Bypass and parallel backflow assemblies in Upstate SC
A pipe around a backflow assembly, a second assembly in parallel, and the small bypass on a fire-line detector are three different arrangements. The state list and the Upstate manuals print a separate rule for each one.
Sources checked November 13, 2026.
If this page and the letter on your account disagree, follow the letter and the manual it cites. What is a backflow preventer is the device on the service. Where a new assembly is placed is on Backflow preventer installation. Who arranges a repair, and the test right after that repair, is on Backflow preventer repair.
A bypass arrangement is a cross connection
Definition (40) in R.61-58 says a cross connection is any actual or potential connection or structural arrangement between a public water supply and any other source or system through which it is possible to introduce into any part of the potable system any used water, industrial fluid, gas, or substance other than the intended potable water. The same definition says bypass arrangements, jumper connections, removable sections, swivel or changeover devices, and other temporary or permanent devices through which or because of which backflow can or may occur are cross connections.
R.61-58.7(F) section (1)(b) says no person shall install, permit to be installed, or maintain any cross connection between a public water system and any other non-public water system, sewer, or a line from any container of liquids or other substances, unless an approved backflow prevention device or assembly is installed between the public water system and the source of contamination. Section (F) does not print a separate installation rule for a customer bypass pipe. The annual test of a testable assembly is section (7), on What is backflow testing.
The same regulation file uses the word bypass for treatment-plant piping, including a bypass around softening units and bypass piping on a hydropneumatic storage tank. Those sentences are not a rule for the assembly on a customer service.
The January 1, 2026 state list
The notice headed January 1, 2026 is the list of approved assemblies. The filename on the state site spells “equipment” the way the URL shows.
Item 7 says by-pass piping is not permitted unless the by-pass piping is equipped with an approved backflow prevention assembly similar to the main line assembly. It says that in many instances it will be desirable, or necessary to install two approved backflow prevention assemblies in order that water service will not be interrupted during the testing or repair of the assembly. The same numbered item ends with the sentence “Approved type II assemblies are noted in this listing.” A later heading in the file is “Type II – Double Check Detector Assemblies & Reduced Pressure Detector Assemblies.” That heading is a detector by-pass. The first sentences of item 7 are the service-line rule.
Item 10 says that if a manufacturer markets a prefabricated manifold series, it will be approved as long as both of the assemblies in the manifold are from the approved list. The file prints the word “prefabricate.”
Item 11 describes a detector assembly sold for fire sprinkler systems. That by-pass is part of the assembly the manufacturer ships. It is not the service-line by-pass in the first sentences of item 7.
- Item 11 says a Type I double check detector assembly or reduced pressure detector assembly has one assembly on the main line and one on the by-pass, and both must be tested. A meter on the by-pass detects water use. The Type I heading says both assemblies are required to be tested when the annual testing is done. The example printed in that sentence is “Mainline Assem. And by-pass Assem.”
- Item 11 says a Type II assembly has one double check or one reduced pressure principle assembly on the main fire line. The by-pass is installed at or near test cock number 3, and that by-pass has a single check valve after the water meter. The Type II heading says that when the annual testing is done, the main line backflow assembly and the single check on the by-pass line should both be tested.
Both headings say the meter on the by-pass line should be read periodically to be of any value. Neither heading prints a reading schedule. Both say the assembly must be assembled by the manufacturer and shipped as a complete unit. A field alteration has to meet the manufacturer’s specifications and/or the letters “USCFCCC&HR” printed in those headings. Item 3 of the same notice names the University of Southern California’s Foundation for Cross Connection Control and Hydraulic Research, in the sentence about a vertical reduced pressure principle assembly.
Which fire system uses a double check and which uses a reduced pressure assembly is on Fire-line backflow. The order for testing a reduced pressure detector assembly is on RPZ testing step by step.
Greenville Water
Section 5-4.4 of the Cross Connection Control Manual says no bypass is permitted around the assembly unless there is an equal backflow prevention assembly in the by-pass. The file properties record a creation date of November 10, 2025.
Section 5-4.6 is a separate item. It says customers with situations that prohibit shutting off the water service to test or repair the assembly should install a backflow prevention assembly in parallel, or install a separate parallel duplicate service line with proper backflow protection.
The definitions section uses “bypass arrangements” inside the cross-connection definition, in the same list of jumpers and removable sections as definition (40). The double detector check definition is a different line: a main-line double check with a small bypass line that includes a double check valve assembly and a meter, used to detect leakage or unauthorized use of water on fire lines. That definition is not section 5-4.4.
On November 12, 2026 a text extract of the manual used the words bypass, by-pass, and parallel only in those definitions and in sections 5-4.4 and 5-4.6. The manual does not print a dollar amount for a second assembly.
Spartanburg Water
Section 9.3, item 2, of the manual revised June 4, 2026 puts Greenville Water’s two items in one numbered item. It says no by-pass is permitted around the assembly unless there is an equal backflow prevention assembly in the by-pass. The same item says customers with situations that prohibit shutting off the water service to test or repair the assembly should install a backflow prevention assembly in parallel, or install a separate parallel duplicate service line with proper backflow protection. The file properties record a creation date of June 5, 2026. The cover line is “Revised 6/4/2026.”
Section 9.6 says no backflow prevention assembly will be removed, by-passed, or downgraded without prior written approval of Spartanburg Water.
Section 6 says service of water to any premises may be discontinued when a backflow prevention assembly required by the manual is not installed, tested, and maintained according to requirements, or if it is found that a backflow prevention assembly has been removed or by-passed, or if an unprotected cross connection exists on the premises. Section 11.3(a) lists three grounds: a required assembly is not installed, tested, and maintained; a backflow prevention device has been removed or by-passed; or an unprotected cross connection exists on the premises and there is inadequate backflow protection at the service connections. It says water service will not be restored until such conditions and defects are corrected. Section 11.3(b) says a written notice will be provided to the customer that water service will be terminated within ten days if the requirements of the policy are not met. Section 11.3(c) says the customer will be responsible for all applicable reconnection fees and charges. It does not print a dollar amount. It says Spartanburg Water will not be liable for damages, losses, or claims arising from discontinuance of water service.
The definitions section’s cross-connection sentence includes bypass arrangements. The double detector check definition is a small by-pass line that includes a double check valve assembly and a meter, to detect leakage or unauthorized use of water on fire lines. That definition is not section 9.3.
Anderson
Anderson’s September 2008 policy prints two installation sentences. It does not print the “equal assembly in the bypass” sentence that Greenville Water section 5-4.4 and Spartanburg Water section 9.3 print.
The air-gap paragraph says no branch, tap, tee, bypass, or any other connection that may allow a substance to enter or exit the water line shall be installed between the meter and the air gap.
The device-installation list says no branch, tap, tee, wye (“Y”), bypass, or any other connection that may allow a substance to enter or exit the water line shall be installed between the meter and the device. That list does not print a parallel-assembly sentence.
A later bullet, under the heading “Unacceptable Practices,” says Electric City Utilities will not allow anything not associated with the testing and/or maintenance of a device to be permanently or temporarily connected to the test cocks. The prohibited items include hose bib connections, pressure gauges, hose pipes, and bypass piping. If Electric City Utilities personnel discover that, water service to that account will be terminated in accordance with the policy. That bullet is piping on a test cock. It is not section 5-4.4 of the Greenville Water manual.
The definitions section counts bypass arrangements as cross connections. A double detector check valve assembly is an approved double check with a bypass installed on the assembly. The bypass will have an approved double check valve assembly and may have a meter. A reduced pressure principle detector assembly is an approved reduced pressure assembly with a bypass that will have an approved reduced pressure assembly and may have a meter. Greenville Water’s and Spartanburg Water’s double detector check definitions say the small bypass includes a meter. Anderson’s definitions say the bypass may have a meter. Fire-line backflow is the fire-line case. The policy does not print a dollar amount for a bypass or for a second assembly.
Powdersville Water
Section 8 of the cross-connection policy revised September 2024 is headed “Installations Requiring Continuous Service: Parallel Installation.”
It says assemblies with test cocks are tested once per year, every 12 months, at a minimum. It says testing may require a water shutdown usually lasting five to twenty minutes. For facilities that require an uninterrupted supply of water, and when it is not possible to provide water service from a separate meter, provisions shall be made for a “parallel installation” of backflow prevention assemblies. During testing of parallel installations, one assembly is left on while the other is being tested. The section says Powdersville Water will not accept an unprotected bypass around a backflow preventer.
The same section says multi-story buildings which have a number of flushometer toilets should be equipped with parallel assemblies. It says experience has shown that if the water supply is shut off to this type of building, flushometers may have to be manually reset. That sentence is the policy’s. It is not a count from this site.
The five-to-twenty-minute sentence is that shutdown. It is not a duration printed in R.61-58.7(F). The rest of the policy, including who tests, is on Powdersville Water. Section 8 does not print a dollar amount for the parallel assemblies.
City of Westminster
Section 8 of the Cross-Connection Control Policy revised September 12, 2024 uses the same heading, “Installations Requiring Continuous Service: Parallel Installation.” The policy is in the November 12, 2024 council packet.
It says assemblies with test cocks are tested once per year, every 12 months, at a minimum, and that testing may require a water shutdown usually lasting five to twenty minutes. Where an uninterrupted supply is required and a separate meter is not available, the section requires a parallel installation. One assembly stays on while the other is tested. The city will not accept an unprotected bypass. The flushometer example is the policy’s sentence. The five-to-twenty-minute line is that shutdown. It is not a duration in R.61-58.7(F).
The double detector check definition says those devices cannot be used in new installations. That definition is the fire-line bypass. It is not section 8. The rest of the policy is on City of Westminster. Section 8 does not print a dollar amount for the parallel assemblies.
These sections do not print a price
The January 1, 2026 notice, Greenville Water sections 5-4.4 and 5-4.6, Spartanburg Water sections 6, 9.3, 9.6, and 11.3, Anderson’s installation section and the test-cock bullet, Powdersville Water section 8, and Westminster section 8 do not print a dollar amount for a second assembly, a manifold, or a bypass pipe. Spartanburg Water’s reconnection fees in section 11.3(c) are named and not priced. The cost guide keeps a third-party range for a backflow test a customer hires. That range is not a price for this work.
A county list on this site is the SCDES General Tester report. It is the list for a test of a testable assembly. It is not a list of contractors who install a parallel line, and a row is not an appointment. Start with Greenville County, Spartanburg County, or Anderson County only when the letter is about the test. General vs Limited is the card.
If the utility is not one of these
Bypass sentences already on this site for other Upstate systems stay on those pages: Seneca Light & Water, Easley Combined Utilities, SJWD, Blue Ridge Rural Water, and Laurens. Greer CPW’s sentence on removing or bypassing an assembly is on Greer CPW. This page does not add a bypass rule for a utility whose file is not cited here. Use the letter on the account. Official links are on Resources.
Where the assembly goes Fire-line detector bypass
Sources checked November 12, 2026: R.61-58 on des.sc.gov, including definition (40) and R.61-58.7(F); the notice of approved backflow prevention assemblies headed January 1, 2026, items 3, 7, 10, and 11, and the Type I and Type II headings; Greenville Water’s November 10, 2025 manual, the definitions and sections 5-4.4 and 5-4.6; Spartanburg Water’s manual revised June 4, 2026, the definitions and sections 6, 9.3, 9.6, and 11.3; Anderson Electric City’s September 2008 policy, the air-gap paragraph, the device-installation list, the unacceptable-practices bullet, and the detector definitions; and Powdersville Water’s September 2024 policy, section 8. Westminster’s section 8 and the double detector check definition were checked November 13, 2026 in the Cross-Connection Control Policy revised September 12, 2024, printed in the November 12, 2024 council packet.