an underground system, tested before service and every three years after. That sentence is not the restaurant example. City of Clemson is the water page, both flyers, and the code section already summarized there.
Files that do not use the word
A text reading on November 14, 2026 did not contain the word restaurant in any of these files. Silence in the file is not a finding that the account has no assembly. Use the notice.
- Greenville Water’s backflow page and the manual created November 10, 2025. Section 5-1 says a reduced pressure principle assembly or an air gap is used for a high hazard, and a double check valve assembly or a dual check is used for a low hazard. The section does not name a facility type. Greenville Water is the notice and the portal. Greenville County testers are the General Testers in that county.
- Spartanburg Water’s manual revised June 4, 2026. Section 7(a) names sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries, and plating plants as examples of premises protected by an air gap or a reduced-pressure principle assembly. A restaurant is not in that list. Section 7(b) is water or a substance that would be objectionable but not hazardous to health, protected by an approved double-check valve assembly. It does not name a facility. Section 9.1 repeats the hazard split and adds a pressure vacuum breaker for a back-siphonage hazard on the high-hazard side. A retrieval of the older path
/ccc-and-backflowreturned the commercial and industrial page, and that page’s text did not contain the word restaurant. Spartanburg Water is the manual’s notice language. Spartanburg County testers are the General Testers in that county. - Easley Combined Utilities’ water page and the standard specifications with a March 2025 cover. The water page’s backflow sentences are the definition of backflow and the residential lawn dual-check line. Easley Combined Utilities is that page, the test form, and the specifications.
- Powdersville Water’s cross-connection policy, revised September 2024. Powdersville Water is the 90-day letter and the irrigation classes in that file.
- Blue Ridge Rural Water’s company policies PDF. The file-properties title is “2020 Company Policies,” and the modification stamp is July 30, 2026. Blue Ridge Rural Water is section 14.
- Gaffney Board of Public Works’ water construction specifications. Gaffney is the test form and those specifications.
- City of Clinton’s water distribution page. Clinton is the 2026 test form.
What to do with the letter
Hire a General Tester, the classification that may test for the public. County pages on this site copy that classification from the SCDES report printed July 9, 2026. Confirm the current card before you hire. A row on this site is not an appointment.
The letter names the assembly, the date, and where the report goes. How to read your notice is the reading for the forms Greenville Water, Spartanburg Water, and Anderson publish. A failed result is on Failed backflow test. A repair, and the retest after it, is on Backflow preventer repair.
The regulation does not set a price for the device or the test. None of the restaurant lines above print a test fee. The cost guide is a third-party range for a test a customer hires. It is not a restaurant price and it is not a utility fee. Official links are on Resources.
Assembly testing for businesses Greenville County testers
Sources checked November 14, 2026: R.61-58 on des.sc.gov, section 58.7(F); the SCDES program page; Greenville Water’s backflow page and the manual created November 10, 2025, including section 5-1; Spartanburg Water’s manual revised June 4, 2026, including sections 7 and 9.1, and the commercial and industrial page returned by the older backflow path; Anderson Electric City’s September 2008 policy, including Table 1 and the device section that follows it; Greer CPW’s cross-connection control plan amended April 2025, including section 5.2, the adjustment sentence, Appendix A’s test form, and Appendix D; Seneca Light & Water’s backflow page and the manual revised October 2021, including the double-check and reduced-pressure bullets; Laurens County Water and Sewer Commission’s backflow page; the City of Clinton water distribution page; the City of Pickens public-works page; the City of Clemson water page and the backflow flyer; Easley Combined Utilities’ water page and the specifications with a March 2025 cover; Powdersville Water’s September 2024 cross-connection policy; Blue Ridge Rural Water’s company policies PDF; and Gaffney Board of Public Works’ water construction specifications.