Pressure vacuum breaker: the 12-inch rule
A pressure vacuum breaker is a testable assembly for backsiphonage. Where it is used, South Carolina’s drinking-water rule puts it at least 12 inches above the highest downstream piping and keeps it off a line that can push back. The letter from the utility names the assembly on the account.
Sources checked October 26, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is how to tell this assembly from a double check, a reduced pressure assembly, and a residential dual check. Double check versus reduced pressure is the hazard split those two assemblies follow. Lawn schedules are on Irrigation backflow testing. This page is the pressure vacuum breaker: the 12-inch height, the backsiphonage limit, and the order on the 2025 state sheets.
What the assembly is
Spartanburg Water’s manual revised June 4, 2026 (PDF created June 5, 2026) defines a pressure vacuum breaker as one spring-loaded check valve, an air-inlet valve, ball-type shutoff valves at each end, and two test cocks. That definition says the assembly is approved only for back-siphonage, that it is installed 12 inches above any downstream piping, outlets, or flood level rim, and that Spartanburg Water approves it for high-hazard cross connections.
Anderson’s September 2008 policy defines it as an independently operating, internally loaded check valve and an independently operating loaded air-inlet valve on the discharge side of the check, with resilient-seated test cocks and tightly closing resilient-seated shutoff valves at each end. The definition says the assembly is designed to operate under pressure for prolonged periods of time to prevent backsiphonage, and that it is not designed to withstand any amount of back pressure.
Greenville Water’s manual (PDF created November 10, 2025) lists an air gap, a reduced pressure principle assembly, a double check valve assembly, a double detector check, and a residential dual check. The definitions and section 5-1, read on October 26, 2026, do not name a pressure vacuum breaker. Section 5-1 says a high hazard uses a reduced pressure principle assembly or an air gap, and a low hazard uses a double check valve assembly or a dual check. Questions in that manual go to the Cross Connection Control Department at (864) 241-6100. If a Greenville Water letter names a pressure vacuum breaker, follow the letter.
SCDES’s sample test form labels a pressure vacuum breaker as PVB, ASSE #1020. The same form has a separate label, SRVB, ASSE #1056, for a spill-resistant vacuum breaker. The results block for those assemblies has a check valve and an air inlet. The form says many jurisdictions require their own form.
The 12-inch rule
Section (9) of R.61-58.7(F) is the state sentence. Where a pressure vacuum breaker is used, it is installed at a minimum of twelve inches above the highest downstream piping and is not subject to backpressure.
The January 1, 2026 approved-assembly list groups pressure vacuum breakers with spill-resistant pressure vacuum breakers. That section says they are approved for protecting the potable water system from back siphonage only when a health hazard or a non-health hazard is involved, that the PVB/SVB is not designed for backpressure, and that the PVB/SVB must be installed 12 inches above any downstream plumbing. The filename on the state site spells “equipment” the way the URL shows. Note 9 on that list applies to a reduced pressure principle assembly, a pressure vacuum breaker, or a double check valve assembly: resilient-seated ball valves or resilient-wedged gate valves. Butterfly valves on that note are acceptable when the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research has approved them.
The four height sentences are not the same sentence:
| Source | Height | Backpressure |
|---|---|---|
| R.61-58.7(F)(9) | At least 12 inches above the highest downstream piping. | The assembly shall not be subject to backpressure. |
| January 1, 2026 list | 12 inches above any downstream plumbing. | Not designed for backpressure. Back siphonage only. |
| Spartanburg Water, definition (5) | 12 inches above any downstream piping, outlets, or flood level rim. | Approved only for back-siphonage. |
| Anderson, installation section | Above ground, and at least 12 inches above the highest downstream portion of the customer’s system. | Not designed to withstand any amount of back pressure. Not used where backpressure is expected. |
Anderson adds installation limits the state sentence does not print. The policy says a pressure vacuum breaker is never installed inside a building, and it is not installed in a flood plain or where the air-inlet valve may become submerged. The air-inlet valve stays clear of foreign debris, including shrubbery. The minimum setback for landscaping, with the policy’s examples of trees, flowers, shrubbery, and birdbaths, is 3 feet. On an in-ground irrigation test, the tester checks that no permanent debris, such as a shrub, sits within 1 foot in any direction, and that the device is at least 12 inches above all downstream portions of the customer’s system. The tester documents debris on the form and does not remove it. Electric City follows up. Debris still there 14 days after the test puts the customer at risk of disconnection until the condition is fixed. The policy says applicable reconnection fees apply. It does not print the fee amount in that paragraph. Those irrigation sentences are also on Irrigation backflow testing. Questions in the policy go to the coordinator at (864) 231-5230.
Spartanburg Water section 9.3 is titled for a reduced pressure assembly and a double check. Item 5 in that section says all backflow prevention assemblies are installed in an enclosure or building on the customer’s property, protected from freezing, traffic, and vandalism, and kept accessible for testing. Item 4 points height and side clearance to Appendix B. The file linked above is 18 pages and ends on an attachments cover. It prints the 12-inch sentence in definition (5) and does not include that appendix. Where definition (5) and section 9.3 do not read the same way, use the notice. Questions on the commercial and industrial page go to Matthew Jamison, Field Operations Manager, at (864) 598-7213 or ccc@spartanburgwater.org.
Which hazard the documents assign
| Source | Where a pressure vacuum breaker is named |
|---|---|
| R.61-58.7(F)(2) | Minimum on a low hazard, together with an approved double check valve assembly, except the residential lawn policy in section (3). |
| R.61-58.7(F)(4) | A high hazard is an air gap or an approved reduced pressure principle assembly. This paragraph does not name a pressure vacuum breaker. |
| Spartanburg Water, section 9.1 | High hazard, for back-siphonage hazards only, together with a reduced pressure principle assembly or an air gap. The low-hazard sentence names a double check or a double detector check. |
| Anderson, device rule | High hazard, together with an air gap or a reduced pressure assembly, and not where backpressure is expected. A low hazard may use those devices or a double check. |
| Greenville Water, section 5-1 | The section does not name a pressure vacuum breaker. |
Section (3) is the residential lawn exception to the low-hazard minimum. A low-hazard residential system follows the utility’s written policy, which may use a residential dual check. A residential lawn system that adds chemicals, or that is also connected to a water source other than an approved public system, is a high hazard under section (3)(b) and follows section (4). Those lawn schedules are on Irrigation backflow testing.
The 2025 recertification study guide says a pressure vacuum breaker is designed for a health or high-hazard cross connection under backsiphonage only, and that it is not approved or designed for backpressure. The same paragraph says the assembly works under continuous pressure, so a shutoff valve may be installed downstream. Section (9) of the regulation does not use the words “continuous pressure.” The study guide is the recertification sheet. The notice is the utility’s choice of assembly. Seneca’s manual says booster pumps shall not be used with a pressure vacuum breaker. The pressure numbers in the state design standard and in the utility fire sections are on Booster pumps and backpressure.
A spill-resistant vacuum breaker, and an atmospheric vacuum breaker
The January 1, 2026 list’s abbreviation for the spill-resistant assembly is SVB. The sample form’s abbreviation is SRVB. The list’s approval paragraph covers “PVB’s & SVB’S” with the same backsiphonage limit and the same 12-inch line. The definition sections of the Greenville Water, Spartanburg Water, and Anderson manuals read for this page do not define a spill-resistant vacuum breaker. If the letter names one, follow the letter.
An atmospheric vacuum breaker is a different part. Anderson’s policy says atmospheric vacuum breakers, barometric loops, a double check with an intermediate atmospheric vent, and hose-bib vacuum breakers are not approved to protect the public distribution system. The policy says they may be used for internal protection, and that an additional device is still required. The study guide calls the atmospheric vacuum breaker non-testable, says it is installed 6 inches above any downstream use or piping, and says no control valves are installed downstream of the outlet, so continuous pressure is not allowed. That 6-inch sentence is the study guide. It is not section (9). Section (7) of the regulation names the assemblies a certified tester tests when they protect the public system: a double check valve assembly, a pressure vacuum breaker, and a reduced pressure principle assembly. An atmospheric vacuum breaker is not in that list.
Who tests it, and how often
Section (7) applies when a pressure vacuum breaker protects the public system from a customer’s service. A certified tester tests it after installation and before the customer uses it. Except for the low-hazard residential irrigation schedule in section (3), each assembly is tested at least once a year. After a repair of any kind, it is tested again immediately. The certified tester who made the test sends the written report to the water system.
The SCDES program page says the recertification wet lab is a double check valve assembly, a pressure vacuum breaker, and a reduced pressure principle assembly, on the tester’s own differential gauge. The gauge rule is on Backflow test kits. The classification that tests for the general public is the General Tester. General vs Limited is how those cards differ.
A customer does not run the field test below. A certified tester does, with the gauge in hand. If the sheet in the tester’s hand and this page disagree, follow the sheet.
The order on the 2025 sheets
The program page links both files. On October 26, 2026 the pressure-vacuum-breaker sheet is the third sheet in each file, and both of those sheets are direction-of-flow sheets.
The three-valve title prints “3-Valve Test Procedure for a Pressure Vacuum Breaker Assembly (PVB)” and “(Direction of Flow).” The five-valve title prints “5 - Valve Test Procedure Pressure Vacuum Breaker(PVB)” and “(Direction of Flow).” Both preparation headings print “PREPERATION.” This page keeps that spelling. Use the sheet that matches the gauge. Do not move a step from one sheet onto the other.
The study guide matches the hose order both sheets print. The high hose on test cock number 2 is the air-inlet test, which each sheet calls test number 1. The high hose on test cock number 1 is the check-valve test, which each sheet calls test number 2. The study guide says that if either shutoff valve is leaking, water leaves the assembly and the gauge drops to zero.
Three-valve sheet
Preparation:
- Notify the customer.
- Inspect the area for safety.
- Determine if the assembly is approved and appropriate. The sheet prints “Approved & Appropriate.”
- Record the make, model number, serial number, and static working pressure on the test report form.
- Close all valves on the test gauge.
- Remove the canopy and clean debris around the air inlet.
- Flush test cock number 1.
- Flush test cock number 2.
- Turn off shutoff valve number 2.
The sheet prints a note: attach the high hose only on the gauge.
Air-inlet opening, test number 1:
- Attach the high hose to test cock number 2.
- Slowly open test cock number 2.
- Open the high-side control valve.
- Open the vent/bypass valve and bleed the air.
- Close the vent/bypass valve.
- Turn off shutoff valve number 1.
- Center the gauge to the assembly.
- Slowly open the vent/bypass valve and observe the reading when the air inlet pops. The sheet says to record the value, and it prints “1.0psid or greater.”
- Close test cock number 2 and remove the hose.
- Turn on shutoff valve number 1.
Check-valve value, test number 2. These lines are in the order the sheet prints them:
- Attach the high-side hose to test cock number 1.
- Slowly open test cock number 1.
- Bleed the air, then close the vent/bypass valve.
- Turn off shutoff valve number 1.
- With the gauge centerline at the elevation of the assembly.
- Slowly open test cock number 2 fully and record the reading when water stops flowing from test cock number 2. The sheet prints “1.0psid or greater.”
- Close both test cocks and remove the hose.
Restore the system:
- Open shutoff valve number 1 first.
- Open shutoff valve number 2.
Five-valve sheet
Preparation:
- Notify the customer.
- Inspect the area for safety.
- Determine if the assembly is approved and appropriate.
- Record the make, model number, serial number, and static working pressure on the test report form.
- Close all valves on the test gauge.
- Remove the low-side hose from the gauge, if it is on the gauge.
- Remove the canopy and clean debris around the air inlet.
- Flush test cock number 1.
- Flush test cock number 2.
- Turn off shutoff valve number 2.
- Open the high-side bleed valve.
Air-inlet opening, test number 1:
- Attach the high hose to test cock number 2.
- Slowly open test cock number 2.
- Close the high-side bleed valve when the air stops.
- Turn off shutoff valve number 1.
- Center the gauge with the assembly.
- Slowly open the high-side bleed valve and observe the reading when the air inlet pops. The sheet prints “1.0psid or better.”
- Close test cock number 2.
- Turn on shutoff valve number 1.
Check-valve value, step number 2:
- Attach the high-side hose to test cock number 1.
- Slowly open test cock number 1.
- Close the high-side bleed valve.
- Turn off shutoff valve number 1.
- Center the gauge with the assembly.
- Slowly open test cock number 2 and record the reading when water stops flowing from test cock number 2. The sheet prints “1.0 psid or greater.”
- Close test cock number 2 and test cock number 1.
- Remove the hose from test cock number 1.
Restore the system:
- Open shutoff valve number 1 first.
- Open shutoff valve number 2.
The three-valve air-inlet block uses a vent/bypass valve. The five-valve air-inlet block uses a high-side bleed valve. The passing lines above are what those two sheets print. They do not print a maximum.
Anderson’s Table 2 is that utility’s minimum. It is not a statewide number from R.61-58.7(F). For a pressure vacuum breaker, Table 2 lists the check at 1.0 psi minimum and 4.0 psi maximum, and the air inlet valve at 1.0 psi maximum and 4.0 psi maximum. The high-hazard heading on that table says the test uses a three-hose or five-hose differential gauge only. A later paragraph says a differential-pressure test or a direction-of-flow test using the differential gauge is acceptable for a pressure vacuum breaker. The 2025 sheets read for this page are direction-of-flow sheets. The tester uses the procedure SCDES and the utility accept for that account. What each manual requires after a result that does not pass is on Failed backflow test.
If the utility is not one of these three
Greer CPW’s published irrigation devices are on Greer CPW. Seneca Light & Water’s published installation notes are on Seneca Light & Water. This page does not add a pressure-vacuum-breaker sentence for a utility whose document is not cited here. Section (9) still applies where a pressure vacuum breaker is used. The device, the date, and the place the report goes are on that utility’s notice.
County lists of General Testers copied from the July 9, 2026 SCDES report start at Greenville County, Spartanburg County, and Anderson County. Confirm the current card before you hire. A row on this site is not an appointment.
This site does not publish a price for this test. The cost guide keeps a third-party range, labeled as that range, separate from any utility fee. Official links are on Resources.
Irrigation backflow testing What a preventer is
Sources checked October 26, 2026: R.61-58 on des.sc.gov, the SCDES program page, the January 1, 2026 approved-assembly list, the SCDES sample test form, the 2025 three-valve and five-valve test-procedure PDFs, the 2025 recertification study guide, Greenville Water’s November 10, 2025 manual, Spartanburg Water’s commercial and industrial page and the manual revised June 4, 2026, and Anderson Electric City’s September 2008 policy.