Powdersville Water backflow testing

The September 2024 policy gives existing customers 90 days after the letter to finish the test. Appendix A prints dollar amounts for a test Powdersville Water performs when the customer does not.

Sources checked November 3, 2026.

The policy the builders and developers page labels Cross-Connection Policy is the September 2024 PDF. The cover line is “Revised September 2024.” A February 4, 2017 article still links a different file, Cross-Connection-Control-Policy-Revised-2024.pdf. That file’s cover line is “Revised March 2024.” The sentences below are from the September file unless the paragraph names the March file. Current copies of the policy are available, the definitions section says, in the Project Coordinating Office at (864) 404-2107.

The about page says Powdersville Water is a special purpose district chartered to serve drinking water to portions of Anderson and Pickens counties. The service area page says the boundaries shown there are not exact and to contact the office about a particular property. The SCDES drinking-water record for Powdersville Water District, SC0420002, lists the principal county as Anderson. Section 2.1 of the policy says the treatment facilities are owned and controlled by other entities, that water is master metered into the system, and that Powdersville Water is a consecutive system. The same SCDES record lists water purchases from Anderson Regional Joint Water System, Greenville Water, and Easley Combined Utilities. Greenville Water deadlines do not transfer to a Powdersville account. Easley Combined Utilities deadlines do not transfer either. Anderson Regional Joint Water System is not Electric City Utilities. Electric City’s clocks are on Anderson, Pickens, and Oconee. If this summary and the letter on the account disagree, follow the letter and the current PDF.

Section 2.1 uses “master metered” for water entering Powdersville Water’s own system, and for the source master meter on its distribution pipes. Anderson’s September 2008 policy uses master-metered system for a customer account, and it calls that account a bulk water system. That customer definition is on Master-metered and bulk water. Powdersville Water’s 90-day letter does not transfer to that Anderson account.

The contact page prints 1719 Circle Road, Powdersville, SC 29642, telephone 864.269.5440, and fax 864.295.1496. It says press 4 for a customer service representative. Its office-hours line prints Monday through Friday, 8:00 AM to 5:00 PM. The office-location block on the same page prints Monday through Thursday, 8:00 AM to 5:00 PM, and Friday, 8:00 AM to 12:00 PM. Both lines are on that page. Use the hours the office confirms for the day you call. Section 10.1 of the policy gives the same telephone number and says Option 4 for a copy of the water-system guidelines.

The 90-day letter

Section 2.3 says customers with an existing backflow prevention device in Powdersville Water’s inventory are notified annually by letter. The customer contacts a certified tester and has the test completed within 90 days of notification. A report that is not back within that 90-day period is noncompliance. The policy says Powdersville Water will then proceed with administrative actions, up to and including immediate discontinuance of water service within a 30-day period.

A new testable assembly is tested upon installation and before the customer uses it. The installer contacts a certified tester, and the successful report has to be received before water service is established. Section 1.4 says the assembly is tested when it is installed, before the system is placed in service, and every year after that, and that testing and repair reports on an approved SCDES form are submitted every 12 months.

Section 2.2 says the customer has certified inspections and operational tests at least once a year, every 12 months, at the water user’s expense. It says SCDES or Powdersville Water may require those inspections more often when the hazard is great enough. A copy of testing and repair reports goes to Powdersville Water. The original stays on site. What is backflow testing is the state rule, R.61-58.7(F). How to read your notice walks through the forms other Upstate utilities publish. Use the letter on the account for the date.

Section 2.3 also says Powdersville Water will randomly retest assemblies from recently returned reports, at its expense. The customer is notified in advance of that retest if service will be interrupted.

Which assembly the policy names

The definitions section describes two degrees of hazard, high and low. Section 2.2 also uses the words “Medium Hazard.” An auxiliary supply that the policy treats as a danger to the system, and premises where material dangerous to health is handled, are high hazard. Protection is an approved air gap or an approved reduced-pressure principle assembly. The examples named there are sewage treatment plants, chemical manufacturing and processing plants, medical facilities, mortuaries, and metal plating operations. A substance that would be objectionable but not hazardous to health is the case section 2.2 calls a medium hazard, protected by an approved double-check valve assembly. Double check versus reduced pressure is the state hazard split. RPZ testing is the reduced-pressure assembly on the other published manuals.

Section 6 says an approved air gap is at least twice the diameter of the supply outlet and never less than one inch. The same one-inch minimum is in the air-gap definition. Air gap separation is where Greenville Water, Spartanburg Water, and Anderson print their own minimums. Anderson’s minimum is not this policy’s. A reduced-pressure principle assembly is not installed where flooding is possible. The introduction’s quotation of the state rule includes pits or vaults below grade that do not have a positive gravity drain to the ground surface. The definition says that assembly is installed above finished grade with positive drainage. A double check valve assembly may be installed below grade.

A pressure vacuum breaker, where the policy says one is provided, is installed a minimum of 12 inches above the highest downstream piping and is not subject to backpressure. Pressure vacuum breaker is the state rule for that height.

Section 2.2 says a residential lawn system with no chemical injection or addition is a low hazard and is protected by a dual check. A customer who adds a testable device on that system bears the maintenance and testing. Chemical addition on a residential system is a high hazard and is protected by a reduced-pressure device. A commercial, non-residential lawn system is a medium hazard and is protected by at least a double check valve assembly. The residential dual-check definition says that device has no shutoff valves and no test cocks, and that Powdersville Water changes those devices on a 10-year rotation at the customer’s water meter for residential irrigation and domestic metering. Section 2.2 says non-testable dual checks are on a 10-year replacement cycle by Powdersville Water for taps with residential lawn irrigation. Residential backflow testing is the homeowner page for other Upstate utilities. Irrigation backflow testing is the state irrigation rule and those other manuals.

Section 5 says a physical separation must be made between any private water supply, including a groundwater well, and the Powdersville Water system. The private wells page, dated February 4, 2017, says the approved policy does not allow interconnection of a private well with the same piping served by one of its taps. It says to call 269-5440, option 4, and that any corrections at the tap will be free of charge. Auxiliary water and private wells is how Spartanburg Water and Anderson word a well. Those sentences are not this policy.

Who pays for the assembly

Section 1.2 says that when Powdersville Water judges an approved assembly is required, it gives a dated notice in writing, and the customer installs that assembly at the customer’s expense. Failure to install, test, and maintain it is grounds for discontinuing service until the requirements are met. Section 1.3 says the same expense rule for the piping beyond the meter.

The February 4, 2017 cross-connection article says that if Powdersville Water has to install a backflow device at the meter, the customer will not bear any of the cost. The February 4, 2017 wells page says corrections at the tap are free of charge. Those two pages and section 1.2 of the September 2024 policy do not use the same words. This summary does not pick one of them for an account. Read the notice on that account.

Section 15 says no backflow prevention device will be installed inside the building without authorization from Powdersville Water, and that devices shall be located at the property line. The sentence points to “section 2.2.3.” Section 2.2 says an approved assembly is installed on the service line at or near the property line. Backflow preventer installation is how the other published manuals describe a new assembly.

The test form

The customer forms page links Backflow Device Test. On November 3, 2026 that page’s heading was Backflow Device Test, and the page loaded a form headed Backflow Device Test Report. The page’s own modified time is July 18, 2023. The form’s blanks that day were:

  • Date, and an email blank
  • Account name or business name, and account address
  • Account number and meter number
  • Device name, model number, serial number, size, and device location
  • Tested by
  • Check No. 1 and Check No. 2, each for the test before repairs and the test after repairs, marked Leaked or Closed Tight, with a differential-pressure line and a repairs-and-new-materials line
  • An air-inlet valve or relief valve, before repairs and after repairs, with an “Opened at (lbs.)” line
  • Shutoff valves marked #1 Gate or Ball and #2 Gate or Ball, each Leaked or Closed Tight, before repairs and after repairs
  • Tester signature, certification number, company name, and company telephone number
  • Category: General, Limited, or Inspector Tester
  • Method of testing, test kit used, and comments

The form does not print a pass or fail line, a due date, a fee, or a Powdersville mailing address for the finished report. The email blank is not labeled as a Powdersville inbox. The policy says reports are submitted to Powdersville Water and does not print an email address for that submission. Ask at the phone on the contact page before you rely on a filing method from another utility. Backflow test kits is what SCDES requires of the gauge. General vs Limited is the state card. The form lists General, Limited, and Inspector Tester. The policy’s introduction quotes the state list of four tester types, which also names a manufacturer’s agent. Confirm the current SCDES card before you hire, and confirm with Powdersville Water that the category on the form is one it will accept.

Appendix A, and the older fee table

Appendix A is headed “Annual Testing (when customer fails to complete).” The test-per-unit line says “Effective January 1, 2025.” It prints $750.00 for a DCVA, RP, or PVB less than 6 inches, and $1,000.00 for a DCVA, RP, or PVB 6 inches or larger. It prints $35.00 to lock or unlock a meter, and $47.00 to lock or unlock a meter after 5 PM. The last line says all fees are subject to change without notice.

Section 3.5 says fees for testing will only be charged by Powdersville Water when the customer has failed to submit a current successful test report after a final notice and discontinuance of water service would impact public health, such as a medical clinic. Section 14.4 says non-compliance fees include service charges to lock and unlock meters when a customer fails to comply with testing, maintenance, and repair, and it points to Appendix A. Those amounts are Powdersville Water’s charges in this policy. They are not a price for a tester the customer hires. The cost guide is a third-party range for that hired test. It is not an Appendix A fee.

The March 2024 file still linked from the 2017 article prints a different test-per-unit table and does not print the “Effective January 1, 2025” line. That table is $300.00 for a DCVA, RP, or PVB less than 8 inches, and $500.00 for 8 inches or larger. Its lock and unlock amounts match the September file, $35.00 and $47.00 after 5 PM. The builders page links the September file. Use the file the current notice cites.

Fire lines

Section 10 says Class 1 and Class 2 fire connections are protected by a double check valve. Class 1, as that section describes it, has no pumps, tanks, or reservoirs, no physical connection from another water supply, no antifreeze or additives, and sprinkler drains discharging to atmosphere, dry wells, or other safe outlets. It says those connections must never cause system pressure to drop below 50 psi. Class 2 may use a fill pipe to a tank that supplies booster pumps, with the same 50 psi floor during filling. The section says violations will be subject to severe fines for every pressure-drop event that leaves a residual below 50 psi. It does not print a dollar amount for that fine. That 50 psi residual is Powdersville Water’s line. The 20, 25, and 30 psi lines in other files are on Booster pumps and backpressure.

Section 10.2 says every new or renovated fire sprinkler system has an FM meter meeting Powdersville Water specifications and an approved double check valve assembly. Installation of that assembly is the owner’s responsibility, and the assembly is installed so it is accessible for testing, maintenance, and inspection. Section 10.4 says the owner maintains the fire sprinkler system from the discharge side of the meter, including the backflow assembly. Section 10.1 says no antifreeze or similar chemicals are allowed in fire sprinkler systems unless Powdersville Water approves them. The introduction quotes the state sentence that a high-hazard fire system, including an antifreeze system, is protected by an air gap or a reduced-pressure principle assembly. Section 10 does not name a substitute assembly for a system it has approved to use antifreeze. Fire-line backflow is the state rule and the other published manuals. Use the notice for the device on that account.

The definitions section says a double detector check assembly cannot be used in new installations. Section 10.1 points to section 02772 of the water-system guidelines for fire-connection details and says to call customer service for a complete copy. The builders page links that guidelines PDF. This page does not restate section 02772. Section 10.2 points to Appendix I of the development policy for the double check valve assembly. This page does not restate that appendix.

When the result fails

Section 2.3 says that if the assembly fails the required test and cannot be repaired immediately, the device must be replaced immediately, tested successfully, and the report submitted promptly. Section 3.4 says that after any repair, overhaul, re-piping, or relocation, the customer has the assembly retested. Failed backflow test is how Greenville Water, Spartanburg Water, and Anderson count the days after a result that does not pass. Those clocks are not this policy’s. Backflow preventer repair is who arranges a repair on those other systems.

Section 14 splits enforcement three ways. An existing customer with no device, where Powdersville Water has determined contaminants are a health hazard, takes immediate corrective action on notification. Where Powdersville Water has determined a potential system hazard, the customer installs an approved assembly or corrects the hazard within 30 days of notification, or water service is terminated. A new customer installs, tests, and reports the device before service is established. A device that does not meet Powdersville Water’s standards is replaced immediately. A malfunctioning device on a low hazard is repaired or replaced within 30 days after notification. A malfunctioning device on a high hazard is repaired or replaced immediately, or water service is discontinued.

Section 14.2 says service will be discontinued if a required assembly is not installed, tested, and maintained. The sentence prints the words “maintained pers schedule.” It also covers a device that has been removed or bypassed, and an unprotected cross connection with inadequate protection at the service connection. Service is not restored until the condition is corrected. A written notice says service will be terminated if the policy is not met. The section says Powdersville Water will not be liable for losses, damages, or claims arising from that termination.

Section 12 says the device owner protects an outdoor assembly from freezing, and that weather damage is the account owner’s responsibility and must be repaired immediately. Freeze protection shall not interfere with inspection, operation, or maintenance.

Section 11 says a customer system closed by a backflow assembly, a pressure reducing valve, or any other checking device needs an approved auxiliary relief valve between the checking device and the water heating equipment. The valve limits thermal expansion to not more than 80 pounds per square inch no-flow pressure at any fixture. The discharge line is not less than 1/4 inch inside diameter. That installation is the owner’s responsibility, and the plumbing beyond the meter is the customer’s, including a residential water heater. How Greenville Water, Spartanburg Water, and Greer CPW word the same subject, including the 150 psi line this section does not print, is on Thermal expansion.

A shutdown during the test

Section 8 says assemblies with test cocks are tested at least once a year. It says testing may require a water shutdown usually lasting five to twenty minutes. Where a facility needs uninterrupted water and a separate meter is not available, the policy requires a parallel installation. During that test, one assembly stays on while the other is tested. Powdersville Water will not accept an unprotected bypass around a backflow preventer. The five-to-twenty-minute sentence is that shutdown. It is not a duration printed in R.61-58.7(F). The state rule does not say how long a field test lasts.

Section 7 is a guide to assembly selection. It says the health hazard governs the final choice. The guide lists a fire sprinkler system at a double check valve assembly and a fire-fighting system that uses toxic liquid foam at a reduced-pressure principle assembly. It lists irrigation with chemical additives at a reduced-pressure principle assembly, and non-residential irrigation at a double check valve assembly. The non-residential row is printed “Irrigations systems (non-residential).” It lists a sewage treatment plant at a reduced-pressure principle assembly and a sewage lift station at a double check valve assembly. The guide is not a device selected for an address.

Finding a tester

Anderson County testers and Pickens County testers are General Testers from the SCDES report dated July 9, 2026. This site does not copy a tester list from Powdersville Water. A row here is not an appointment. Confirm the card is still current, and confirm with the utility that the tester’s category is one it will accept on the form above. Match the name on the bill before you use a county list. A Powdersville address can sit next to a different water system.

Section 2.2 says testers of devices in this system are certified by SCDES and in good standing with SCDES. It says Powdersville Water may check the tests, and that a tester whose records it determines were falsified will be banned from work in the system and reported to SCDES’s Cross Connection Control Department.

Official links are on Resources.

Anderson County testers Powdersville Water cross-connection policy

Sources checked November 3, 2026: the Cross-Connection Policy PDF linked from the Powdersville Water builders and developers page (cover “Revised September 2024”; path dated 2024/10), including sections 1, 2, 3.4, 3.5, 5, 6, 7, 8, 10, 11, 12, 14, and 15, the definitions, the introduction’s quotation of the state rule, and Appendix A; the PDF linked from the February 4, 2017 cross-connection article (path dated 2024/05; cover “Revised March 2024”), Appendix A only, for the older test-per-unit amounts; that February 4, 2017 article; the private-wells page dated February 4, 2017; the about page; the service-area page; the contact page, including both hour lines, the telephone, the fax, and option 4; the customer-forms page; the Backflow Device Test page (modified time July 18, 2023) and the Backflow Device Test Report form that page loaded; and the SCDES drinking-water record for Powdersville Water District, SC0420002, including the principal county and the water-purchases table. Section 02772 of the water-system guidelines and Appendix I of the development policy were named in the September policy and were not restated here. The builders page links both of those PDFs.